GAS SYSTEM SERIES 4000 NATURAL GAS

GAS SYSTEM
SERIES 4000 NATURAL GAS
400V / 50 Hz
NOx < 500 mg/Nm3
SYSTEM RATINGS
Gas genset with optional heat recovery
Genset
Type
Engine
Type
MTU 8V4000 GS
MTU 8V4000 GS
MTU 8V4000 GS
MTU 12V4000 GS
MTU 12V4000 GS
MTU 16V4000 GS
MTU 16V4000 GS
MTU 16V4000 GS
MTU 20V4000 GS
MTU 20V4000 GS
L33
L33
L64
L33
L64
L33
L64
L64
L33
L64
Output
Elect.1)
kWel.
776
854
1012
1199
1523
1718
1999
2028
2145
2530
Therm.2)
kWth.
401
443
475
616
712
974
952
965
1161
1200
Exhaust3)
kWth. (°C)
422 (120)
448 (120)
461 (120)
636 (120)
691 (120)
821 (120)
930 (120)
936 (120)
1078 (120)
1147 (120)
Low Temp.
kWth. (°C)
47 (40)
49 (40)
69 (43)
82 (40)
104 (43)
113 (40)
125 (43)
127 (43)
142 (40)
175 (43)
Energy
input4)
kW
1832
1993
2298
2795
3438
3991
4519
4573
4990
5748
Efficiency
Electr.
nel. (%)
42.4
42.8
44.0
42.9
44.3
43.0
44.2
44.3
43.0
44.1
Total
ntot (%)
87.3
87.5
84.8
87.7
85.1
88.0
85.9
85.9
87.9
84.8
Output
Elect.1)
kWel.
776
1169
1560
1948
Therm.2)
kWth.
446
632
863
1035
Exhaust3)
kWth. (°C)
420 (120)
638 (120)
805 (120)
1101 (120)
Low Temp.
kWth. (°C)
32 (53)
43 (53)
76 (53)
78 (53)
Energy
input4)
kW
1853
2747
3651
4577
Efficiency
Electr.
nel. (%)
41.9
42.5
42.7
42.6
Total
ntot (%)
88.6
88.8
88.4
89.2
Methane
number5)
≥ 70
≥ 80
≥ 80
≥ 80
≥ 80
≥ 80
≥ 80
≥ 80
≥ 80
≥ 80
hot ambient conditions
Genset
Type
Engine
Type
MTU 8V4000 GS
MTU 12V4000 GS
MTU 16V4000 GS
MTU 20V4000 GS
L32
L32
L32
L32
1) Rated power at nominal voltage, power factor = 1,0 and nominal frequency
2) Heat output from engine cooling with tolerance of ± 8%
3) Heat output from exhaust (exhaust cooling to 120°C) with tolerance of ± 8%
4) Performance data in accordance with ISO 3046/I-2002 with tolerance of 5%
5) Referenced methane number
Project specific data on request:
- different alternator voltage
- different flow-/return-temperatures, hot cooling, methane number, installation conditions etc.
- Container
Methane
number5)
≥ 80
≥ 80
≥ 80
≥ 80
DRAWINGS AND DIMENSIONS
Note: This drawing is provided for reference only and should not be used for installation planning.
Genset Type
MTU 8V4000 GS
MTU 12V4000 GS
MTU 16V4000 GS
MTU 20V4000 GS
Dimensions Genset (L x W x H)
4200 x 2000 x 2400 mm
5000 x 2000 x 2400 mm
5500 x 2000 x 2600 mm
6000 x 2000 x 2600 mm
Heat recovery module (Lh x W x H)
1500 x 1900 x 2000 mm
1500 x 1900 x 2000 mm
1500 x 1900 x 2000 mm
1500 x 1900 x 2000 mm
4000
Configuration
No. of cylinders
Bore/Stroke
Cyl. displacement
90° V
8/12/16/20
170/210 mm
4.77 lit.
DESIGN AND EQUIPMENT (EXTRACT)
// Sliding gear starter 24V
// Gas supply with electronically controlled gas metering valve
// Electronic high-voltage capacitor ignition system with one ignition coil
per cylinder
// Electronic speed governor for speed and power output control with
automatic knocking control
Any specifications, descriptions, values, data or other information related to dimensions, power or other technical performance criteria of the goods as provided in
this general productinformation are to be understood as non-binding and may be subject to further changes such as but not limited to technical evolution at any time.
Version: 01.08.2014, materials and specifications subject to change without notice due to technical advances.
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Subject to change. | 3234731 | Edition 02/14 | ENC 2014-08 | Printed in Germany on chlorine-free bleached papaer.
ENGINE DATA