Pn390b - Panduit

© Panduit Corp. 2010
INSTALLATION INSTRUCTIONS
PN390B
Panduit TX6A™ and TX6A-SD™ 10Gig™ UTP COPPER CABLING SYSTEM
INSTALLATION GUIDELINES
The TX6A™ and TX6A-SD™ 10Gig™ UTP Copper Cabling System is to be installed in
accordance to the cable management requirements set forth in ANSI/TIA/EIA-568-C
(Commercial Building Telecommunications Cabling Standard) and in ANSI/TIA/EIA-569-C
(Commercial Building Standard for Telecommunications Pathways and Spaces). To aid
compliant installation, guidelines for the TX6A™ and TX6A-SD™ 10Gig™ UTP Copper Cabling
System are provided below.
Pathways and Spacing Management
Pathways should be located to minimize occupant disruption and allow for easy
moves, adds, and changes.
For initial installation, the maximum fill capacity for pathways (i.e. conduit, raceways,
trays, baskets) is 40 percent.
Number cables =









Pathway Internal Area X 40%
Cable Area
For the TX6A™ 10Gig™ Plenum (i.e. P/N PUP6A04**) cable, the cable
area is 0.0707 inches2 (46 mm2).
For the TX6A™ 10Gig™ Riser (i.e. P/N PUR6A04**) cable, the cable area
is 0.0707 inches2 (46mm2).
For the TX6A™ 10Gig™ Low Smoke Zero Halogen (i.e. P/N PUL6A04**)
cable, the cable area is 0.0707 inches2 (46 mm2).
For the TX6A™ 10Gig™ CM/PVC (i.e. P/N PUC6A04**) cable, the cable
area is 0.0707 inches2 (46 mm2).
For the TX6A-SD™ 10Gig™ Plenum (i.e. P/N PUP6ASD04**) cable, the
cable area is 0.0452 inches2 (29 mm2).
For the TX6A-SD™ 10Gig™ Riser (i.e. P/N PUR6ASD04**) cable, the
cable area is 0.0452 inches2 (29mm2).
For the TX6A-SD™ 10Gig™ Low Smoke Zero Halogen (i.e. P/N
PUL6ASD04**) cable, the cable area is 0.0452 inches2 (29 mm2).
For the TX6A-SD™ 10Gig™ CM/PVC (i.e. P/N PUC6ASD04**) cable, the
cable area is 0.0452 inches2 (29 mm2).
Refer to the TX6A™ and TX6A-SD™ 10Gig™ UTP Copper Cabling
conduit fill capacity guideline table in Appendix A of this document to
determine the maximum number of cables per conduit trade size.
The maximum fill capacity of 60 percent is allowed to accommodate future additions
after initial installation.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 8
© Panduit Corp. 2010
INSTALLATION INSTRUCTIONS
PN390B
Proper cable bend radius control must be maintained throughout the pathways. The
bend radius needs to be four (4) times the cable diameter.

For the TX6A™ 10Gig™ Plenum (i.e. P/N PUP6A04**) cable, the
minimum bend radius is 1.20 inches (30 mm)

For the TX6A™ 10Gig™ Riser (i.e. P/N PUR6A04**) cable, the minimum
bend radius is 1.20 inches (30 mm)

For the TX6A™ 10Gig™ Low Smoke Zero Halogen (i.e. P/N PUL6A04**)
cable, the minimum bend radius is 1.20 inches (30 mm)

For the TX6A™ 10Gig™ CM/PVC (i.e. P/N PUC6A04**) cable, the
minimum bend radius is 1.20 inches (30 mm)

For the TX6A-SD™ 10Gig™ Plenum (i.e. P/N PUP6ASD04**) cable, the
minimum bend radius is 0.96 inches (24 mm)

For the TX6A-SD™ 10Gig™ Riser (i.e. P/N PUR6ASD04**) cable, the
minimum bend radius is 0.96 inches (24 mm)

For the TX6A-SD™ 10Gig™ Low Smoke Zero Halogen (i.e. P/N
PUL6ASD04**) cable, the minimum bend radius is 0.96 inches (24 mm)

For the TX6A-SD™ 10Gig™ CM/PVC (i.e. P/N PUC6ASD04**) cable, the
minimum bend radius is 0.96 inches (24 mm)
Pathways and Spacing Management
For data center applications, it is recommended to use Panduit® FiberRunner™ or
GridRunner™ Underfloor Cable Routing Systems for cable raceway management.
The fittings provide minimum 1.5-inch bend radius to protect against signal loss due
to excessive cable bends.
Pathways should be designed to allow for future expansion (minimum two cables per
work area, with pathways supporting three cables per work area). Therefore when
designing a pathway, the pathway needs to accommodate 150% of the initial cable
installation. For example, if the initial design requires 2 cables each for ten work
areas, the pathway shall be designed to accommodate 30 cables.
Conduit should be run in the most direct route possible with no more than two 90
degree bends between pull boxes and serve no more than three outlet boxes.
Conduit bends should be at least six times the conduit diameter.
Cable trays are to be installed per manufacturing guidelines and loading capacities
must be considered during cabling installation.
Cable trays used in the ceiling should allow for at least 12 inches (305 mm) of
clearance above the tray. Cable trays used in the floor should allow for at least 2
inches (51 mm) of clearance between the top part of the tray and the bottom of the
floor tile.
J-Mod or J-Pro Cable Support System should be located at 5 foot intervals
maximum and have at least 3 inches (76 mm) of clearance above suspended
ceilings.
Please reference Panduit website for J-Mod or J-Pro Cabling Support System fill
capacity information for various sizes available.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 2 of 8
© Panduit Corp. 2010
INSTALLATION INSTRUCTIONS
PN390B
Cable Separation Management
TX6A™ and TX6A-SD™ 10Gig™ UTP Copper Cables do not have any specific
limitations with sharing pathways with other category copper cables throughout the
whole cable run.
Separation and physical barriers between TX6A™ or TX6A-SD™ 10Gig™ UTP
Copper Cable and power cables must be maintained within raceways. If TX6A™ or
TX6A-SD™ 10Gig™ UTP Copper Cable and power cables need to cross install
perpendicular to each other. Please reference the National Electric Code for local
installation guidelines.
The maximum channel distance for the TX6A™ 10Gig™ UTP Copper Cabling
System in the backbone and/or horizontal is 328 feet (100 meters). The total length
of equipment cords, patch cords and work area cords shall not exceed 33 feet (10
meters)
The maximum permanent link distance for the TX6A™ 10Gig™ UTP Copper Cabling
System in the backbone and/or horizontal is 295 feet (90 meters)
The maximum channel distance for the TX6A-SD™ 10Gig™ UTP Copper Cabling
System in the backbone and/or horizontal is 230 feet (70 meters). The total length of
equipment cords, patch cords and work area cords shall not exceed 33 feet (10
meters)
The maximum permanent link distance for the TX6A-SD™ 10Gig™ UTP Copper
Cabling System in the backbone and/or horizontal is 197 feet (60 meters)
Cable Pulling & Installation Management
The maximum pulling tension is not to exceed 25 lbf. Cable installation should not in
any way deform the cable jacket.
The cable should not come in contact with any water or chemicals (ex. paint,
lubricants), or be exposed to any high humidity during or after installation.
Avoid any cable kinks and maintain proper bend radius control during cabling pulling.
If any kinks should occur, kinked cable should be removed and replaced.
Tak-Ty® Hook & Loop Cable Ties, Contour-Ty® Cable Ties, Belt-Ty™ In-Line Cable
Ties or Pan-Ty® Cable Ties should be applied loosely and at random intervals to
cable bundles to avoid any pinching or crushing of the cable jackets.
For aesthetics and ease of bundling, the Cable Bundling and Organizing Tool (i.e.
P/N CBOT24K) is recommended.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 8
© Panduit Corp. 2010
INSTALLATION INSTRUCTIONS
PN390B
Cable Management in the Telecommunication Room
Organize and manage cables for quick and easy moves, adds and changes
Use the rack vertical manager fill cable capacity table in Appendix B of this document
to determine the maximum number of cables per telecommunication rack.
Termination procedures at the patch panel include:
Feed cables from both sides of the panel
Maintain acceptable bend radius levels
Do not kink cables
Do not cinch cable ties so tightly as to deform the cable in any way

To enhance wire management in the back of the panel, it is
recommended that a strain relief bar (i.e. P/N SRBM19BLY) be mounted
to the rack. The strain relief bar includes Tak-Ty® Hook & Loop Cable
Ties for additional cable management.
Termination procedures for the DP6A™ 10Gig™ Punchdown Patch Panel include:
 Follow installation instruction sheet PN379.
 Outer cable jacket should be as close as possible to point of termination
 Last twist should be no further than 0.5 inches from the point of
termination.
Cable Management in the Work Area
For surface raceway applications, the Pan-Way® TG Surface Raceway System is the
optimal solution in the work area for routing TX6A™ or TX6A-SD™ 10Gig™ Copper
Cables. The TG Raceway system provides adequate space to maintain proper cable
bend radius control.
Allow for at least one outlet per work area with a minimum of two cable terminations.
Pathways should be designed to allow for future expansion. For example, work
areas with two cables must be served by pathways that can accommodate a
minimum of three cables.
Allow for at least 12 inches (305 mm) of slack at the work area. Pull slack up into the
ceiling or back into the raceway and store it there, where it can later be pulled into
the box if re-termination is necessary.
Terminate Mini-Com® TX6A™ 10GigTM UTP Jack Modules per installation instruction
sheet PN511.
To improve bend radius control of TX6A™ or TX6A-SD™ 10Gig™ Copper Cable in
junction boxes, it is recommended that Panduit sloped faceplates (i.e. P/N
UICFPSE2**) be used in the work area.
With Panduit sloped faceplates, the following junction boxes can be used with
TX6A™ or TX6A-SD™ 10Gig™ UTP Copper Cable (i.e. P/N JBX3510**-A, JB1**-A,
JBP1**-A, JBP1I**-A, JB1FS**-A, JBP2**-A, JB1D**-A, JBP1D**-A, JBP2D**-A).
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 8
© Panduit Corp. 2010
INSTALLATION INSTRUCTIONS
PN390B
With Panduit® flush faceplates, the following junction boxes can be used with
TX6A™ or TX6A-SD™ 10Gig™ UTP Copper Cable (i.e. P/N JB1D**-A, JBP1D**-A,
JBP2D**-A).
Reference Documents
ANSI/TIA/EIA-568-C (Commercial Building Telecommunications Cabling Standard)
ANSI/TIA/EIA-569-C (Commercial Building Standard for Telecommunications Pathways
and Spaces)
DP6TM 10GigTM Patch Panel installation instruction sheet PN379.
Mini-Com® TX6ATM 10GigTM UTP Jack Modules installation instruction sheet PN511.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 8
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2010
PN390B
Appendix A
Panduit TX6ATM and TX6A-SDTM 10GigTM UTP Copper Cabling System
Conduit Fill Capacity Table
TX6A™ 10Gig™ UTP Copper Cable
Conduit
Trade Size
Inches (mm)
3/4
1
1
1
2
2-1/2
3
3-1/2
4
5
6
(21)
(27)
(35)
(41)
(53)
(63)
(78)
(91)
(103)
(129)
(155)
Internal Diameter
inches
mm
0.82
1.05
1.38
1.61
2.07
2.47
3.07
3.55
4.03
5.05
6.07
20.9
26.6
35.1
40.9
52.5
62.7
77.9
90.1
102.3
128.2
154.1
Internal Conduit Area
Area-.79D2 Total 100%
inches2
mm2
0.53
0.87
1.50
2.05
3.39
4.82
7.45
9.96
12.83
20.15
29.11
345
559
973
1322
2177
3106
4794
6413
8268
12984
18760
Cable Area
Area 40% Fill
inches2
mm2
0.21
0.35
0.60
0.82
1.35
1.93
2.98
3.98
5.13
8.06
11.64
138
224
389
529
871
1242
1918
2565
3307
5194
7504
inches2
mm2
0.0707
0.0707
0.0707
0.0707
0.0707
0.0707
0.0707
0.0707
0.0707
0.0707
0.0707
46
46
46
46
46
46
46
46
46
46
46
Max. No. Cables
Using 40% Fill Rate
3
5
8
12
19
27
42
56
73
114
165
TX6A-SD™ 10Gig™ UTP Copper Cable
Conduit
Trade Size
Inches (mm)
3/4
1
1
1
2
2-1/2
3
3-1/2
4
5
6
(21)
(27)
(35)
(41)
(53)
(63)
(78)
(91)
(103)
(129)
(155)
Internal Diameter
inches
mm
0.82
1.05
1.38
1.61
2.07
2.47
3.07
3.55
4.03
5.05
6.07
20.9
26.6
35.1
40.9
52.5
62.7
77.9
90.1
102.3
128.2
154.1
Internal Conduit Area
Area-.79D2 Total 100%
inches2
mm2
0.53
0.87
1.50
2.05
3.39
4.82
7.45
9.96
12.83
20.15
29.11
345
559
973
1322
2177
3106
4794
6413
8268
12984
18760
Cable Area
Area 40% Fill
inches2
mm2
0.21
0.35
0.60
0.82
1.35
1.93
2.98
3.98
5.13
8.06
11.64
138
224
389
529
871
1242
1918
2565
3307
5194
7504
inches2
mm2
0.0452
0.0452
0.0452
0.0452
0.0452
0.0452
0.0452
0.0452
0.0452
0.0452
0.0452
44
44
44
44
44
44
44
44
44
44
44
Max. No. Cables
Using 40% Fill Rate
5
8
13
18
30
43
66
88
114
178
258
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 8
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2010
PN390B
Appendix B
Panduit Rack Vertical Manager Horizontal Cable Fill Capacity Table
™
™
PatchRunner 6"
Cable
Diameter
(inches)
Front
Channel
Practical
Area
Fill
2
(in )
™
PatchRunner 8"
Back
Channel
Practical
Area
Fill
2
(in )
Front
Channel
Practical
Area
Fill
2
(in )
PatchRunner 12"
Back
Channel
Practical
Area
Fill
2
(in )
Front
Channel
Practical
Area
Fill
2
(in )
Back
Channel
Practical
Area
Fill
2
(in )
PUP6004**
0.233
319
208
473
308
783
510
PUR6004**
0.240
300
196
446
291
738
481
PUC6004**
0.225
342
223
508
331
840
547
PUL6004**
0.225
342
223
508
331
840
547
PUP6504**
0.265
246
161
366
238
605
394
PUR6504**
0.266
244
159
363
236
601
391
PUP6A04**
0.300
192
126
286
186
473
308
PUR6A04**
0.300
192
126
286
186
473
308
PUC6A04**
0.300
192
126
286
186
473
PUL6A04**
0.300
PUP6ASD04**
0.240
300
196
446
291
738
481
PUR6ASD04**
0.240
300
196
446
291
738
481
PUC6ASD04**
0.240
300
196
446
291
738
481
PUL6ASD04**
0.240
300
196
446
291
738
481
PUP6X04**
0.331
158
103
234
153
388
253
PUR6X04**
0.342
148
96
220
143
363
236
PUC6X04**
0.338
151
99
225
146
372
242
PUL6X04**
0.342
148
96
220
143
363
236
34.00
192
22.20
126
50.50
286
32.90
186
83.50
473
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 8
54.40
308
308
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2010
Net-Access™ - End
Front
Cable
Diameter
(inches)
Channel
Area (in2)
Net-Access™ - Center
Back
Practical
Fill
PN390B
Channel
Area (in2)
Front
Practical
Fill
Channel
Area (in2)
Back
Practical
Fill
Channel
Area (in2)
Practical
Fill
PUP6004**
0.233
396
396
792
792
PUR6004**
0.240
373
373
746
746
PUC6004**
0.225
424
424
849
849
PUL6004**
0.225
424
424
849
849
PUP6504**
0.265
306
306
612
612
PUR6504**
0.266
303
303
607
607
PUP6A04**
0.295
239
239
478
478
PUR6A04**
0.295
239
239
478
478
PUC6A04**
0.295
239
239
478
PUL6A04**
0.295
PUP6ASD04**
0.240
373
373
746
746
PUR6ASD04**
0.240
373
373
746
746
PUC6ASD04**
0.240
373
373
746
746
PUL6ASD04**
0.240
373
373
746
746
PUP6X04**
0.331
196
196
392
392
PUR6X04**
0.342
183
183
367
367
PUC6X04**
0.338
188
188
376
376
PUL6X04**
0.342
183
183
367
367
42.20
239
42.20
239
Net-Access™ - End with Slack Spool
Front
Cable
Diameter
(inches)
Channel
Area (in2)
84.40
Channel
Area (in2)
Front
Practical
Fill
478
84.40
478
Net-Access™ - Center with Slack Spool
Back
Practical
Fill
478
Channel
Area (in2)
Back
Practical
Fill
Channel
Area (in2)
Practical
Fill
PUP6004**
0.233
304
304
700
700
PUR6004**
0.240
286
286
659
659
PUC6004**
0.225
326
326
750
750
PUL6004**
0.225
326
326
750
750
PUP6504**
0.265
235
235
541
541
PUR6504**
0.266
233
233
537
537
PUP6A04**
0.300
183
183
422
422
PUR6A04**
0.300
183
183
422
422
PUC6A04**
0.300
183
183
422
PUL6A04**
0.300
PUP6ASD04**
0.240
286
286
659
659
PUR6ASD04**
0.240
286
286
659
659
PUC6ASD04**
0.240
286
286
659
659
PUL6ASD04**
0.240
286
286
659
659
PUP6X04**
0.331
150
150
346
346
PUR6X04**
0.342
141
141
324
324
PUC6X04**
0.338
144
144
332
332
PUL6X04**
0.342
141
141
324
324
32.40
183
32.40
183
74.60
422
74.60
422
422
Practical Fill: Estimate assumes a 40% fill factor (i.e. Sum of the cable cross sectional
areas equals 40% of the vertical channel.) The 40% factor is intended to account for
cable routing.
Note: All content subject to change without notice.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 8 of 8