gaS SyStem SeRieS 4000 natuRal gaS

GAS system
Series 4000 natural gas
400V / 50 Hz
NOx < 500 mg/Nm3
System Ratings
Gas genset with optional heat recovery module
Genset
Engine
Type
Type
MTU 8V4000 GS
L33
MTU 8V4000 GS
L33
MTU 8V4000 GS
L64
MTU 12V4000 GS
L33
MTU 12V4000 GS
L64
MTU 16V4000 GS
L33
MTU 16V4000 GS
L64
MTU 16V4000 GS
L64
MTU 20V4000 GS
L33
MTU 20V4000 GS
L64
Output
Elect.1) Therm.2) Exhaust3) Low Temp.
kWel. kWth.
kWth. (°C) kWth. (°C)
776
401
422 (120) 47 (40)
854
443
448 (120) 49 (40)
1012 475
461 (120) 69 (43)
1286 664
659 (120) 88 (40)
1523 712
691 (120) 104 (43)
1718 974
821 (120) 113 (40)
1999 950
928 (120) 125 (43)
2028 965
936 (120) 127 (43)
2145 1161
1078 (120)142 (40)
2535 1186
1212 (120) 176 (43)
Energy
input4)
kW
1832
1993
2298
2974
3438
3991
4511
4573
4990
5751
Efficiency
Electr.
Total
ntot (%)
nel. (%)
42.4
87.3
42.8
87.5
44.0
84.8
43.2
87.7
44.3
85.1
43.0
88.0
44.3
85.9
44.3
85.9
43.0
87.9
44.1
85.8
Methane
number5)
≥ 70
≥ 80
≥ 80
≥ 80
≥ 80
≥ 80
≥ 80
≥ 80
≥ 80
≥ 80
Hot ambient conditions MTU 8V4000 GS
MTU 12V4000 GS
MTU 16V4000 GS
MTU 20V4000 GS
L32
L32
L32
L32
776
1169
1560
1948
446
632
863
1035
420 (120) 32 (53)
638 (120) 43 (53)
805 (120) 76 (53)
1101 (120) 78 (53)
1853
2747
3651
4577
41.9
42.5
42.7
42.6
88.6
88.8
88.4
89.2
≥ 80
≥ 80
≥ 80
≥ 80
921
1143
937 (120) 84 (53)
1181 (120) 99 (53)
3848
4812
40.5
40.5
88.8
88.8
≥ 60
≥ 60
Low methane number MTU 16V4000 GS
MTU 20V4000 GS
L32 ER
L32 ER
1560
1948
1) Rated power at nominal voltage, power factor = 1,0 and nominal frequency
3) Heat output from exhaust (exhaust cooling to 120°C) with tolerance of ± 8%
5) Referenced methane number
2) Heat output from engine cooling with tolerance of ± 8%
4) Performance data in accordance with ISO 3046/I-2002 with tolerance of 5%
Project specific data on request:
- different alternator voltage
- different flow-/return-temperatures, hot cooling, methane number, installation conditions etc.
- Container
Drawings and dimensions
Note: This drawing is provided for reference only and should not be used for installation planning.
Genset Type
MTU 8V4000 GS
MTU 12V4000 GS
MTU 16V4000 GS
MTU 20V4000 GS
Dimensions Genset (L x W x H)
4200 x 2000 x 2400 mm
5000 x 2000 x 2400 mm
5500 x 2000 x 2600 mm
6000 x 2000 x 2600 mm
Heat recovery module (Lh x W x H)
1500 x 1900 x 2000 mm
1500 x 1900 x 2000 mm
1500 x 1900 x 2000 mm
1500 x 1900 x 2000 mm
4000
Configuration
No. of cylinders
Bore/Stroke
Cyl. displacement
90° V
8/12/16/20
170/210 mm
4.77 lit.
design and equipment (extract)
// Sliding gear starter 24V
// Gas supply with electronically controlled gas metering valve
// Electronic high-voltage capacitor ignition system with one ignition coil
per cylinder
// Electronic speed governor for speed and power output control with
automatic knocking control
Any specifications, descriptions, values, data or other information related to dimensions, power or other technical performance criteria of the goods as provided in
this general productinformation are to be understood as non-binding and may be subject to further changes such as but not limited to technical evolution at any time.
Version: 01.08.2014, materials and specifications subject to change without notice due to technical advances.
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Subject to change. | 3234731 | Edition 01/15 | ENC 2015-04 | Printed in Germany on chlorine-free bleached papaer.
Engine Data