GAS SYSTEM SERIES 4000 NATURAL GAS 400V / 50 Hz NOx < 500 mg/Nm3 SYSTEM RATINGS Gas genset with optional heat recovery Genset Type Engine Type MTU 8V4000 GS MTU 8V4000 GS MTU 8V4000 GS MTU 12V4000 GS MTU 12V4000 GS MTU 16V4000 GS MTU 16V4000 GS MTU 16V4000 GS MTU 20V4000 GS MTU 20V4000 GS L33 L33 L64 L33 L64 L33 L64 L64 L33 L64 Output Elect.1) kWel. 776 854 1012 1199 1523 1718 1999 2028 2145 2530 Therm.2) kWth. 401 443 475 616 712 974 952 965 1161 1200 Exhaust3) kWth. (°C) 422 (120) 448 (120) 461 (120) 636 (120) 691 (120) 821 (120) 930 (120) 936 (120) 1078 (120) 1147 (120) Low Temp. kWth. (°C) 47 (40) 49 (40) 69 (43) 82 (40) 104 (43) 113 (40) 125 (43) 127 (43) 142 (40) 175 (43) Energy input4) kW 1832 1993 2298 2795 3438 3991 4519 4573 4990 5748 Efficiency Electr. nel. (%) 42.4 42.8 44.0 42.9 44.3 43.0 44.2 44.3 43.0 44.1 Total ntot (%) 87.3 87.5 84.8 87.7 85.1 88.0 85.9 85.9 87.9 84.8 Output Elect.1) kWel. 776 1169 1560 1948 Therm.2) kWth. 446 632 863 1035 Exhaust3) kWth. (°C) 420 (120) 638 (120) 805 (120) 1101 (120) Low Temp. kWth. (°C) 32 (53) 43 (53) 76 (53) 78 (53) Energy input4) kW 1853 2747 3651 4577 Efficiency Electr. nel. (%) 41.9 42.5 42.7 42.6 Total ntot (%) 88.6 88.8 88.4 89.2 Methane number5) ≥ 70 ≥ 80 ≥ 80 ≥ 80 ≥ 80 ≥ 80 ≥ 80 ≥ 80 ≥ 80 ≥ 80 hot ambient conditions Genset Type Engine Type MTU 8V4000 GS MTU 12V4000 GS MTU 16V4000 GS MTU 20V4000 GS L32 L32 L32 L32 1) Rated power at nominal voltage, power factor = 1,0 and nominal frequency 2) Heat output from engine cooling with tolerance of ± 8% 3) Heat output from exhaust (exhaust cooling to 120°C) with tolerance of ± 8% 4) Performance data in accordance with ISO 3046/I-2002 with tolerance of 5% 5) Referenced methane number Project specific data on request: - different alternator voltage - different flow-/return-temperatures, hot cooling, methane number, installation conditions etc. - Container Methane number5) ≥ 80 ≥ 80 ≥ 80 ≥ 80 DRAWINGS AND DIMENSIONS Note: This drawing is provided for reference only and should not be used for installation planning. Genset Type MTU 8V4000 GS MTU 12V4000 GS MTU 16V4000 GS MTU 20V4000 GS Dimensions Genset (L x W x H) 4200 x 2000 x 2400 mm 5000 x 2000 x 2400 mm 5500 x 2000 x 2600 mm 6000 x 2000 x 2600 mm Heat recovery module (Lh x W x H) 1500 x 1900 x 2000 mm 1500 x 1900 x 2000 mm 1500 x 1900 x 2000 mm 1500 x 1900 x 2000 mm 4000 Configuration No. of cylinders Bore/Stroke Cyl. displacement 90° V 8/12/16/20 170/210 mm 4.77 lit. DESIGN AND EQUIPMENT (EXTRACT) // Sliding gear starter 24V // Gas supply with electronically controlled gas metering valve // Electronic high-voltage capacitor ignition system with one ignition coil per cylinder // Electronic speed governor for speed and power output control with automatic knocking control Any specifications, descriptions, values, data or other information related to dimensions, power or other technical performance criteria of the goods as provided in this general productinformation are to be understood as non-binding and may be subject to further changes such as but not limited to technical evolution at any time. Version: 01.08.2014, materials and specifications subject to change without notice due to technical advances. MTU Onsite Energy A Rolls-Royce Power Systems Brand www.mtuonsiteenergy.com Subject to change. | 3234731 | Edition 02/14 | ENC 2014-08 | Printed in Germany on chlorine-free bleached papaer. ENGINE DATA