GAS SYSTEM SERIES 4000 NATURAL GAS 480V / 60 Hz NOx < 500 mg/Nm3 SYSTEM RATINGS Gas genset Genset Type Engine Type MTU 8V4000 GS MTU 8V4000 GS MTU 12V4000 GS MTU 16V4000 GS MTU 20V4000 GS L33 L33 L33 L33 L33 Output Elect.1) kWel. 762 840 1272 1705 2129 Therm.2) kWth. 410 452 664 974 1158 Exhaust3) kWth. (°C) 426 (120) 453 (120) 659 (120) 821 (120) 1077 (120) Low Temp. kWth. (°C) 47 (40) 49 (40) 88 (40) 113 (40) 142 (40) Energy input4) kW 1851 2014 2974 3991 4985 Efficiency Electr. nel. (%) 41.2 41.7 42.8 42.7 42.7 Total ntot (%) 86.3 86.6 87.3 87.7 87.5 Output Elect.1) kWel. 762 1147 1550 1932 Therm.2) kWth. 455 632 863 1035 Exhaust3) kWth. (°C) 424 (120) 638 (120) 805 (120) 1101 (120) Low Temp. kWth. (°C) 32 (53) 43 (53) 76 (53) 78 (53) Energy input4) kW 1872 2747 3651 4577 Efficiency Electr. nel. (%) 40.7 41.8 42.5 42.2 Total ntot (%) 87.7 88.0 88.1 88.9 Methane number5) ≥ 70 ≥ 80 ≥ 80 ≥ 80 ≥ 80 hot ambient conditions Genset Type Engine Type MTU 8V4000 GS MTU 12V4000 GS MTU 16V4000 GS MTU 20V4000 GS L32 L32 L32 L32 1) Rated power at nominal voltage, power factor = 1,0 and nominal frequency 2) Heat output from engine cooling with tolerance of ± 8% 3) Heat output from exhaust (exhaust cooling to 120°C) with tolerance of ± 8% 4) Performance data in accordance with ISO 3046/I-2002 with tolerance of 5% 5) Referenced methane number Project specific data on request: - different alternator voltage - different flow-/return-temperatures, hot cooling, methane number, installation conditions etc. - Container Methane number5) ≥ 80 ≥ 80 ≥ 80 ≥ 80 H DRAWINGS AND DIMENSIONS L W Note: This drawing is provided for reference only and should not be used for installation planning. Genset Type MTU 8V4000 GS MTU 12V4000 GS MTU 16V4000 GS MTU 20V4000 GS Dimensions Genset (L x W x H) 5000 x 2000 x 2500 mm 5850 x 2000 x 2500 mm 6800 x 2000 x 2600 mm 7250 x 2000 x 2600 mm 4000 Configuration No. of cylinders Bore/Stroke Cyl. displacement Rated speed 90° V 8/12/16/20 170/210 mm 4.77 lit. 1500 rpm DESIGN AND EQUIPMENT (EXTRACT) // Sliding gear starter 24V // Gas supply with electronically controlled gas metering valve // Electronic high-voltage capacitor ignition system with one ignition coil per cylinder // Electronic speed governor for speed and power output control with automatic knocking control Any specifications, descriptions, values, data or other information related to dimensions, power or other technical performance criteria of the goods as provided in this general productinformation are to be understood as non-binding and may be subject to further changes such as but not limited to technical evolution at any time. Version: 01.08.2014, materials and specifications subject to change without notice due to technical advances. MTU Onsite Energy A Rolls-Royce Power Systems Brand www.mtuonsiteenergy.com Subject to change. | 3237291 | Edition 02/14 | ENC 2014-08 | Printed in Germany on chlorine-free bleached papaer. ENGINE DATA