KFX - Power Entry Modules with Line Filter

KFX
Power Entry Modules with Line Filter
www.schurter.com/PG06
C14
70° C
Description
-Panel Mount:
Screw-on mounting from front side
-2 Functions:
Appliance Inlet Protection class I, Line-filter in standard version
-Quick connect terminals 6.3 x 0.8 mm
OU
T
IEC Appliance Inlet C14 with Filter, Increased Dielectric Strength
Characteristics
-Compact design with optimal shielding
-All single elements are already wired
-Universal line filter for standard applications
With enhanced surge withstand voltage
-Suitable for use in equipment according to IEC/UL 60950
References
-VDE Certificate Number: 40004665 (FGX)
-UL File Number: E72928 (FGX)
We recommend for new applications the type 5120 Last order date: 31.12.2014
E-
Approvals
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Mating
Connectors, e-Shop, SCHURTER-Stock-Check, Distributor-StockCheck, CAD-Drawings, Accessories, Detailed request for product
Newly available variants corresponding to V-Lock mating cordset. The connector is equipped with a notch intended for use with the latching cordset.
The cord latching system prevents against accidental removal of the cordset.
Technical Data
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
> 4 kV between L-N (CX1)
> 5 kV between L/N-PE
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
AS
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Impulse Withstand Voltage
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Line Filter
MTBF
C14 acc. to IEC 60320,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I
Standard Version, IEC 60939, UL 1283,
CSA C22.2 no. 8
Technical Details
> 3'100'000 h acc. to MIL-HB-217 F
PH
Terminal
Panel Thickness s
Appliance-Inlet/-Outlet
Material: Housing
Connectors
1
KFX
Power Entry Modules with Line Filter
www.schurter.com/PG06
Dimension
40 ±0.1
28.5
+0.5
0
ø 5.8x90°
28
40
49.3
KFX
T
ø 3.2
R3
max. 54
3.8
19.6
21.5
Technical Data of Filter-Components
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
2.2
1
Medical Version (M80)
2 x 10
47
1
Medical Version (M5)
2 x 10
47
2
Medical Version (M5)
2x4
47
Medical Version (M5)
2 x 1.5
47
Medical Version (M5)
2 x 0.8
47
Medical Version (M5)
1
Standard Version
2
Standard Version
4
Standard Version
6
Standard Version
10
Standard Version
L
N
47
-
2 x 10
47
2.2
2x4
47
2.2
2 x 1.5
47
2.2
2 x 0.8
47
2.2
2 x 0.3
47
2.2
L’
Cx
Cy
R
L2
PH
1) Line
2) Load
2
-
-
2 x 0.3
L1
1) PE
-
-
AS
Diagrams
Standard version
+0.5
0
E-
4
6
10
M3
5.8
max. 67
23.3
Rated Current
[A]
OU
R4
Connectors
Cy
PE’ 2)
N’
KFX
Power Entry Modules with Line Filter
www.schurter.com/PG06
Attenuation Loss
- - - - differential mode _____ common mode
Standard version
2A
4A
6A
10 A
All Variants
Type
Rated Current
[A]
CX Class
KFX
1
Standard Version
KFX
2
Standard Version
X1
4300.5062
KFX
4
Standard Version
X1
4300.5063
KFX
6
Standard Version
X1
4300.5064
KFX
10
Standard Version
X1
4300.5065
KFX
1
Medical Version (M5)
X1
4300.5101
KFX
2
Medical Version (M5)
X1
4300.5102
KFX
4
Medical Version (M5)
X1
4300.5103
KFX
6
Medical Version (M5)
X1
4300.5104
KFX
10
Medical Version (M5)
X1
4300.5105
X1
Order Number
4300.5061
AS
E-
Filter-Type
OU
T
1A
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-CheckSCHURTER
Suffix ".21" corresponds to the version with V-Lock mating cordset. The connector is equipped with a notch
intended for use with the latching cordset. The cord latching system prevents against accidental removal of the
cordset.
10 Pcs PH
Packaging unit Connectors
3
KFX
Power Entry Modules with Line Filter
www.schurter.com/PG06
Accessories
Description
T
Assorted Covers
Rear Cover
0859.0048
Cord retaining kits
Cord retaining strain relief
Flat head, Z
Countersunk, C
OU
0888.0021
4700.0003
Mating Outlets/Connectors
E-
Category / Description
Appliance Outlet Overview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder Terminal
4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal
4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal
5091
Appliance Outlet further types to KFX
Connector Overview complete
4782
4022 Mounting: Power Supply Cord, 3 x 1.5 mm², Screw clamps, Connector: IEC C13
4022
4785 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4785
4300-06 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4300-06
4012 Mounting: Power Supply Cord, 3 x 1.5 mm², Screw clamps, Connector: IEC C13
4012
Connector further types to KFX
...
AS
4782 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
Mating Outlets/Connectors shuttered
PH
Power Cord Overview complete
VAC17KS, North America, 2.0 m, Connector C17, cord end:
6051.2801
VAC17KS, Europlug, 2.0 m, Connector IEC C17, cord end:
6051.2803
VAC17KS, Europlug, 2.0 m, Connector IEC C17, cord end:
6051.2813
VAC13KS, Overview, diverse Connector IEC C13, cord end:
VAC13KS
Power Cord further types to KFX
4
Connectors
24.08.2015
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.