These compact and efficient power supplies are
optimized for machinery, with features that include
overload resistance and high performance reserves.
They also provide an increased level of reliability.
Should one phase fail, the three-phase PRO-M
power supply modules ­­continue to work reliably in
a two-phase operation.
The PRO-M Series power supplies are available in
single-phase and three-phase versions from 70 W to
1000 W, making them particularly suited for use in
many automation applications. The wide-ranging AC
and DC inputs, broad operating temperature range
and international approvals make the PRO-M supplies
a strong choice.
Weidmuller’s new PRO-M Series Switchmode Power
Supplies offer a host of advantages. Available in 10
different versions, the 24 VDC PRO-M power supplies
all feature a solid ultra-slim metal housing, and are
designed to mount on a DIN-rail with no ventilation gap
required between multiple units. This feature provides up
to a 50% savings in space and allows the PRO-M to fit
into the tightest spaces in control cabinets or machines.
• Slim housings for space saving installation in
the cabinet
• DIN-rail mountable without any gap
(no clearance necessary)
• Operating temperature range of -25°C to +70°C
• Autoselect Input for wide input range without any
switch; for DC and AC voltages
• Power boost of 120% enables inductive and
capacitive loads; additional starting capacity
with up to a 2-minute boost
• Parallel connections allow simple power increase
for up to five units without diode module
• MTBF > 500,000 Hours
Canada
Mexico
United States
Weidmuller, Canada
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (877) 300-5635
Email: [email protected]
Website: www.weidmuller.ca
Weidmuller, Mexico
Blvd. Hermanos Serdán 698
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: [email protected]
Website: www.weidmuller.com.mx
Weidmuller
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: [email protected]
Website: www.weidmuller.com
PRO-M SERIES
Single Phase Input Power Supplies
Technical Data
General Specifications
L (+)
AC
N (–)
+
DC
PE
–
Two-Phase operation also possible
L1 (+)
AC
L2 (–)
L3
+
DC
PE
–
Permissible maximum continuous current [A]
Max. limiting average on state current [A]
Type\Temp.
1ph 24V / 3A
1ph 24V / 5A
1ph 24V / 7.5A
45°C
3.6
6
9
1ph 24V / 10A
1ph 24V / 20A 1ph 24V / 40A 3ph 24V / 5A 3ph 24V / 10A
3ph 24V / 20A
3ph 24V / 40A
12
24
48
6
12
24
48
50°C 55°C 60°C65°C70°C
3.3
3.0
2.6 2.2 1.8
5.5
5.0
4.4 3.8 3.1
8.6 8.25 7.5 6.75 5.6
11.5
23
46
5.75
11.5
23
46
11
22
44
5.5
11
22
44
10
20
40
5
10
20
40
9
18
36
4.5
9
18
36
7.5
15
30
3.7
7.5
15
30
Current limiting > 120 % IN
Ambient temp. operating / storage –25 °C … +70 °C / –40 °C … +85 °C
Max. perm. air humidity (operation) Protection class Class of protection Overvoltage category 20 %…95 % RH
IP20
I, with PE connection
II
Pollution severity Insulation voltage MTBF Protection against reverse voltages from the load Parallel connection option Housing version Indication 2
4 kV I/O / 2 kV I/ground / 0.5 kV O/ground
> 500,000 h acc. to IEC 1709 (SN29500)
30…35 V DC
yes, without diode module
metal, corrosion resistant
operation, green LED
Mounting position, installation notice horizontal on mounting rail TS35,
50 mm spacing top and bottom for free air circulation,
can be mounted side by side with no space in between
EMC / shock / vibration
Noise emission acc. to EN55022 Noise immunity tests acc. to Limiting of mains voltage harmonic currents Class B
EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),
EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted),
EN61000-4-11 (Dips)
Acc. to EN 61000-3-2
Resistance against vibration and shock Electrical safety (applied standards)
Acc. to EN50178, shock: 5g in all directions
Electrical equipment of machines Safety transformers for switched-mode power units Machinery with electronic equipment Safety extra-low voltage Protective separation / protection against electrical shock
Acc. to EN60204
Acc. to EN61558-2-17
Acc. to EN50178 / VDE0160
SELV acc. to EN60950, PELV acc. to EN60204
VDE0100-410 / acc. to DIN57100-410
Protection against dangerous shock currents Acc. to VDE0106-101
Project Planning Data
Type
Rated input voltage­­
Mains voltage range
Mains input current (max/min)
Rec. fuse [char..]
Efficiency @ 230VAC
Rated power loss [W]
Installation width
mm
24 V / 3 A
24 V / 5 A
1.9...0.6 A
2 A / D I
6 A, [B]
2...4 A, [C]
88%
10 W
33
3.2...1.0 A
4 A / D I
6 A, [B]
3...5 A, [C]
89 %
15 W
40
24 V / 7.5 A
24 V / 10 A
1 - phase
100...240 V AC
85...264 V AC
4.7...1.6 A
3.2...1.1 A
6 A / D I
6 A / D I
16 A, [B]
16 A, [B]
5...10 A, [C]
5...10 A, [C]
90 %
90 %
20 W
27 W
50
60
Input terminals
Conductor, solid min/max
mm2
0.5...6
Conductor, flexible min/max
mm2
0.5...2.5
Conductor, AWG/kcmil min/max
26 / 12
Output terminals Number plus/minus
2 / 2
Conductor, solid min/max
mm2
0.5...6
2
Conductor, flexible min/max
mm 0.5...2.5
Conductor, AWG/kcmil min/max
26 / 12
2
24 V / 20 A
24 V / 40 A
24 V / 5 A
6.4...2.1 A
12.7...4.1 A 0.4...0.2 A
10 A / D I
16 A / D I
2 A / D I
20 A, [B]
25 A, [B]
-
10...12 A, [C] 14...16 A, [C] 1...2 A, [C]
> 90 %
> 90 %
90 %
53 W
106 W
13 W
121
180
40
24 V / 10 A
24 V / 20 A
3 - phase
3 x 400...500 V AC
3 x 320...575 V AC
0.7...0.4 A
1.3...0.7 A
2 A / D I
2 A / D I
-
-
2...3 A, [C]
3...5 A, [C]
> 90 %
> 90 %
26 W
53 W
60
121
24 V / 40 A
2.6...1.2 A
4A/DI
10 A, [B]
6...8 A, [C]
> 90 %
107 W
180
Screw connection
0.5...60.5...6 0.5...6
0.5...2.50.5...2.5 0.5...2.5
26 / 10
26 / 12
26 / 12
Screw connection
2/3
0.5...6 0.5...16
0.5...2.52.5...10
26 / 10 26 / 6
0.5...6
0.5...2.5
26 / 12
0.5...60.5...16
0.5...2.5 2.5...0
26 / 10
26 / 6
Single Phase Input Power Supplies
PRO-M SERIES
CP M SNT 70W 24V 3A
CP M SNT 120W 24V 5A
Derating Curve
Ordering Data
Type CP M SNT 70W 24V 3A Part No.
8951330000
Type CP M SNT 120W 24V 5A
Part No.
8951340000
Technical Data
Input Specifications
Rated input voltage
AC input voltage range
AC frequency range
100...240 V AC (wide-range input)
85...264 V AC
47...63 Hz
80...370 V DC
0.80 A @ 230 V AC / 1.5A @ 115 V AC
100...240 V AC (wide-range input)
85...264 V AC
47...63 Hz
80...370 V DC
1.3 A @ 230 V AC / 2.4 A @ 115 V AC
0.25 A @ 370 V DC / 1.1 A @ 80 V DC
yes/max. 20 A
0.5 A @ 370 V DC / 1.8 A @ 80 V DC
yes/max. 30 A
2 A / DI, safety fuse
6 A, Char. B, Circuit breaker
2...4 A, Char. C, Circuit breaker
4 A / DI, safety fuse
6 A, Char. B, Circuit breaker
3...5 A, Char. C, Circuit breaker
Power boost @ 24 V DC, 60 °C
24 V DC ± 1 %
22.5…29.5 V DC (adjustable via potentiometer on front)
100 mVss @ 24 V DC, IN
3 A @ 55 °C
3.6 A @ 45 °C
3.3 A @ 50 °C
1.8 A @ 70 °C
3.6 A for 1 min, ED=5 %
24 V DC ± 1 %
22.5…29.5 V DC (adjustable via potentiometer on front)
100 mVss @ 24 V DC, IN
5 A @ 55 °C
6.0 A @ 45 °C
5.5 A @ 50 °C
3.1 A @ 70 °C
6 A for 1 min, ED=5 %
General Specifications
Efficiency
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Length x Width x Height Weight
88 % @ 230 V AC / > 85 % @ 115 V AC
> 0.5 @ 230 V AC / > 0.53 @ 115 V AC
> 100 ms @ 230 V AC / > 20 ms @ 100 V AC
yes
125 x 33 x 130
0.69 kg
89 % @ 230 V AC / > 85 % @ 115 V AC
> 0.5 @ 230 V AC / > 0.53 @ 115 V AC
> 100 ms @ 230 V AC / > 20 ms @ 100 V AC
yes
125 x 40 x 130
0.8 kg
CE, cURus, UL508, CSA22.2 no.107
CE, cURus, UL508, CSA22.2 no.107
InputOutput
Screw connection Screw Connection
3 for L/N/PE 4 (++/--)
0.5 / 6 0.5 / 6
0.5 / 2.5 0.5 / 2,.5
26 / 12 26 / 12
InputOutput
Screw connection Screw Connection
3 for L/N/PE 5 (++/---)
0.5 / 6 0.5 / 6
0.5 / 2.5 0.5 / 2.5
26 / 12 26 / 26
* Recommendation applies only for AC operation; the max.
permissible operating voltage is to be observed in all cases!
* Recommendation applies only for AC operation; the max.
permissible operating voltage is to be observed in all cases!
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal)/Inrush current
Circuit Protection
Output Specifications
Rated output voltage
Output voltage
Residual ripple, switching peaks
Rated output current @ Vrated
Continuous output current @ 24 V DC
mm
Approvals/Certifications
Connection Data
Type of connection
Number of terminals
Conductor cross-section, rigid min/max Conductor cross-section, flexible min/max Conductor cross-section, AWG/kcmil min/max
mm²
mm²
3
PRO-M SERIES
Single-Phase Input Power Supplies
CP M SNT 180W 24V 7.5A
CP M SNT 250W 24V 10A
Derating Curve
Temperature De-Rating
% of Nominal Current
120%
100%
80%
60%
40%
20%
0%
0%
10%
20%
30%
40%
50%
60%
65%
70%
Ambient Temperature (°C)
­­­
Ordering Data
Type CP M SNT 180W 24V 7.5A
Part No.
8951350000
Type
CP M SNT 250W 24V 10A
Part No.
8951360000
Technical Data
Input Specifications
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal)/Inrush current
Circuit Protection­­­
Output Specifications
Rated output voltage
Output voltage
Residual ripple, switching peaks
Rated output current @ Vrated
Continuous output current @ 24 V DC
Power boost @ 24 V DC, 60 °C
General Specifications
Efficiency
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Length x Width x Height Weight
mm
100...240 V AC (wide-range input)
85...264 V AC
47...63 Hz
80...370 V DC
1.9 A @ 230 V AC / 3.6 A @ 115 V AC
100...240 V AC (wide-range input)
85...264 V AC
47...63 Hz
80...370 V DC
1.3 A @ 230 V AC / 2.5 A @ 115 V AC
0.6 A @ 370 V DC / 2.6 A @ 80 V DC
yes
6 A / DI, safety fuse
16 A, Char. B, Circuit breaker
5...10 A, Char. C, Circuit breaker
0.9 A @ 370 V DC / 3.4 A @ 80 V DC
yes
6 A / DI, safety fuse
16 A, Char. B, Circuit breaker
5...10 A, Char. C, Circuit breaker
24 V DC ± 1 %
22.5…29.5 V DC (adjustable via potentiometer on front)
24 V DC ± 1 %
22.5…29.5 V DC (adjustable via potentiometer on front)
100 mVss @ 24 V DC, IN
7.5 A @ 60 °C
9.0 A @ 45 °C
8.2 A @ 55 °C
5.6 A @ 70 °C
9 A for 1 min, ED=5 %
100 mVss @ 24 V DC, IN
10 A @ 60 °C
12 A @ 45 °C
11 A @ 55 °C
7.5 A @ 70 °C
12 A for 1 min, ED=5 %
90 % @ 230 V AC / > 85 % @ 115 V AC
> 0.5 @ 230 V AC / > 0.53 @ 115 V AC
> 40 ms @ 230 V AC / > 20 ms @ 100 V AC
yes
150 x 50 x 130
1.0 kg
90 % @ 230 V AC / > 85 % @ 115 V AC
> 0.98 @ 230 V AC / > 0.98 @ 115 V AC
> 40 ms @ 230 V AC / > 20 ms @ 100 V AC
yes
150 x 60 x 130
1.2 kg
CE, cURus, UL508, CSA22.2 no.107
CE, cURus, UL508, CSA22.2 no.107
InputOutput
Screw connection Screw Connection
3 for L/N/PE 5 (++/---)
0.5 / 6 0.5 / 6
0.5 / 2.5 0.5 / 2.5
26 / 12 26 / 12
InputOutput
Screw connection Screw Connection
3 for L/N/PE 5 (++/---)
0.5 / 6 0.5 / 6
0.5 / 2.5 0.5 / 2.5
26 / 12 26 / 12
* Recommendation applies only for AC operation; the max.
permissible operating voltage is to be observed in all cases!
* Recommendation applies only for AC operation; the max.
permissible operating voltage is to be observed in all cases!
Approvals/Certifications
Connection Data
Type of connection
Number of terminals
Conductor cross-section, rigid min/max Conductor cross-section, flexible min/max Conductor cross-section, AWG/kcmil min/max
4
mm²
mm²
Single Phase Input Power Supplies
PRO-M SERIES
CP M SNT 500W 24V 20A
CP M SNT 1000W 24V 40A
Derating Curve
Temperature De-Rating
% of Nominal Current
120%
100%
80%
60%
40%
20%
0%
0%
10%
20%
30%
40%
50%
60%
65%
70%
Ambient Temperature (°C)
Ordering Data
Type CP M SNT 500W 24V 20A
Technical Data
Part No.
8951370000
Type CP M SNT 1000W 24V 40A
Part No.
8951380000
Input Specifications
Rated input voltage
AC input voltage range
AC frequency range
100...240 V AC wide-range input)
85...264 V AC
47...63 Hz
80...370 V DC
2.5 A @ 230 V AC / 4.9 A @ 115 V AC
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal)/Inrush current
Circuit Protection
1.6 A @ 370 V DC / 6.8 A @ 80 V DC
yes
10 A / DI, safety fuse
20 A, Char. B, Circuit breaker
10...12 A, Char. C, Circuit breaker
100...240 V AC (wide-range input)
85...264 V AC
47...63 Hz
80...370 V DC
4.9 A @ 230 V AC / 9.6 A @ 115 V AC
3.0 A @ 370 V DC / 13.5 A @ 80 V DC
yes
16 A / DI, safety fuse
25 A, Char. B, Circuit breaker
14...16 A, Char. C, Circuit breaker
Output Specifications
Rated output voltage
Output voltage
Residual ripple, switching peaks
Rated output current @ Vrated
Continuous output current @ 24 V DC
Power boost @ 24 V DC, 60 °C
General Specifications
Efficiency
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Length x Width x Height Weight
mm
24 V DC ± 1 %
22.5…29.5 V DC (adjustable via potentiometer on front)
100 mVss @ 24 V DC, IN
20 A @ 60 °C
24 A @ 45 °C
22 A @ 55 °C
15 A @ 70 °C
24 A for 1 min, ED=5 %
24 V DC ± 1 %
> 90 % @ 230 V AC / > 85 % @ 115 V AC
> 0.98 @ 230 V AC / > 0.98 @ 115 V AC
> 40 ms @ 230 V AC / > 20 ms @ 100 V AC
yes
150 x 121 x 130
1.5 kg
> 90 % @ 230 V AC / > 85 % @ 115 V AC
> 0.98 @ 230 V AC / > 0.98 @ 115 V AC
> 40 ms @ 230 V AC / > 20 ms @ 100 V AC
yes
150 x 180 x 130
1.5 kg
CE, cURus, UL508, CSA22.2 no.107
CE, cURus, UL508, CSA22.2 no.107
InputOutput
Screw connection Screw Connection
3 for L/N/PE 5 (++/---)
0.5 / 6 0.5 / 6
0.5 / 2.5 0.5 / 2.5
26 / 10 26 / 10
InputOutput
Screw connection Screw Connection
3 for L/N/PE 5 (++/---)
0.5 / 6 0.5 / 16
0.5 / 2.5 2.5 / 10
26 / 10 26 / 6
* Recommendation applies only for AC operation; the max.
permissible operating voltage is to be observed in all cases!
* Recommendation applies only for AC operation; the max.
permissible operating voltage is to be observed in all cases!
22.5…29.5 V DC (adjustable via potentiometer on front)
100 mVss @ 24 V DC, IN
40 A @ 60 °C
48 A @ 45 °C
44 A @ 55 °C
30 A @ 70 °C
48 A for 1 min, ED=5 %
Approvals/Certifications
Connection Data
Type of connection
Number of terminals
Conductor cross-section, rigid min/max Conductor cross-section, flexible min/max Conductor cross-section, AWG/kcmil min/max
mm²
mm²
5
PRO-M SERIES
Three-Phase Input Power Supplies
CP M SNT3 120W 24V 5A
CP M SNT3 250W 24V 10A
Derating Curve
Temperature De-Rating
% of Nominal Current
120%
100%
80%
60%
40%
20%
0%
0%
10%
20%
30%
40%
50%
60%
65%
70%
Ambient Temperature (°C)
Ordering Data
Type CP M SNT3 120W 24V 5A
Part No.
8951390000
Type CP M SNT3 250W 24V 10A
Part No.
8951400000
Technical Data
Input Specifications
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal)
Circuit Protection
Output Specifications
Rated output voltage
Output voltage
Residual ripple, switching peaks
Rated output current @ Vrated
Continuous output current @ 24 V DC
Power boost @ 24 V DC, 60 °C
General Specifications
Efficiency
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Length x Width x Height Weight
mm
3 x 400...3 x 500 V AC (wide-range input)
3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC acc. to UL508)
0.25 A @ 3 x 500 V AC / 0.3 A @ 3 x 400 V AC
3 x 400...3 x 500 V AC (wide-range input)
3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC acc. to UL508)
0.5 A @ 3 x 500 V AC / 0.6 A @ 3 x 400 V AC
0.2 A @ 800 V DC / 0.4 A @ 450 V DC
no
0.4 A @ 800 V DC / 0.7 A @ 450 V DC
no
2 A / DI, safety fuse
1...2 A, Char. C, Circuit breaker
2 A / DI, safety fuse
2...3 A, Char. ­C, Circuit breaker
24 V DC ± 1 %
22.5…29.5 V DC (adjustable via potentiometer on front)
100 mVss @ 24 V DC, IN
5 A @ 60 °C
6.0 A @ 45 °C
5.5 A @ 55 °C
3.7 A @ 70 °C
6 A for 1 min, ED=5 %
24 V DC ± 1 %
22.5…29.5 V DC (adjustable via potentiometer on front)
100 mVss @ 24 V DC,IN
10 A @ 60 °C
12 A @ 45 °C
11 A @ 55 °C
7.5 A @ 70 °C
12 A for 1 min, ED=5 %
90 % @ 3 x 500 V AC / > 90 % @ 3 x 400 V AC
> 0.75 @ 3 x 500 V AC / > 0.78 @ 3 x 400 V AC
> 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes
125 x 40 x 130
0.55 kg
90 % @ 3 x 500 V AC / > 90 % @ 3 x 400 V AC
> 0.75 @ 3 x 500 V AC / > 0.78 @ 3 x 400 V AC
> 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes
150 x 60 x 130
0.9 kg
CE, cURus, UL508, CSA22.2 no.107
CE, cURus, UL508, CSA22.2 no.107
InputOutput
Screw connection Screw Connection
4 for L1/L2/L3/PE 5 (++/---)
0.5 / 6 0.5 / 6
0.5 / 2.5 0.5 / 2.5
26 / 12 26 / 12
InputOutput
Screw connection Screw Connection
4 for L1/L2/L3/PE 5 (++/---)
0.5 / 6 0.5 / 6
0.5 / 2.5 0.5 / 2.5
26 / 12 26 / 12
* Recommendation applies only for AC operation; the max.
permissible operating voltage is to be observed in all cases!
* Recommendation applies only for AC operation; the max.
permissible operating voltage is to be observed in all cases!
Approvals/Certifications
Connection Data
Type of connection
Number of terminals
Conductor cross-section, rigid min/max Conductor cross-section, flexible min/max Conductor cross-section, AWG/kcmil min/max
6
mm²
mm²
Three Phase Input Power Supplies
PRO-M SERIES
CP M SNT3 500W 24V 20A
CP M SNT3 1000W 24V 40A
Derating Curve
Temperature De-Rating
% of Nominal Current
120%
100%
80%
60%
40%
20%
0%
0%
10%
20%
30%
40%
50%
60%
65%
70%
Ambient Temperature (°C)
Ordering Data
Type CP M SNT3 500W 24V 20A
Part No.
8951410000
Type CP M SNT3 1000W 24V 40A Part No.
8951420000
Technical Data
Input Specifications
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
3 x 400...3 x 500 V AC (wide-range input)
3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC acc. to UL508)
0.9 A @ 3 x 500 V AC / 1.1 A @ 3 x 400 V AC
3 x 400...3 x 500 V AC (wide-range input)
3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC acc. to UL508)
1.8 A @ 3 x 500 V AC / 2.1A @ 3 x 400 V AC
0.7 A @ 800 V DC / 1.3 A @ 450 V DC
no
1.4 A @ 800 V DC / 2.5A @ 450 V DC
no
2 A / DI, safety fuse
3...5 A, Char. C, Circuit breaker
4 A / DI, safety fuse
10 A, Char. B, Circuit breaker
6...8 A, Char. C, Circuit breaker
Power boost @ 24 V DC, 60 °C
24 V DC ± 1 %
22.5…29.5 V DC (adjustable via potentiometer on front)
100 mVss @ 24 V DC, IN
20 A @ 60 °C
24 A @ 45 °C
22 A @ 55 °C
15 A @ 70 °C
24 A for 1 min, ED=5 %
24 V DC ± 1 %
22.5…29.5 V DC (adjustable via potentiometer on front)
100 mVss @ 24 V DC, IN
40 A @ 60 °C
48 A @ 45 °C
44 A @ 55 °C
30 A @ 70 °C
48 A for 1 min, ED=5 %
General Specifications
Efficiency
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Length x Width x Height Weight
> 90 % @ 3 x 500 V AC / > 91 % @ 3 x 400 V AC
> 0.75 @ 3 x 500 V AC / > 0.78 @ 3 x 400 V AC
> 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes
150 x 121 x 130
1.5 kg
> 90 % @ 3 x 500 V AC / 92 % @ 3 x 400 V AC
> 0.75 @ 3 x 500 V AC / > 0.78 @ 3 x 400 V AC
> 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes
150 x 180 x 130
2.9 kg
CE, cURus, UL508, CSA22.2 no.107
CE, cURus, UL508, CSA22.2 no.107
InputOutput
Screw connection Screw Connection
4 for L1/L2/L3/PE 5 (++/---)
0.5 / 6 0.5 / 6
0.5 / 2.5 0.5 / 2.5
26 /10 26 / 10
InputOutput
Screw connection Screw Connection
4 for L1/L2/L3/PE 5 (++/---)
0.5 / 6 0.5 / 16
0.5 / 2.5 0.5 / 10
26 / 10 26 / 6
* Recommendation applies only for AC operation; the max.
permissible operating voltage is to be observed in all cases!
* Recommendation applies only for AC operation; the max.
permissible operating voltage is to be observed in all cases!
AC current consumption
DC current consumption
Input fuse (internal)
Circuit Protection
Output Specifications
Rated output voltage
Output voltage
Residual ripple, switching peaks
Rated output current @ Vrated
Continuous output current @ 24 V DC
mm
Approvals/Certifications
Connection Data
Type of connection
Number of terminals
Conductor cross-section, rigid min/max Conductor cross-section, flexible min/max Conductor cross-section, AWG/kcmil min/max
mm²
mm²
7
PRO-M SERIES
Diode Modules
PRO-M: Diode Modules
CP M DM20
CP DM40
L
H
W
1+
3+
4+
1+
11
3+
4+
11
12
14
12
14
12-
34-
12-
34-
21
21
22
24
22
24
2+
2+
Ordering Data
Type
Part No.
1222210000
CP M DM20
Type
Part No.
1222220000
CP M DM40
Technical Data
Input Specifications
Rated input voltage
Input voltage range AC
24 V DC
18…30 V DC
2 x 10 A or 1 x 20 A
24 V DC
18…30 V DC
2 x 20 A or 1 x 40 A
24 V DC
Input voltage - 0.7 V
20 A DC @ 60 °C
24 A @ 45 °C
22.5 A @ 55 °C
15 A @ 70 °C
yes, in both inputs
21.6 V DC, relay is on for Power Good
20.4 V DC, relay is off for Power Fail
Max. 30 V DC / 1 A, CO contact
24 V DC
Input voltage - 0.7 V
40 A @ 60 °C
48 A @ 45 °C
45 A @ 55 °C
30 A @ 70 °C
yes, in both inputs
21.6 V DC, relay is on for Power Good
20.4 V DC, relay is off for Power Fail
Max. 30 V DC / 1 A, CO contact
> 97 % @ 24 V input voltage
150 x 34 x 130
0.3 kg
-25…+70 °C / -40 °C…+85 °C
5 %…95 % RH
IP20
III, without PE connection, for SELV
2
0.5 kV
> 500.000 h according to IEC 1709 (SN29500)
Horizontal on TS35 mounting rail, with 50 mm space at top and
bottom. Direct side by side mounting allowed.
> 97 % @ 24 V input voltage
150 x 60 x 130
0.6 kg
-25…+70 °C / -40 °C…+85 °C
5 %…95 % RH
IP20
III, without PE connection, for SELV
2
0.5 kV
> 500.000 h according to IEC 1709 (SN29500)
Horizontal on TS35 mounting rail, with 50 mm space at top and
bottom. Direct side by side mounting allowed.
Class B
EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),
EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted)
Class B
EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),
EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted)
Resistance against vibration and shock
1 g according to EN50178 / 15 g in all directions
1 g according to EN50178 / 15 g in all directions
Electrical safety (applied standards)
Electrical equipment of machines
Safety transformers for switched-mode power units
Safety extra low voltage
according to EN60204
according to EN50178 / VDE0160
SELV according to EN60950, PELV according to EN60204
according to EN60204
according to EN50178 / VDE0160
SELV according to EN60950, PELV according to EN60204
Approvals
Pending
CE, TUV, cCSAus, GL, GOST
CE, TUV, cULus, GL, GOST
Connection data
Conductor connection system
Number of terminals
Conductor cross section, rigid min/maxmm²
Conductor cross section, flexible min/maxmm²
Conductor cross section, AWG/kcmil min/max
Input
Screw connection
4 (1+, 2+, 1-, 2-)
0.5 / 6
0.5 / 2.5
26 / 12
Input current
Output Specifications
Rated output voltage
Output voltage
Rated (nominal) output current @ UN
Continous output current @ 24 V DC
Voltage monitoring
Switching thresholds
Potential free, floating contacts
General Specifications
Degree of efficiency
Length x width x height
Weight
Ambient temperature (operational) / Storage temperature
Max. permitted humidity (operational)
Degree of protection
Class of protection
Pollution degree
Insulation voltage I/O to housing
MTBF
Mounting position, installation notice
mm
EMC / shock / vibration
Noise emission acc. to EN55022
Noise immunity tests acc. to
8
Output
Screw connection
4 (3+, 4+, 3-, 4-)
0.5 / 6
0.5 / 2.5
26 / 12
Input
Screw connection
4 (1+, 2+, 1-, 2-)
0.5 / 16
2.5 / 10
22 / 6
Output
Screw connection
4 (3+, 4+, 3-, 4-)
0.5 / 16
2.5 / 10
22 / 6
Relay Module
PRO-M SERIES
PRO-M: Relay Module
CP M RM24
H
L
W
red
+
black
–
11
12
14
Ordering Data
Type
Part No.
1222230000
CP M RM24
Technical Data
Input Specifications
Rated input voltage
Input voltage range DC
24 V DC
18…30 V DC
Output Specifications
Voltage monitoring
yes
Switching thresholds
21.6 V DC, relay is on for Power Good
20.4 V DC, relay is off for Power Fail
Potential free, floating contacts
Max. 30 V DC / 1 A, CO contact
General Specifications
Length x width x height
Weight
Ambient temperature (operational) / Storage temperature
Max. permitted humidity (operational)
Degree of protection
Class of protection
Pollution degree
Insulation voltage I/O to housing
MTBF
Mounting position, installation notice
mm
EMC / shock / vibration
Noise emission acc. to EN55022
Noise immunity tests acc. to
22 x 33 x 28
75 g
-25…+70 °C / -40 °C…+85 °C
5 %…95 % RH
IP20
III, without PE connection, for SELV
2
0.5 kV
> 500.000 h according to IEC 1709 (SN29500)
Plugged in to the front of the PRO-M power supply
Class B
EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),
EN61000-4-4 (Burst), EN61000-4-5 (Surge),
EN610004-6 (conducted), EN61000-4-11 (Dips)
Resistance against vibration and shock
1 g according to EN50178 / 15 g in all directions
Electrical safety (applied standards)
Electrical equipment of machines
Safety transformers for switch mode power units
Safety extra low voltage
according to EN60204
according to EN50178 / VDE0160
SELV according to EN60950, PELV according to EN60204
Approvals
Pending
CE, TUV, cULus, GL, GOST
Connection data
Conductor connection system
Number of terminals
Conductor cross section, rigid min/maxmm²
Conductor cross section, flexible min/maxmm²
Conductor cross section, AWG/kcmil min/max
Input
10 cm cable (red/black) with ferrules
Output
PUSH IN
3 (Changeover contact)
0.2 / 1.5
0.2 / 1.5
24 / 16
9
PRO-M SERIES
Capacity Module
PRO-M: Capacity Module
CP M CAP
Pulse triggering for cable circuit breakers:
with the Weidmuller capacitance module
The following conditions apply to the table entries:
• Ambient temperature of 20 °C
• Inner resistance of the circuit breakers is taken
into account
• Half of the rated current flows to a neighbouring
circuit before the short circuit is formed
• DC-compatible circuit breakers: Siemens 5SY series
+
11
12
14
12-
Distance in m
Fuse Tripping
Ordering Data
Type
Part No.
1222240000
CP M CAP
Technical Data
Input Specifications
Rated input voltage
24 V DC
Input voltage range DC
18…30 V DC
Output Specifications
Peak current output
Recovery time for the capacitor
Voltage monitoring
Depending on load
approx. 1 s
yes
Conductor cross section
0.75 mm2
1.0 mm2
1.5 mm2
2.5 mm2
4 mm2
6 mm2
B6
10 m
14 m
20 m
30 m
50 m
B10
6m
9m
15 m
24 m
B16
Switching thresholds
21.6 V DC, relay is on for Power Good
20.4 V DC, relay is off for Power Fail
Max. 30 V DC / 1 A, CO contact
Potential free, floating contacts
General Specifications
Length x width x height
Weight
Ambient temperature (operational) / Storage temperature
Max. permitted humidity (operational)
Degree of protection
Class of protection
Pollution degree
Insulation voltage I/O to housing
MTBF
Mounting position, installation notice
Load
Power supply
+
CAP module
1+
2+
mm
EMC / shock / vibration
Noise emission acc. to EN55022
Noise immunity tests acc. to
150 x 34 x 130
0.4 kg
-25…+70 °C / -40 °C…+85 °C
5 %…95 % RH
IP20
III, without PE connection, for SELV
2
0.5 kV
> 500.000 h according to IEC 1709 (SN29500)
Horizontal on TS35 mounting rail, with 50 mm space at top and
bottom. Direct side by side mounting allowed
Resistance against vibration and shock
Class B
EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),
EN61000-4-4 (Burst), EN61000-4-5 (Surge),
EN610004-6 (conducted), EN61000-4-11 (Dips)
1 g according to EN50178 / 15 g in all directions
Electrical safety (applied standards)
Electrical equipment of machines
Safety transformers for switch mode power units
Safety extra low voltage
according to EN60204
according to EN50178 / VDE0160
SELV according to EN60950, PELV according to EN60204
0.75 mm2
1.0 mm2
1.5 mm2
2.5 mm2
4 mm2
6 mm2
0.75 mm2
1.0 mm2
1.5 mm2
2.5 mm2
4 mm2
6 mm2
0.75 mm2
1.0 mm2
1.5 mm2
2.5 mm2
4 mm2
6 mm2
4m
6m
10 m
16 m
C2
11 m
14 m
21 m
34 m
C4
6m
8m
12 m
19 m
32 m
C6
3m
3,5 m
5,5 m
9m
14 m
C10
2m
3m
5m
8m
12 m
Approvals
CE, TUV, GL
Pending
cULus, GOST
Connection data
Conductor connection system
Number of terminals
Conductor cross section, rigid min/maxmm²
Conductor cross section, flexible min/maxmm²
Conductor cross section, AWG/kcmil min/max
Input
Screw connection
4 (++--)
0.5 / 6
0.5 / 4
26 / 12
10
Output
Screw connection
3 (Changeover contact)
0.5 / 6
0.5 / 2.5
26 / 12
Subject to technical changes • 2/12-XM-LIT0924