Ground Fault Circuit Protection

Ground Fault
Circuit Protection
www.carlingtech . com
Transforming Customer Needs into Customer Solutions
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! By working closely with a customer’s product team and
understanding the requirements of the specific application, Carling’s product experts can tailor switching
and circuit protection solutions to meet any customer’s needs—cost effectively.
Since the company was founded in 1920, there are few products that Carling Technologies hasn’t
turned “ON” and fewer industries that haven’t turned to Carling for solutions. With five ISO registered
manufacturing facilities and technical sales offices worldwide, Carling now ranks among the world’s largest,
privately owned manufacturers of hydraulic magnetic circuit breakers, thermal circuit breakers, electrical
switches, electronic switches, miniature switches, power distribution centers, digital switching systems and
electronic controls.
Globally, there are over 2,000 employees working for Carling, providing solutions to customers’ application
needs with innovation, value, and world-class service for both standard and custom products. Carling’s
breadth and depth of standard product offerings gives customers literally millions of configuration choices
to meet the demands of its Strategic Markets:
Š Marine
Š Military
Š Renewable Energy
Š Telecom/Datacom
Š Transportation
Additional markets served by Carling products include: Audio Visual, Commercial Food Equipment,
Commercial HVAC, Floor Care, Generators, Industrial Control, Kitchen & Small Appliances, Security Systems,
Test & Measurement equipment, among others.
If the standard product does not meet the application requirements, the engineering team at Carling has
the expertise to customize solutions faster and more creatively thanks in measure to over ninety years of
experience as an innovative company that manufactures a diverse range of products. The Carling Sales,
Service and Engineering teams work closely with the customer’s engineering team to advance a custom
project from initial concept to final design and product release, respecting both quality and cost through
out the process. With extensive field knowledge and resources available, Carling Technologies can ensure
that the products created for the customer are of superior quality from the start, thus avoiding costly
secondary operations or modifications. Carling’s commitment to excellence consistently delivers “Quality by
Design,” the company mission.
Carling has an extensive network of Sales Representatives and Distributors to assist with Carling products,
or contact a Carling Technologies’ Technical Sales Representative to design innovative, cost-effective,
quality engineered solutions that exceed the tough demands of today’s applications.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
Table of Contents
2
PB–Series
8
PC–Series
16
PD–Series
21
Thermal Circuit Breaker - Selector Guide
General Specifications
Dimensional Specifications
Wiring Diagrams
Ordering Scheme
General Specifications
Dimensional Specifications
Wiring Diagrams
Dimensions
Time Delay Curves
Ordering Scheme
General Specifications
Circuit & Terminal Diagrams
Ordering Scheme
GFCI/ELCI
This catalog features Carling Technologies’ current line of GFCIs/ELCIs products, which offer
maximum equipment protection against overload and short circuits.
Carling’s Equipment leakage circuit breakers function as hydraulic/magnetic circuit breakers,
offering customized overload and short circuit protection. In addition, they sense and guard
against faults to ground using innovative electronics technologies. With the exception of small
amounts of leakage, the current returning to the power supply will be equal to the current
leaving the power supply. If the difference between the current leaving and returning through
the earth leakage circuit breaker exceeds the leakage sensitivity setting, the breaker trips and
its LED illuminates. The LED gives a clear indication that the trip occurred as a result of leakage
to ground. This protection helps prevent serious equipment damage and fire.
Typical Applications:
Š Marine
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
2 | PB-Series - Introduction
PB-Series
Ground Fault Circuit Protection
The PB-Series utilizes the hydraulic magnetic principle
which provides precise operation and performance
even when exposed to extremely hot and/or cold
application environments.
The new PB-Series, AC Residual Current Circuit Breaker
with Overcurrent Protection (RCBO), combines the
ground fault protection of a GFCI with the familiar
overcurrent tripping characteristics of a normal circuit
breaker.
These precision mechanisms are temperature stable
and are not adversely affected by temperature
changes in their operating environment. As such,
derating considerations due to temperature variations
are not normally required, and heat-induced nuisance
tripping is avoided.
Features:
Š Overload, short circuit and ground fault protection
in a single package
Š Handle or rocker style actuators
Š Wiping Contacts - Mechanical linkage with twostep actuation – cleans contacts, provides high,
positive contact pressure & longer contact life.
Š A trip-free mechanism, a safety feature which
makes it impossible to manually hold the contacts
closed during overload or fault conditions.
Š A common trip linkage between all poles, another
safety feature, ensures that an overload in one pole
will trip all adjacent poles.
Š Front panel mounting
Š Integral push-to-test button
Benefits:
Increases safety around boats and marinas
Š Protects against electrical shock hazards in
areas near water
Š Protects against defects in wires & conductors
Š Reduces fire and shock hazards from defects in
permanently installed appliances such as water
heaters, battery chargers, lighting fixtures, etc.
Š Detects lower level ground faults which do not
trip ordinary circuit breakers, but can lead to
fires, and shock hazards for boating occupants
Š
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PB-Series Circuit Breaker - General Specifications | 3
RESISTANCE, IMPEDANCE VALUES Mechanical
Electrical Tables
from Line to Load Terminals
Table A: UL Listed configurations and performance capabilities
Endurance
as Circuit Breakers (Values Based on Series Trip Circuit Breaker)
1000
VOLTS
Trip Free
(AMPS)
100 HERTZ
Electrical
Maximum Voltage
Current Ratings
Trip Indication
10
10,000 ON-OFF operations @ 6
per minute; with rated Current and
Voltage.
All PB-Series Circuit Breakers will
trip on overload or ground fault, even
when Handle is forcibly held in the ON
position.
The operating Handle moves
positively to the OFF position when an
overload or ground fault causes the
breaker to trip.
120/240VAC 60 Hz
Standard current coils: 0.100, 0.250,
Physical
O
0.500, 0.750, 1.00, 2.50, 5.00, 7.50,
10.0,
15.0,
20.0,
25.0
&
30.0
amps.
1
H
Number of Poles
1 - 3 poles, where the third pole is
Other ratings available, see ordering
neutral
M
scheme.
Internal Circuit Config. Series Trip
S
Insulation Resistance
Minimum of 100 Megohms at 500
Weight
Approximately 65 grams/pole. (2.32
0.1 VDC.
ounces/pole.)
Dielectric Strength
UL, CUL - 1500 V 60 Hz for one
Standard Colors
Housing- Black; Actuator - See
minute between all electrically isolated
Ordering Scheme.
terminals. PB-Series circuit breakers
0.01
comply with the 8mm spacing and
Environmental
3750V 60 Hz dielectric requirements
Designed and tested in accordance with requirements of
from hazardous voltage to operator
specification MIL-PRF- 55629 and MIL-STD-202 as follows:
0.001 accessible surfaces and between
Withstands 100 Gs, 6ms, sawtooth while
0.1poles
1
10
100 Shock
adjacent
RESISTANCE, IMPEDANCE 0.01
VALUES
carrying rated current per Method 213,
from
Line
to
Load
Terminals
Impedance
Values from Line to Load Terminal.
AMPERE RATING
(Values Based on Series Trip Circuit Breaker)
Test Condition “I”. Ultra-short curves
1000
Ampere Rating
tested @ 90% of rated current.
Vibration
Withstands 0.060” excursion from
CURRENT
TOLERANCE
(AMPS)
(%)
100
10-55 Hz, and 10 Gs 55-500 Hz, at
0.100 - 5.0
± 15%
rated current per Method 204C, Test
5.1 - 20.0
± 25%
10
Condition A. Instantaneous and
20.1 - 30.0
± 35%
ultrashort curves tested at 90% of rated
O
FIGURE 1
1
H
current.
Pulse
Tolerance
Curve
M
Method 106D, i.e., ten 24-hour cycles @
Moisture Resistance
S
+ 25°C to +65°C, 80-98% RH.
0.1
Method 101, Condition A (90-95% RH @
Salt Spray
5% NaCl Solution, 96 hrs).
0.01
Thermal Shock
Method 107D, Condition A (Five cycles
@ -55°C to +25°C to +85°C to +25°C).
0.001
0.01
0.1
1
10
100
Operating Temperature -35° C to +65° C
AMPERE RATING
Corrosion
Tested per UL943 FMG Test. 3 weeks @
30°C 75% RH, 100ppb H2S, 20ppb CI2,
Leakage To Ground
200ppb NO2
Standard Must Trip
FIGURE 1
Leakage Current Ratings 5 & 30 milliamps.
Agency Certifications
5± 1mA for UL943, other leakage
UL Listed
ratings test to UL1053.
Circuit Breakers, Molded Case,
UL Standard 489
For other ratings, consult factory.
(Guide DIVQ, File E129899)
Trip Time
300 ms Max. @ 100%, 40ms Max. @
Supplementary Protectors
UL Standard 1077
500% of must trip leakage current.
Class A Ground Fault Circuit Interruptors
UL Standard 943
Test Button
On unit face along side of actuator.
Ground Fault Sensing and Relaying
UL Standard 1053
Equipment
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
Multiple of
Rated Current
Ir
Time Delay Curves
22, 24, 26
12x
t
4.165
CURRENT
(AMPS)
TOLERANCE
(%)
0.100 - 5.0
± 15%
20.1 - 30.0
± 35%
5.1 - 20.0
8.33
16.67
Time in
Milliseconds
± 25%
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
4 | PB-Series – Dimensional Specifications
INDICATE "ON"
1.515 MAX
[38.48]
3.03
[76.9]
INDICATE
"OFF"
AND
SINGLE
COLOR
LINE
.21
[5.3]
1.25
[31.6]
TEST
LOAD
2.17
[55.0]
LOAD
1-POLE 120 VAC VERSION
TEST
LINE
SCALE
0.500
#6-32/M3 MOUNTING INSERTS
1.88
[47.8]
LINE TERMINAL
2.265 MAX
[57.53]
1.660
[42.16]
2.58
[65.6]
TEST
2.37
[60.2]
+.020
1.500
-.000
+.50
38.10
-.00
[
.375
[9.53]
.39
[9.9]
CURRENT TRANSFORMERS
LOAD TERMINAL
1.260
[32.00]
GFCI NEUTRAL WIRE
2-POLE 120/240 VAC VERSION
.20
[5.1]
]
.750 TYP
[19.05]
1.660
[42.16]
SCALE 0.500
+.020
2.250
-.000
+.50
57.15
-.00
[
Ø .156 TYP
[3.96]
]
PANEL CUTOUT
NEUTRAL BREAK POLE
3.015 MAX
[76.58]
.750 TYP
[19.05]
TEST
2-POLE 120/240 VAC WITH NEUTRAL BREAK
Notes:
1
All dimensions are in inches [millimeters].
2
Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PB-Series – Dimensional Specifications | 5
Notes:
1
All dimensions are in inches [millimeters].
2
Tolerance ±.020 [.51] unless otherwise specified.
Time Delay Curves
Instantaneous
Medium
Short
Long
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
6 | PB-Series – Wiring Diagrams
120VAC without Switched Neutral
120VAC with Switched Neutral
SYSTEM NEUTRAL
SYSTEM NEUTRAL
GFCI
MODULE
PIGTAIL
GFCI
MODULE
PIGTAIL
LOAD
HOT
LOAD
NEUTRAL
LOAD
HOT
LINE/SOURCE
(HOT)
LINE/SYSTEM
NEUTRAL
LINE/SOURCE
(HOT)
120 VAC
LOAD
120 VAC
LOAD
AC SOURCE
AC SOURCE
120 VAC WITHOUT SWITCHED NEUTRAL
120 VAC WITHOUT SWITCHED NEUTRAL
120 VAC WITH SWITCHED NEUTRAL
120 VAC WITHOUT SWITCHED
NEUTRAL
120/240VAC with Switched Neutral
120/240VAC without Switched Neutral
SYSTEM
NEUTRAL
SYSTEM
NEUTRAL
GFCI
MODULE
PIGTAIL
GFCI
MODULE
PIGTAIL
LOAD
HOT
1
LINE/SOURCE 1
120 VAC
LOAD
120 VAC
LOAD
LOAD
HOT
2
LINE/
SOURCE
2
LOAD
HOT
1
LOAD
NEUTRAL
LINE/SYSTEM
NEUTRAL
120 VAC
LOAD
120 VAC
LOAD
LINE/SOURCE
(1)
LOAD
HOT
(2)
LINE/
SOURCE
(2)
240 VAC LOAD
240 VAC LOAD
AC SOURCE
AC SOURCE
120 VAC WITHOUT SWITCHED NEUTRAL
120/240 VAC WITH SWITCHED NEUTRAL
120 VAC WITHOUT SWITCHED NEUTRAL
120/240 VAC WITHOUT SWITCHED NEUTRAL
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PB-Series – Ordering Scheme | 7
PB A — B A — 24 — 620 — 2 B A — A G
1
Series
3
Circuit
2
System
Voltage/Poles
4
Actuator
5
Frequency
& Delay
13
2
3
4
5
2 SYSTEM VOLTAGE / POLES
120 VAC single phase, one pole
120/240 VAC single phase, two pole
120/240 VAC single phase with switched neutral, three pole
120 VAC two pole with switched neutral
3 CIRCUIT
B
8
Actuator
Color
7 TERMINAL2
1 SERIES
PB
A
B
C
D
7
Terminal
6
Current Rating
Series Trip (Current)
4 ACTUATOR1
Handle
A
one per pole
B
one per multipole unit
Two Color Curved Visi-Rocker
C
Indicate ON,
vertical legend
D
Indicate ON,
horizontal legend
F
Indicate OFF,
vertical legend
G
Indicate OFF,
horizontal legend
Single Color Curved Rocker
J
Vertical legend
K
Horizontal legend
Two Color Flat Visi-Rocker
1
Indicate OFF,
vertical legend
2
Indicate OFF,
horizontal legend
Single Color Flat Rocker
3
Vertical legend
4
Horizontal legend
Push-On 0.250 Tab (Q.C.)
Screw 8-32 w/upturned lugs
Screw 8-32 (Bus Type)
Screw 10-32 w/upturned lugs
Screw 10-32 (Bus Type)
8 ACTUATOR COLOR & LEGEND
Acuator Color
I-O
White
A
Black
C
Red
F
Green
H
Blue
K
Yellow
M
Gray
P
Orange
R
9 MOUNTING/BARRIERS
A
B
MOUNTING STYLE
Threaded Insert, 2 per pole
6-32 X 0.195 inches
ISO M3 x 5mm
9
Mounting/
Barriers
B
C
E
H
ON-OFF
B
D
G
J
L
N
Q
S
10
Trip Level
11
Agency
Approval
Screw M5 w/upturned lugs
Screw M4 w/upturned lugs
Screw M4 (Bus Type)
Screw M5 (Bus Type)
Dual
1
2
3
4
5
6
7
8
Legend Color
Black
White
White
White
White
Black
Black
Black
BARRIERS
yes
yes
10 LEAKAGE CURRENT TRIP LEVEL - MAX. TRIP CURRENT
A 5 MA (CLASS A GFCI)3,4,5
E 30 MA (ELCB)
11 AGENCY APPROVAL
UL489 Listed, CSA Certified
G
UL1077
C
UL1077/UL1500 Ignition Protected, CSA Certified6
I
Notes:
1
Actuator Code:
A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units.
B: Handle location as viewed from front of breaker:2 pole - left pole 3 pole - center pole
2
Screw Terminals are recommended on ratings greater than 20 amps.
3
Available with leakage current trip level - Max trip current code E, and agency approval C.
4
6mA per UL943, available with agency approval code G.
5
30mA per UL1053, available with agency approval codes C & G.
6
UL1500 only available with 30MA trip level.
5 FREQUENCY & DELAY
22
24
26
60Hz Short
60Hz Medium
60Hz Long
6 CURRENT RATING (AMPERES)
CODE
210
215
220
225
230
235
240
245
250
255
260
265
270
275
280
AMPERES
0.100
0.150
0.200
0.250
0.300
0.350
0.400
0.450
0.500
0.550
0.600
0.650
0.700
0.750
0.800
285
290
295
410
512
415
517
420
522
425
527
430
435
440
445
0.850
0.900
0.950
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
3.000
3.500
4.000
4.500
450
455
460
465
470
475
480
485
490
495
610
710
611
711
612
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
10.000
10.500
11.000
11.500
12.000
712
613
614
615
616
617
618
620
622
624
625
630
12.500
13.000
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
8 | PC-Series - Introduction
PC-Series
Ground Fault Circuit Protection
The PC-Series, AC Residual Current Circuit Breaker with
Overcurrent Protection (RCBO), combines the ground
fault protection of a GFCI with the familiar overcurrent
tripping characteristics of a normal circuit breaker.
The PC-series utilizes the hydraulic magnetic principle
which provides precise operation and performance
even when exposed to extremely hot and/or cold
application
environments.
Features:
Š Overload, short circuit and ground fault protection
in a single package
Š Handle style actuators and rocker style “acuguard”
Š Wiping Contacts - Mechanical linkage with twostep actuation – cleans contacts, provides high,
positive contact pressure & longer contact life
Š A trip-free mechanism, a safety feature which
makes it impossible to manually hold the contacts
closed during overload or fault conditions.
Š A common trip linkage between all poles, another
safety feature, ensures that an overload in one pole
will trip all adjacent poles.
Š Front panel mounting
Š Integral push-to-test button
Š Two integrated LED indicators distinguish if a
breaker is closed with Line Voltage present, or has
opened due to leakage current, or has opened due
to over current, or is closed with no Line Voltage
present.
Š Optional Hot/Neutral reversal detection and
protection
Benefits:
Increases safety around boats and marinas
Š Protects against electrical shock hazards in
areas near water
Š Protects against defects in the wires &
conductors
Š Reduces fire and shock hazards from defects in
permanently installed appliances such as water
heaters, battery chargers, lighting fixtures, etc.
Š Detects low level ground faults, which do not
trip ordinary circuit breakers, that can lead to
fires and shock hazards for boating occupants
Š
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PC-Series Circuit Breaker - General Specifications | 9
Electrical Tables
Table A: Lists UL Listed configurations as a Ground Fault Circuit
Interruptor
PC SERIES TABLE A : LISTS UL LISTED CONFIGURATIONS AS A GROUND FAULT CIRCUIT INTERRUPTOR
CURRENT SHORT CIRCUIT
RATING
CAPACITY
VOLTAGE
CIRCUIT
CONFIGURATION
MAX.
RATING
SERIES
FREQUENCY PHASE
GROUND
FAULT TRIP
LEVEL
AMPS
AMPS
MILLIAMPS
120
50 / 60
1
1 - 50
5000
6
1 or 2 Poles. One pole of a two pole unit must be Neutral
NOTES
120/240
50 / 60
1
1 - 50
5000
6
2 or 3 Poles. One pole of a three pole unit must be Neutral
Table B: Lists UL Listed and Recognized as an Earth Leakage
Circuit Interruptor - 120 and 120/240V
PC SERIES TABLE B : LISTS UL LISTED AND RECOGNIZED CONFIGURATIONS AS AN EARTH LEAKAGE CIRCUIT INTERRUPTOR - 120 and 120/240V
GROUND
CURRENT SHORT CIRCUIT
VOLTAGE
FAULT TRIP
RATING
CAPACITY
LEVEL
CIRCUIT
MAX.
FREQUENCY PHASE
AMPS
MILLIAMPS
NOTES
AMPS
CONFIGURATION
RATING
120
120/240
50 / 60
50 / 60
1
1
1 - 50
1 - 50
5000
5000
30
30
1 or 2 Poles. One pole of a two pole unit must be Neutral
2 or 3 Poles. One pole of a three pole unit must be Neutral
SERIES
120
50 / 60
1
1 - 50
3000
30
1 or 2 Poles. One pole of a two pole unit must be Neutral
IGNITION PROTECTED
120/240
50 / 60
1
1 - 50
5000
30
2 or 3 Poles. One pole of a three pole unit must be Neutral
SERIES
Table C: Lists UL Listed and Recognized as an Earth Leakage
Circuit Interruptor - 240V
PC SERIES TABLE C : LISTS UL LISTED AND RECOGNIZED CONFIGURATIONS AS AN EARTH LEAKAGE CIRCUIT INTERRUPTOR - 240V
GROUND
CURRENT SHORT CIRCUIT
VOLTAGE
FAULT TRIP
RATING
CAPACITY
LEVEL
CIRCUIT
MAX.
FREQUENCY PHASE
AMPS
AMPS
MILLIAMPS
NOTES
CONFIGURATION
RATING
SERIES
240
50 / 60
1
1 - 30
5000
30
2 or 3 Poles. One pole of a three pole unit must be Neutral. Suffix 11
SERIES IGNITION PROTECTED
240
50 / 60
1
1 - 50
3000
30
2 or 3 Poles. One pole of a three pole unit must be Neutral. Suffix 12
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
10 | PC-Series Circuit Breaker - General Specifications
Mechanical
Electrical
Current Ratings
Voltage Rating
Current Trip Level
Current Trip Time
Operating Frequency
Interrupt Capacity
1 - 50 Amps maximum
120VAC, 120/240VAC, 240VAC
30mA & 6mA
For 30mA leakage trip:
≤ 22.2mA, shall not trip
30mA, shall trip within .10 seconds
The above complies with UL-1053
& ABYC E11. For 6mA leakage
trip: ≤25ms
The above complies with UL-943.
50/60 Hz for 30mA leakage trip
60 Hz for 6mA leakage trip
5,000 Amps
Endurance
Trip Free
10,000 ON-OFF operations @ 6
per minute; with rated Current and
Voltage.
Trips on short circuit, overload or
leakage to ground, even when
actuator is forcibly held in the “On”
position
Physical
Number of Poles
(Breakers only)
Impedence
Termination
20.1 - 50.0
Mounting
Actuator
1-pole (1 Circuit Breaker + 1
GFCISensor Module), 120V
2-pole (2 Circuit Breakers + 1 GFCI
Sensor Module), 120/240V or 120V
with Neutral Break. 240VAC two pole
3-pole 120/240V with Neutral Break
(Sensor module has 2 pole width)
Circuit Breaker Line Side: #10-32,
Threaded stud.
GFCI Sensor Module Load Side: #1032 threaded stud. Neutral pigtail.
Front Panel, #6-32 and M3 threaded
inserts.
Handle, Flat Rocker, Curved Rocker
(with or without rocker guard),
Push-to-Reset Rocker
Environmental
Innovative Features
Indicator
Two integrated LEDs, Red & Green
Neutral Protection
Test Button
Š Green LED On, Red LED Off
Line Voltage is present, the
breaker is closed, and the device
is protecting the circuits against
over current and leakage current.
Š Green LED Off, Red LED On
The device has detected leakage
current and has opened the cicuit
breaker.
Š Green LED Flashing, Red LED Off
The circuit breaker has opened due
to over current or has been turned off
manually
Š Green LED Off, Red LED Off
Line Voltage is not present
Š Green LED Flashing, Red LED
Off, Amber LED ON
Indicates Hot & Neutral are reversed
and the circuit breaker is open
When neutral is grounded on load
side of circuit
Located on Ground Fault Module
*Manufacturer reserves the right to change product specification without prior notice.
Designed and tested in accordance with requirements of
specification MIL-PRF- 55629 and MIL-STD-202G as follows:
Shock
Withstands 100 G, 6ms, sawtooth at
rated current per Method 213, Test
Condition “I”.
Vibration
Withstands 0.06” excursion from 1055 Hz, and 10 G 55-500 Hz, at rated
current per Method 204C, Test Condition
A. Instantaneous and ultrashort curves
tested at 90% of rated current.
Moisture Resistance
93% RH at 30°C for 168 Hours.
Operating Temperature -35°C to +66°C
Corrosion
UL-943-6.21, 3 weeks
Humidity:
30±2°C, 70±2% relative humidity
Mixed Flowing Gases:
100 ppb H2S, 20 ppb CI2,
200±50 ppb NO2
Agency Certifications
UL Listed
UL Standard 489
UL Standard 1077
UL Standard 943
UL Standard 1053
UL Standard 1500
Circuit Breakers, Molded Case,
(Guide DIVQ, File E129899)
Supplementary Protectors
Class A Ground Fault Circuit
Interruptors
Ground Fault Sensing and Relaying
Equipment
Ignition Protection
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PC-Series – Wiring Diagrams | 11
1
2
INDICATE OFF / SINGLE COLOR
ROCKER ACTUATOR
3
HANDLE / INDICATE ON
ROCKER ACTUATOR
4
TERMINAL
LOCATIONS
I
D
PCE
120 VAC VERSIO
W/ REVERSE POLA
INDICATOR
PCA
120 VAC
VERSION
C
PCF
120/240 VAC VERSIO
W/ REVERSE POLARI
INDICATOR
PCB
120/240 VAC
VERSION
3.015
[76.58]
MAX.
B
PCC
120/240 VAC
VERSION
W/ NEUTRAL BREAK
3.775
[95.88]
MAX.
A
PCD
120 VAC
VERSION
W/NEUTRAL BREAK
1
2
3
4
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PC-Series ELCI/RCBO Instruction Bulletin
12 | PC-Series – Wiring Diagrams & Panel Cut Out
s voltage. Can cause death or serious injury. Turn off
upply before installing PC-Series ELCI/RCBO.
3.
st a line to line fault
e of the
4
est instructions
RMINAL
CATIONS
ed applications.
osures.
or hi-pot test.
efore hi-potting
Sect. 550-12, NEC).
ons.
4.
5.
Depress the “TEST” button. This will cause the actuator to
move to the “OFF” position and the red LED to turn on and
5
6
show steady illumination, indicating that the ELCI/RCBO is
functioning properly. The green LED will also go from
steady to off. If the actuator fails to move to the “OFF”
HANDLE
/ INDICATE ON
INDICATE
SINGLE
COLOR the
position or
the red OFF
LED /fails
to illuminate,
unit MUST
ROCKER ACTUATOR
ROCKER ACTUATOR
be replaced.
Turn the ELCI/RCBO actuator to the “ON” position. The
red LED should turn off and only the green LED should be
illuminated.
This test is to be performed on a monthly basis and
recorded on the “Monthly Test Reminder” label.
7
8
DRAWING FILE NO.
DWG REV
CLA-8112
TERMINAL
LOCATIONS
01
REVISIONS
REV
DESCRIPTION
DATE
X
X
X
PCE
WHEN
ELCI/RCBO TRIPS:
120
VAC VERSION
The PC-Series
ELCI/RCBO opens the circuit when there is an
W/ REVERSE
POLARITY
over
current or ground fault condition. If the red LED is
INDICATOR
ed by a qualified
continuously illuminated the tripping is due to a ground fault
condition. If the green LED is flashing, the tripping is due to an
over current:
1. Some faults are self-clearing. Try resetting the breaker
once.
2. If this device is installed as a main breaker, turn off all
branch breakers and reset the breaker. If it does not trip,
turn branch breakers on one at a time to locate the fault.
3. If the breaker continues to trip with the branch breakers off
recheck that the neutral is not grounded on the load side
of the ELCI circuit breaker.
4. If the breaker continues to trip, but no grounding of the
PCF
neutral
is observed, disconnect all load side connections
120/240 VAC
VERSION
and
reset the breaker. If the breaker still trips with no load
W/ REVERSE
POLARITY
connections in place, the breaker may be defective.
INDICATOR
5. If the breaker does not trip with the loads disconnected but
does trip when the loads are connected, the device is
performing its intended protection function, which means
that a hazardous condition could exist. A qualified
electrician should be called to evaluate the circuit and
perform more advanced troubleshooting if the problem
cannot be located.
r to enclosure in
d.
tor.
wires to the Load
Fig. A for terminal
e wires directly to
ce Terminals.
and mount front
eaker actuator.
nstructions.
el in a convenient
d instruct equipment
mportance of
tests.
Turn on the power
e flashing and the
he green “POWER”
nd the red
n off.
NOTE: NEUTRAL & GROUND PIGTAIL WIRES - SUPPLIED 12" LONG MIN. (CIRCUIT CODES A,B,E & F)
PANEL CUTOUT HANDLE
PANEL CUTOUT ROCKER
LOAD NEUTRAL
3.790 [96.27]
3.040 [77.22]
3.040 [77.22]
2.280 [57.91]
LINE 1
.156 DIA. [Ø3.96]
2 PLC'S. TYP.
PER POLE
1.660 [42.16]
1.453 [36.91]
SOURCE
NEUTRAL
LINE 2
2.280 [57.91]
LINE 1
1.260 [32.00]
LINE 2
MATERIAL:
2.062 [52.37]
ASSEMBLY
FINISH:
DRAWING INTERPRETATIONS
.200 [5.08]
SOURCE
NEUTRAL
HOT 2
LINE 2
OAD HOT 1
LINE 1
.432 [10.97]
.750 [19.05]
TYP.
LOAD HOT 2
OR 230V NEUTRAL
LOAD HOT 1
PCA
PCB, PCD & PCE
1-Phase 240VAC
IST-0010
Rev. C
FRAC.
± 1/64 [0.4]
ANGLES ± 1 °
CHECKED BY:
SCALE
DRAWN BY:
DATE DRAWN:
0.750
04-May-10
SIZE
APPROVED BY:
DATE APPROVED:
D
DO NOT SCALE DRAWING
TITLE
ROCKER ACTUATOR
NOTICE TO ALL PERSONS RECEIVING THIS
CARLING TECHNOLOGIES, INC. AND IS NOT TO BE
DISCLOSED, REPRODUCED IN WHOLE OR IN
PART OR USED FOR MANUFACTURING PURPOSES
BY ANYONE WITHOUT THE CONSENT OF
CARLING TECHNOLOGIES, INC.
6
± .005 [0.13]
± .01 [0.25]
TAF
TOLERANCES
±.005
DRAWING.
THIS[.12]
DOCUMENT IS THE PROPERTY OF
5
X.XXX
X.XX
MODELED BY:
PANEL CUTOUT
DETAILNOTICE
PROPRIETARY
4
UNSPECIFIED TOLERANCES
1
HANDLE ACTUATOR
1-Phase 120 / 240 VAC
with Neutral Switching
DIMENSIONS
INCHES
[MILLIMETERS]
PCC & PCF
LINE 2
OR 230V NEUTRAL
PCC & LINE
PCF
PROJECTIONS
PCA, PCB
PCD & PCE
C SERIES ELCI ASSEMBLY
CONTROL SYMBOLS
.XXX
CRITICAL DIM.
CRITICAL CHAR.
TOOL NO.
REV.
X
REFERENCE NO.
PR5055-400
INTRALINK MODEL
Carling Technologies
Innovative Designs, Powerful Solutions
DRAWING FILE NO.
DRAWING VERSION
INTRALINK MODEL REVISION/VERSION
CLA-8112
1
01.16
PRODUCT SERIES: C
PR5055-400-12
7
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
DRAWING REV.
01
SHEET 5 OF 5
8
PC-Series – Dimensions | 13
1
2
3
4
5
2.265
[57.53]
MAX.
1.510
[38.35]
2.975
[75.57]
0.430
[10.92]
0.275
[6.99]
0.750
TYP.
[19.05]
2.518
[63.96]
2.062
[52.37]
3.800
[96.52]
1.453
[36.91]
0.429
[10.91]
0.350
[8.89]
NEUTRAL PIGTAIL (CIRCUIT
CODE A+B ONLY)
#6/32 / M3 MOUNTING INSERTS
0.125
[3.18]
1.245
1.660 [31.62]
[42.16]
0.208
[5.28]
0.100
[2.54]
1
2
3
4
5
Notes:
For additional circuit breaker dimensions, reference the C-Series Breakers in the
Carling Circuit Protection catalog
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
14 | PC-Series –Time Delay Curves
Time Delay Curves
Instantaneous
Medium
Ultra Short
Long
Short
Notes:
Other time delay values available, consult factory.
Delay Curves 21,22,24,26: Breakers to hold 100% and must trip at 125% of rated
current and greater within the time limit shown in this curve.
Delay Curve 20: Breakers to hold 100% and must trip at 150% of rated current
and greater within the time limit shown in this curve.
All Curves: Curve data shown represents breaker response at ambient temperature of 77°F (25°C) with no preloading. Breakers are mounted in standard
wall-mount position.
The minimum inrush pulse tolerance handling capability is 12 times the rated current. These values are based on a 60 Hz 1/2 cycle, 8.33 ms pulse.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PC-Series – Ordering Scheme | 15
PC B — B A — 24 — 620 — 1 B A — A 10
1
Series
2
System
Voltage/Poles
3
Circuit
4
Actuator
5
Frequency
& Delay
1 SERIES
PC
120 VAC single phase, one pole
120/240 VAC single phase, two pole
120/240 VAC single phase with switched neutral, three pole
120 VAC single phase with switched neutral, two pole
120 VAC single phase with reversed polarity indicator, two pole
120/240 VAC single phase with reversed polarity indicator, three pole
240 VAC single phase, two pole
3 CIRCUIT
B
Series Trip (Current)
4 ACTUATOR
Handle
A
one per pole
B
one per multipole unit
Two Color Curved Visi-Rocker
C
Indicate ON,
vertical legend
D
Indicate ON,
horizontal legend
F
Indicate OFF,
vertical legend
G
Indicate OFF,
horizontal legend
Single Color Curved Rocker
J
Vertical legend
K
Horizontal legend
Two Color Curved Visi-Rocker
Push-to-Reset
N
Vertical legend
O
Horizontal legend
Single Color Curved Rocker
Push-to-Reset
R
Vertical legend
U
Horizontal legend
Two Color Flat Visi-Rocker
1
Indicate OFF,
vertical legend
2
Indicate OFF,
horizontal legend
Single Color Flat Rocker
3
Vertical legend
4
Horizontal legend
Two Color Flat Visi-Rocker
Push-to-Reset
5
Indicate OFF,
vertical legend
6
Indicate OFF,
horizontal legend
Single Color Flat Rocker
Push-to-Reset
7
Vertical legend
8
Horizontal legend
210
215
220
225
230
235
240
245
250
255
260
265
270
275
280
9
Mounting/
Barriers
10
Trip Level
11
Agency
Approval
1
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
Notes:
1
This device meets the requirements of ABCY E11.
2
6mA per UL943, available with agency approval code 10.
3
30mA per UL1053, available with agency approval codes 11 & 12.
4
AIC Rating at 120 VAC 3kA, at 120/240 VAC 5kA
0.100
0.150
0.200
0.250
0.300
0.350
0.400
0.450
0.500
0.550
0.600
0.650
0.700
0.750
0.800
285
290
295
410
512
415
517
420
522
425
527
430
435
440
445
0.850
0.900
0.950
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
3.000
3.500
4.000
4.500
450
455
460
465
470
475
480
485
490
495
610
710
611
711
612
712
613
614
615
616
617
618
620
622
624
625
630
635
640
650
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
10.000
10.500
11.000
11.500
12.000
12.500
13.000
14.000
15.000
16.000
17.000
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
50.000
Stud, 10-32 threaded
8 ACTUATOR COLOR & LEGEND
Acuator Color
I-O
White
A
Black
C
Red
F
Green
H
Blue
K
Yellow
M
Gray
P
Orange
R
9 MOUNTING/BARRIERS
A
B
E
F
5 FREQUENCY & DELAY
AMPERES
7 TERMINAL
C
D
20
21
22
24
26
8
Actuator
Color
6 CURRENT RATING (AMPERES)
CODE
2 SYSTEM VOLTAGE / POLES
A
B
C
D
E
F
G
7
Terminal
6
Current Rating
G
H
ON-OFF
B
D
G
J
L
N
Q
S
Legend Color
Black
White
White
White
White
Black
Black
Black
Dual
1
2
3
4
5
6
7
8
MOUNTING STYLE
Threaded Insert, 2 per pole
6-32 X 0.195 inches
ISO M3 x 5mm
Rockerguard Bezel
Threaded Insert, 2 per pole
6-32 X 0.195 inches
ISO M3 x 5mm
Standard Bezel with Recessed Off-Side Flat Rocker
Threaded Insert, 2 per pole
6-32 X 0.195 inches
ISO M3 x 5mm
Push-to-Reset Bezel
Threaded Insert, 2 per pole
6-32 X 0.195 inches
ISO M3 x 5mm
BARRIERS
yes
yes
yes
yes
yes
yes
yes
yes
10 LEAKAGE CURRENT TRIP LEVEL - MAX. TRIP CURRENT
A 5 MA (CLASS A GFCI)2
E 30 MA (ELCB)1,3
11 AGENCY APPROVAL
AA W/O Approvals
UL 9432
10
UL 10531,3
11
UL 1053 & UL 15001,3,4
12
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
16 | PD-Series - Introduction
PD-Series
Ground Fault Circuit Protection
SmartGuard is an equipment ground fault protection
device that functions as a standard high-quality
Carling hydraulic/magnetic circuit breaker, offering
customized overload and short circuit protection.
In addition, this breaker senses and guards against
faults to ground using a state of the art integrated
circuit developed by Carling. This new technology
detects faults and when a fault occurs, the breaker
trips and an LED illuminates. The LED gives a clear
indication that the trip occurred as a result of leakage.
This protection helps prevent serious equipment
damage and fire.
Agency Certifications:
Features:
Š Overload, short circuit and ground fault protection UL Standard 1077 Component Recognition
in a single package
Program as Equipment
Š Handle style actuators with optional
Leakage Circuit Interrupter
“handleguard”
and, Protectors, Supplementary
Š Wiping Contacts - Mechanical linkage with two(FTTJ2, File E177510).
step actuation – cleans contacts, provides high,
UL Standard 943 Tested as Ground Fault Circuit
positive contact pressure & longer contact life
Interrupters for Equipment
Š A trip-free mechanism, a safety feature which
Protection.
makes it impossible to manually hold the contacts CSA Certified
Component Equipment Leakage
closed during overload or fault conditions.
Current Interrupter with
Š A common trip linkage between all poles, another
Supplementary Protector, under
safety feature, ensures that an overload in one
Class C22.2,No. 144-M91, File
pole will trip all adjacent poles.
LR47848-50
Š Front panel or DIN rail mounting options
TUV Certified
IEC 947-2 and appendix B: Circuit
Š “State of the art” integrated circuit developed by
Breakers incorporating Residual
Carling
Current Protection. Complies
Š Equipment leakage sensitivity from 10 to 100
with waveform requirements of
milliamps
IEC 1008-1, Type A.
Š Integral push-to-test button and LED “tripped”
indicator
Š Immediate reset after fault has been cleared
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PD-Series Circuit Breaker - General Specifications | 17
Electrical Tables
Table A: Lists UL Recognized & CSA Certified configurations
and performance capabilities as a Component Supplementary
Protector.
Table B: Lists TUV Certified configurations and performance
capabilities as a Circuit breaker incorporating residual current
protection.
PD-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTOR & EARTH LEAKAGE CURRENT INTERRUPTER
VOLTAGE
CIRCUIT
CONFIGURATION
SERIES
INTERRUPTING
CURRENT RATING
FULL
GENERAL
LEAKAGE
CAPACITY (AMPS)
CURRENT
UL / CSA
MUST - TRIP
MAX RATING
FREQUENCY
LOAD
PURPOSE
WITHOUT
RATING
VOLTS
HERTZ
PHASE
AMPS
AMPS
BACKUP FUSE
(MILLIAMPS)
120/208
50/60
1
1-50
---
5000
7-100
120/208
50/60
31
1-50
---
5000
7-100
208-240
50/60
3
1-50
---
2000
7-100
480Y
50/60
3
1-30
30.1-50
2000
7-100
Electrical
Mechanical
Maximum Voltage AC, 480 WYE/277 VAC, 50/60 Hz
Endurance
Standard Current Ratings 1.00, 2.50, 5.00, 7.50, 10.0, 15.0,
20.0, 25.0, 30.0, 35.0, 40.0 & 50.0
Trip Free
amps. For other ratings, consult factory.
Insulation Resistance
Minimum of 100 Megohms @ 500 VDC.
Dielectric Strength
1960 VAC, 60 Hz for one minute
between all electrically isolated
terminals.
Trip Indication
Resistance, Impedance From Line to Load Terminal
(Values Based on Series Trip Circuit
Breaker)
RESISTANCE, IMPEDANCE VALUES
from Line to Load Terminals
Ampere Rating
10,000 ON-OFF operations @ 6 per
minute; with rated current and voltage.
All SmartGuard equipment leakage
circuit breakers will trip on overload
or leakage to ground, even when
actuator is forcibly held in the ON
position.
The actuator moves to the OFF
position when an overload or earth
leakage ground fault causes the
breaker to trip. The LED is illuminated
when leakage to ground causes the
circuit breaker to trip.
Physical
20.1 - 50.0
Pulse Tolerance Curve
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
Multiple of
Rated Current
Ir
Time Delay Curves
22, 24, 26
12x
t
4.165
Leakage To Ground
Standard Must Trip
Leakage Current Ratings
Trip Time
Test Button
Leakage Trip Indicator
8.33
16.67
Time in
Milliseconds
Number of Poles
2, 3 & 4
Length (included switched
or unswitched neutral)
4.2 inches ( 106.7 mm)
Width
2-pole: 3.0 inches (76.2 mm)
3-pole: 3.75 inches (95.3 mm)
4-pole: 4.5 inches (114.3 mm)
Depth
2.5inches (63.5mm).
Weight: 2-pole
16.0 oz. (453.6 gm)
3-pole: 21.4 oz. (606.7 gm)
4-pole: 26.9 oz. (762.6 gm)
Standard Colors
Housing - gray;
Actuator - black, red, or white
Mounting
Front Panel or Standard 35mm
Symmetrical DIN Rail (35 x 7.5 or
35 x 15mm per DIN EN5002).
Termination
Box Lug
7, 10, 15, 30, 50 & 100 milliamps. For
other ratings, consult factory.
300 ms Max. @ 100%, 40ms Max. @
Environmental
500% of must trip leakage current.
Operating Temperature +10°C to +50°C
On breaker face above actuator.
Red LED on breaker face above
actuator.
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
18 | PD-Series – Circuit & Terminal Diagrams
Notes:
1
All dimensions are in inches [millimeters].
2
Tolerance ±.020 [.51] unless otherwise specified.
Notes:
Other time delay values available, consult factory.
Delay Curves 21,22,24,26: Breakers to hold 100% and must trip at 125%
of rated current and greater within the time limit shown in this curve.
Delay Curve 20: Breakers to hold 100% and must trip at 150% of rated
current and greater within the time limit shown in this curve.
All Curves: Curve data shown represents breaker response at ambient
temperature of 77°F (25°C) with no preloading. Breakers are mounted in
standard wall-mount position.
The minimum inrush pulse tolerance handling capability is 12 times the
rated current. These values are based on a 60 Hz 1/2 cycle, 8.33 ms pulse.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PD-Series – Circuit & Terminal Diagrams | 19
Notes:
1
All dimensions are in inches [millimeters].
2
Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
20 | PD-Series – Ordering Scheme
PD R – B – 24 – 650 – B – 2 A 1 – 1 – C
1
Series
3
Circuit
2
System
Voltage/Poles
4
Frequency
& Delay
5
Current Rating
2 SYSTEM VOLTAGE / POLES1
System Voltage
120VAC 1Ø
A
120/240 VAC 1Ø
B
120/208 VAC 1Ø,
C
120/240 VAC 1Ø
120/208 VAC 1Ø,
D
120/240 VAC 1Ø
208/240 VAC 3Ø
E
208/240 VAC 3Ø
F
208/240 VAC 3Ø
G
480Y VAC 3Ø
P
480Y VAC 3Ø
Q
480Y VAC 3Ø
R
Poles
One plus unswitched neutral
Two
Two plus unswitched neutral
Two plus switched neutral
Three
Three plus unswitched neutral
Three plus switched neutral
Three
Three plus unswitched neutral
Three plus switched neutral
3 CIRCUIT
Series Trip (Current)
4 FREQUENCY & DELAY
20
22
410
512
415
517
420
522
425
527
430
435
440
24
26
50/60Hz Instantaneous
50/60Hz Short
AMPERES
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
3.000
3.500
4.000
8
Actuator
9
Actuator
Color
10
Mounting
11
Agency
Approval
445
450
455
460
465
470
475
480
485
490
495
4.500
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
7 TERMINAL
2
Front Connected Box Lug
8 ACTUATOR
A
Handle
B
Handle w/ handleguard
9 ACTUATOR COLOR & LEGEND4
Acuator Color
I-O
ON-OFF
White
A
B
Black
C
D
Red
E
F
Dual
1
2
3
Legend Color
Black
White
White
10 MOUNTING3
1 THREADED INSERT 6-32 X 0.195 INCHES
2 THREADED INSERT ISO M3 X 6.5 MM
50/60Hz Medium
50/60Hz Long
11 AGENCY APPROVAL
UL Recognized & CSA Certified
C
TUV Certified
U
5 CURRENT RATING (AMPERES)
CODE
7
Terminal
6 EQUIPMENT LEAKAGE - TRIP CURRENT (MILLIAMPS)2
B
7
D
15
F
50
C
10
E
30
G
100
1 SERIES
PD
B
6
Equipment
Leakage Trip Current
610
710
611
711
612
712
613
614
615
616
617
10.000
10.500
11.000
11.500
12.000
12.500
13.000
14.000
15.000
16.000
17.000
Time Delay Curves
618
620
622
624
625
630
635
640
650
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
50.000
Notes:
1
Units with a switched or unswitched neutral connection are the same size as a unit with
an additional breaker pole (e.g. a 2-pole unit with a switched or unswitched neutral is the
same physical size as a 3-pole unit.)
Switched neutral poles contain the same overcurrent protection as the other poles.
2
The leakage currents shown will cause the breaker to trip (must-trip current). The musthold current is 67% of the must-trip current.
3
All breakers are front panel mountable using screw size shown. Breakers may also be
mounted on either 35mm x 7.5mm or 35mm x 15mm symmetrical DIN rail.
4
TUV certifed units must have I-O or Dual legends
Instantaneous
Medium
Short
Long
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
GFCI Circuit Breaker Selector Guide | 21
PB-SERIES
PC-SERIES
PD-SERIES
1-3 poles, 3rd pole switched neutral
1-poles(1 Circuit Breaker + 1 GFCISensor
Module), 120V
2-pole (2 Circuit Breakers + 1 GFCI Sensor
Module), 120/240V or 120V with Neutral
Break.
3-pole 120/240V with Neutral Break (Sensor module has 2 pole width)
1-3 poles, with switched or
unswitched neutral options
Handle, Rocker, Flat Rocker actuators
Handle, Rocker, Flat Rocker, Push-to-reset
Handle, with handleguard option
30mA & 6mA
30mA & 6mA
7-100 milliamps
LEAKAGE CURRENT
TRIP LEVEL
For 30mA leakage trip:
≤ 22.2mA, shall not trip
30mA, shall trip within .10 seconds,
complying with UL-1053
& ABYC E11. For 6mA leakage
trip: ≤25ms, complying with UL-943.
For 30mA leakage trip:
≤ 22.2mA, shall not trip
30mA, shall trip within .10 seconds,
complying with UL-1053
& ABYC E11. For 6mA leakage
trip: ≤25ms, complying with UL-943.
300 ms Max. @ 100%, 40ms
Max. @ 500% of must trip leakage current
LEAKAGE CURRENT
TRIP TIME
0.10 - 30 amps @ 120/240VAC
0.10 - 50 amps @ 120/240VAC - 240VAC
120VAC, Single Phase
120/208VAC, Single Phase
120/240VAC, Single Phase
208/240VAC, Three Phase
480Y/277VAC, Three Phase
5,000 amps
5,000 amps
5,000A @ 120/208 VAC;
120/240VAC, Single phase
2,000A @ 208/240, Three phase
2,000A @ 480Y/277VAC,
Three phase
Series Trip
Series Trip
Series Trip
.250 Quick Connect Tabs
8-32, 10-32, M4,M5 screw with upturned lugs
8-32, 10-32, M4,M5 screw, Bus Type
10-32 Threaded Stud
Front Connected Box Lug
w/ pressure plate
TERMINAL
OPTIONS
Front Panel
Front Panel
Front Mounted or Din Rail
Mounted
MOUNTING METHOD
-35° C to +65° C
-35° C to +65° C
-10°C to 60°C
UL489, CSA, UL1077, UL1500
UL943, UL1053, UL1500
UL Recognized, CSA, TUV
NUMBER OF POLES
ACTUATOR STYLE
MAXIMUM CURRENT &
VOLTAGE RATINGS
MAXIMUM
INTERRUPTING
CAPACITY
AVAILABLE
CIRCUITS
OPERATING
TEMPERATURE
AGENCY
APPROVALS
DIMENSIONS
3.800
[96.52]
0.350
[8.89]
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062 1177
Phone: (860) 793 9281 • Fax: (860) 793 9231
Email: sales carlingtech.com • www.carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
nt 8 2 2737 2277 • Fax: nt 8 2 2736 9332
Email: [email protected]
Europe/Middle East/Africa Headquarters
nt
Carling Technologies, Ltd.,
Devon, England 06062-1177
1392 36 22 • Fax: nt
1392 36
Email: [email protected]
77
GFCI-CAT_05_12