QUICKTRONIC PROFESSIONAL QTP-OPTIMAL osram.com QUICKTRONIC PROFESSIONAL QTP-OPTIMAL 1 ECG for T5/∅16mm, T8/∅26mm, DULUX L / F fluorescent lamps QTP-OPTIMAL i.e. LUMILUX® T5 HO ES LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 01 QUICKTRONIC PROFESSIONAL QTP-OPTIMAL Product Features: • • • • • • • • • • • One ECG for three lamp technologies; T5, T8, Dulux L / F 1 Up to 100.000 hours lifetime Lamp start with optimized filament preheating within 1.5 sec. Suitable for lighting with very high switching cycles Reliable lamp ignition between -20°C...+50°C Cut-off Technology 2 Suitable for luminaries of protection classes I and II 3 CELMA Energy Efficiency Index A2 BAT (Best Available Technology) Automatic safety shut-down in case of a defect or at the end of the lamp’s life (EoL T.2) Automatic restart after lamp replacement Suitable for emergency installations (DC operation) Technical Data Max. cross section 2 for IDC-contakt [mm ]: „s“ : 0.5; „f“ : 0.75 Max. cross section for 2 push-in contact [mm ]: „s“ : 0.5…1.0 4 5 4 Starting time: t: < 1 ,5 sec. (<0.3 sec. in case of line interruptions/switchover of <0.5 sec.) Line voltage: 220 - 240 V Voltage range (AC): 198 - 264 V Voltage range (DC): 176 - 276 V Line frequency: 0, 50 - 60 Hz Operating frequency: Electrical strength: 40 - 50 kHz 300 V permanent, 320 V 48 hours, 350 V 2 hours Ambient temperature ta: -20 °C to +50 °C Measuring point temperature tc: U-OUT: 1 2 3 4 5 max. +75 °C 330 V 430 V QTP-OPTIMAL 1x18-40 QTP-OPTIMAL 2x18-40 QTP-OPTIMAL 1x54-58 QTP-OPTIMAL 2x54-58 at T = 65°C @ Tc. 50.000 h with max. 10% failure rate at tc = 75°C max No need to connect earth in suitable luminaires of protection class II EEI: A2 for QTP-OPTIMAL 1x18-40 “s” = solid wire “f” = flexible wire LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 02 QUICKTRONIC PROFESSIONAL QTP-OPTIMAL Inrush current and max. number of ECG per circuit breaker ECG Inrush Current Ip [A] 24 37 37 57 QTP-OPTIMAL 1x18-40 QTP-OPTIMAL 2x18-40 QTP-OPTIMAL 1x54-58 QTP-OPTIMAL 2x54-58 Max. number of ECG per circuit breaker TH [µs] 230 200 200 150 B: 10A 17 12 12 8 B: 16A 28 19 19 13 C: 16 A 47 32 32 22 Standards and approval marks Safety: acc. to EN 61347-2-3 + A1 + A2:2006-02 / IEC 61347-2-3 (ed.2):2011 Radio interference: acc. EN 55015:2006 + A1:2007 + A2:2009 / CISPR 15: 2005 + A1:2006 + A2:2008 Harmonic content: acc. to EN 61000-3-2:2006 + A1:2009 + A2:2009 / IEC 61000-3-2:2005 + A1:2008 + A2:2009 Immunity: acc. to EN 61547:2009 / IEC 61547:2009 Approval marks: Dimensions & weight Description Description Length [mm] width [mm] height [mm] distance mounting holes [mm] Weight [g] QTP-OPTIMAL 1x18-40 280 30 21 270 170 QTP-OPTIMAL 2x18-40 360 30 21 350 230 QTP-OPTIMAL 1x54-58 280 30 21 270 160 QTP-OPTIMAL 2x54-58 360 30 21 350 240 LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 03 QUICKTRONIC PROFESSIONAL QTP-OPTIMAL Lamp wiring QTP-OPTIMAL 1x… 1 ~ 2 3 ~ 220... 240 V 21 22 23 24 L Max. permitted cable length between ECG and lamp: 2.0 m (PIN 21, 22); 1.0 m (PIN 23, 24) QTP-OPTIMAL 2x… 1 ~ 2 3 ~ 220... 240 V 21 22 23 24 25 26 L L Max. permitted cable length between ECG and lamp: 2.0 m (PIN 21, 22, 25, 26); 1.0 m (PIN 23, 24) LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 04 QUICKTRONIC PROFESSIONAL QTP-OPTIMAL Logistic Data Description EAN 10 EAN 40 Packaging Unit QTP-OPTIMAL 1x18-40 4008321873743 4008321873750 20 QTP-OPTIMAL 2x18-40 4008321873767 4008321873774 20 QTP-OPTIMAL 1x54-58 4008321873729 4008321873736 20 QTP-OPTIMAL 2x54-58 4008321880253 4008321880260 20 Lifetime Measuring point temperature tc: Lifetime with max. 10% failure rate 75 °C 50,000 h 65 °C 100,000 h Expected lifetime ECG ambient temperature (ta) ECG Lamp HO 24 HO 39 QTP-OPTIMAL 1x18-40 L18 L30 L36 HO 24 HO 39 QTP-OPTIMAL 2x18-40 L18 L30 DL 18 HO54 QTP-OPTIMAL 1x54-58 L58 DL 55 lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] 40°C 100,000 50 100,000 55 100,000 50 100,000 50 100,000 55 100,000 505 100,000 60 100,000 50 100,000 55 100,000 50 100,000 55 100,000 55 100,000 55 50°C 100,000 60 100,000 60 100,000 60 100,000 60 100,000 60 100,000 60 100,000 65 100,000 60 100,000 60 100,000 60 100,000 60 100,000 60 100,000 60 60°C 80,000 70 80,000 70 90,000 70 80,000 70 80,000 70 80,000 70 50,000 75 80,000 65 70,000 70 90,000 65 70,000 70 80,000 70 70,000 70 LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 05 QUICKTRONIC PROFESSIONAL QTP-OPTIMAL ECG ambient temperature (ta) ECG QTP-OPTIMAL 2x54-58 Lamp HO54 L58 DL 55 lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] lifetime [h] temperature at tc-point [°C] 40°C 100,000 60 100,000 55 100,000 60 50°C 90,000 65 100,000 65 100,000 65 60°C 50,000 75 60,000 75 60,000 75 Expected lifetime is the calculation of the ECG lifetime according to IEC_60929_Edition_4_2011. As background for this estimation, are the MTTF values according to SN 29500 and the component- parameters used LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 06 QUICKTRONIC PROFESSIONAL QTP-OPTIMAL Lamp/ECG System Combination ECG QTP-OPTIMAL 1x18-40 QTP-OPTIMAL 2x18-40 Lamp L 15 L 16 ES L 18 L 18 U DL 18 DF 18 HO 20 ES HO 24 DL 24 DF 24 L 30 L 32 ES HO 34 ES L 36 L 36-1 DL 36 DF 36 HO 39 DL 40 2x L 15 2x L 16 ES 2x L 18 2x L 18 U 2x DL 18 2x DF 18 2x HO 20 ES 2x HO 24 2x DL 24 2x DF 24 2x L 30 2x L 32 ES 2x HO 34 ES 2x L 36 HF lamp wattage [W] 13,5 14:2 16 16 16 16 20 23 22 22 30 29 34 32 32 32 32 38 40 13,5 14:2 16 16 16 16 20 23 22 22 30 29 34 32 System wattage [W] in preparation in preparation 20.0 20.0 19.0 18.0 24.5 28.2 27.3 25.3 33.1 in preparation 36.7 35.8 35.8 35.6 33.8 41.3 44.4 in preparation in preparation 39.0 39.0 36.2 33.6 47.6 52.9 53.8 49.7 63.0 in preparation 75.9 69.5 Line current [A] in preparation in preparation 0.10 0.10 0.09 0.08 0.11 0.13 0.12 0.12 0.15 in preparation 0.16 0.16 0.16 0.16 0.15 0.18 0.20 in preparation in preparation 0.17 0.17 0.16 0.16 0.22 0.24 0.23 0.23 0.28 in preparation 0.34 0.31 Luminous flux at 25°C [lm] 950 1100 1350 1350 1200 1100 1650 1750 1800 1700 3000 2500 3250 3200 3200 2850 2750 3100 3675 950 1100 1350 1350 1200 1100 1650 1750 1800 1700 3000 2500 3250 Luminous flux at 35°C [lm] 2000 2000 3500 3500 - 3200 - 2000 2000 3500 Power factor [λ] in preparation in preparation 0.95 0.95 0.9c 0.9c 0,98 0,98 0.95 0.95 0.95 in preparation 0.98 0.98 0.98 0.98 0.98 0.98 0.98 in preparation in preparation 0.95 0.95 0.95 0.95 0.98 0.98 0.98 0.98 0.98 in preparation 0.99 0.98 LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 07 QUICKTRONIC PROFESSIONAL QTP-OPTIMAL QTP-OPTIMAL 1x54-58 QTP-OPTIMAL 2x54-58 2x L 36-1 2x DL 36 2x DF 36 2x HO 39 DL 40 HO 50 ES HO 54 DL 55 L 51 ES L 58 2x HO 50 ES 2x HO 54 2x DL 55 2x L 51 ES 2x L 58 32 32 32 38 40 50 54 50 44.5 50 50 54 50 44.5 50 69.5 70.4 67.1 80.0 88.3 54 55 54 50 55 108 110 108 100 110 0.31 0.30 0.30 0.36 0.37 0.24 0.26 0.24 0.23 0.25 0.24 0.26 0.24 0.23 0.25 3200 2850 2750 3100 3675 4450 4450 4450 4200 5000 4450 4450 4450 4200 5000 3500 5000 5000 5000 5000 - in preparation 0.98 0.98 0.99 0.99 0.98 0.98 0.98 0.96 0.98 0.98 0.98 0.98 0.96 0.99 For more information on ECG refer to http://www.osram.com/ecg For more information on System Guarantee refer to http://www.osram.com/guarantee LE MK-EM TECG, Edition: 13.05.2013. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided. TECHNICAL INFORMATION 08