QUICKTRONIC PROFESSIONAL QTP-OPTIMAL

QUICKTRONIC PROFESSIONAL QTP-OPTIMAL
osram.com
QUICKTRONIC PROFESSIONAL
QTP-OPTIMAL
1
ECG for T5/∅16mm, T8/∅26mm, DULUX L / F
fluorescent lamps
QTP-OPTIMAL
i.e. LUMILUX® T5 HO ES
LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
01
QUICKTRONIC PROFESSIONAL QTP-OPTIMAL
Product Features:
•
•
•
•
•
•
•
•
•
•
•
One ECG for three lamp technologies; T5, T8, Dulux L / F
1
Up to 100.000 hours lifetime
Lamp start with optimized filament preheating within 1.5 sec.
Suitable for lighting with very high switching cycles
Reliable lamp ignition between -20°C...+50°C
Cut-off Technology
2
Suitable for luminaries of protection classes I and II
3
CELMA Energy Efficiency Index A2 BAT (Best Available Technology)
Automatic safety shut-down in case of a defect or at the end of the lamp’s life (EoL T.2)
Automatic restart after lamp replacement
Suitable for emergency installations (DC operation)
Technical Data
Max. cross section
2
for IDC-contakt [mm ]:
„s“ : 0.5; „f“ : 0.75
Max. cross section for
2
push-in contact [mm ]:
„s“ : 0.5…1.0
4
5
4
Starting time:
t: < 1 ,5 sec.
(<0.3 sec. in case of line interruptions/switchover of <0.5 sec.)
Line voltage:
220 - 240 V
Voltage range (AC):
198 - 264 V
Voltage range (DC):
176 - 276 V
Line frequency:
0, 50 - 60 Hz
Operating frequency:
Electrical strength:
40 - 50 kHz
300 V  permanent, 320 V  48 hours, 350 V  2 hours
Ambient temperature ta:
-20 °C to +50 °C
Measuring point temperature tc:
U-OUT:
1
2
3
4
5
max. +75 °C
330 V
430 V
QTP-OPTIMAL 1x18-40
QTP-OPTIMAL 2x18-40
QTP-OPTIMAL 1x54-58
QTP-OPTIMAL 2x54-58
at T = 65°C @ Tc. 50.000 h with max. 10% failure rate at tc = 75°C max
No need to connect earth in suitable luminaires of protection class II
EEI: A2 for QTP-OPTIMAL 1x18-40
“s” = solid wire
“f” = flexible wire
LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
02
QUICKTRONIC PROFESSIONAL QTP-OPTIMAL
Inrush current and max. number of ECG per circuit breaker
ECG
Inrush Current
Ip [A]
24
37
37
57
QTP-OPTIMAL 1x18-40
QTP-OPTIMAL 2x18-40
QTP-OPTIMAL 1x54-58
QTP-OPTIMAL 2x54-58
Max. number of ECG per circuit breaker
TH [µs]
230
200
200
150
B: 10A
17
12
12
8
B: 16A
28
19
19
13
C: 16 A
47
32
32
22
Standards and approval marks
Safety:
acc. to EN 61347-2-3 + A1 + A2:2006-02 / IEC 61347-2-3 (ed.2):2011
Radio interference:
acc. EN 55015:2006 + A1:2007 + A2:2009 / CISPR 15: 2005 + A1:2006 + A2:2008
Harmonic content:
acc. to EN 61000-3-2:2006 + A1:2009 + A2:2009 / IEC 61000-3-2:2005 + A1:2008 + A2:2009
Immunity:
acc. to EN 61547:2009 / IEC 61547:2009
Approval marks:
Dimensions & weight
Description
Description
Length
[mm]
width
[mm]
height
[mm]
distance
mounting
holes [mm]
Weight [g]
QTP-OPTIMAL 1x18-40
280
30
21
270
170
QTP-OPTIMAL 2x18-40
360
30
21
350
230
QTP-OPTIMAL 1x54-58
280
30
21
270
160
QTP-OPTIMAL 2x54-58
360
30
21
350
240
LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
03
QUICKTRONIC PROFESSIONAL QTP-OPTIMAL
Lamp wiring
QTP-OPTIMAL 1x…
1 ~
2
3 ~
220...
240 V
21
22
23
24
L
Max. permitted cable length between ECG and lamp: 2.0 m (PIN 21, 22); 1.0 m (PIN 23, 24)
QTP-OPTIMAL 2x…
1 ~
2
3 ~
220...
240 V
21
22
23
24
25
26
L
L
Max. permitted cable length between ECG and lamp: 2.0 m (PIN 21, 22, 25, 26); 1.0 m (PIN 23, 24)
LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
04
QUICKTRONIC PROFESSIONAL QTP-OPTIMAL
Logistic Data
Description
EAN 10
EAN 40
Packaging Unit
QTP-OPTIMAL 1x18-40
4008321873743
4008321873750
20
QTP-OPTIMAL 2x18-40
4008321873767
4008321873774
20
QTP-OPTIMAL 1x54-58
4008321873729
4008321873736
20
QTP-OPTIMAL 2x54-58
4008321880253
4008321880260
20
Lifetime
Measuring point
temperature tc:
Lifetime
with max. 10% failure rate
75 °C
50,000 h
65 °C
100,000 h
Expected lifetime
ECG ambient temperature (ta)
ECG
Lamp
HO 24
HO 39
QTP-OPTIMAL
1x18-40
L18
L30
L36
HO 24
HO 39
QTP-OPTIMAL
2x18-40
L18
L30
DL 18
HO54
QTP-OPTIMAL
1x54-58
L58
DL 55
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
40°C
100,000
50
100,000
55
100,000
50
100,000
50
100,000
55
100,000
505
100,000
60
100,000
50
100,000
55
100,000
50
100,000
55
100,000
55
100,000
55
50°C
100,000
60
100,000
60
100,000
60
100,000
60
100,000
60
100,000
60
100,000
65
100,000
60
100,000
60
100,000
60
100,000
60
100,000
60
100,000
60
60°C
80,000
70
80,000
70
90,000
70
80,000
70
80,000
70
80,000
70
50,000
75
80,000
65
70,000
70
90,000
65
70,000
70
80,000
70
70,000
70
LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
05
QUICKTRONIC PROFESSIONAL QTP-OPTIMAL
ECG ambient temperature (ta)
ECG
QTP-OPTIMAL
2x54-58
Lamp
HO54
L58
DL 55
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
lifetime [h]
temperature at tc-point [°C]
40°C
100,000
60
100,000
55
100,000
60
50°C
90,000
65
100,000
65
100,000
65
60°C
50,000
75
60,000
75
60,000
75
Expected lifetime is the calculation of the ECG lifetime according to
IEC_60929_Edition_4_2011. As background for this estimation, are the MTTF values
according to SN 29500 and the component- parameters used
LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
06
QUICKTRONIC PROFESSIONAL QTP-OPTIMAL
Lamp/ECG System Combination
ECG
QTP-OPTIMAL 1x18-40
QTP-OPTIMAL 2x18-40
Lamp
L 15
L 16 ES
L 18
L 18 U
DL 18
DF 18
HO 20 ES
HO 24
DL 24
DF 24
L 30
L 32 ES
HO 34 ES
L 36
L 36-1
DL 36
DF 36
HO 39
DL 40
2x L 15
2x L 16 ES
2x L 18
2x L 18 U
2x DL 18
2x DF 18
2x HO 20 ES
2x HO 24
2x DL 24
2x DF 24
2x L 30
2x L 32 ES
2x HO 34 ES
2x L 36
HF lamp
wattage [W]
13,5
14:2
16
16
16
16
20
23
22
22
30
29
34
32
32
32
32
38
40
13,5
14:2
16
16
16
16
20
23
22
22
30
29
34
32
System
wattage [W]
in preparation
in preparation
20.0
20.0
19.0
18.0
24.5
28.2
27.3
25.3
33.1
in preparation
36.7
35.8
35.8
35.6
33.8
41.3
44.4
in preparation
in preparation
39.0
39.0
36.2
33.6
47.6
52.9
53.8
49.7
63.0
in preparation
75.9
69.5
Line current [A]
in preparation
in preparation
0.10
0.10
0.09
0.08
0.11
0.13
0.12
0.12
0.15
in preparation
0.16
0.16
0.16
0.16
0.15
0.18
0.20
in preparation
in preparation
0.17
0.17
0.16
0.16
0.22
0.24
0.23
0.23
0.28
in preparation
0.34
0.31
Luminous flux at
25°C [lm]
950
1100
1350
1350
1200
1100
1650
1750
1800
1700
3000
2500
3250
3200
3200
2850
2750
3100
3675
950
1100
1350
1350
1200
1100
1650
1750
1800
1700
3000
2500
3250
Luminous flux at
35°C [lm]
2000
2000
3500
3500
-
3200
-
2000
2000
3500
Power factor
[λ]
in preparation
in preparation
0.95
0.95
0.9c
0.9c
0,98
0,98
0.95
0.95
0.95
in preparation
0.98
0.98
0.98
0.98
0.98
0.98
0.98
in preparation
in preparation
0.95
0.95
0.95
0.95
0.98
0.98
0.98
0.98
0.98
in preparation
0.99
0.98
LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
07
QUICKTRONIC PROFESSIONAL QTP-OPTIMAL
QTP-OPTIMAL 1x54-58
QTP-OPTIMAL 2x54-58
2x L 36-1
2x DL 36
2x DF 36
2x HO 39
DL 40
HO 50 ES
HO 54
DL 55
L 51 ES
L 58
2x HO 50 ES
2x HO 54
2x DL 55
2x L 51 ES
2x L 58
32
32
32
38
40
50
54
50
44.5
50
50
54
50
44.5
50
69.5
70.4
67.1
80.0
88.3
54
55
54
50
55
108
110
108
100
110
0.31
0.30
0.30
0.36
0.37
0.24
0.26
0.24
0.23
0.25
0.24
0.26
0.24
0.23
0.25
3200
2850
2750
3100
3675
4450
4450
4450
4200
5000
4450
4450
4450
4200
5000
3500
5000
5000
5000
5000
-
in preparation
0.98
0.98
0.99
0.99
0.98
0.98
0.98
0.96
0.98
0.98
0.98
0.98
0.96
0.99
For more information on ECG refer to http://www.osram.com/ecg
For more information on System Guarantee refer to http://www.osram.com/guarantee
LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
08