Datasheet PRO-M Series Power Supplies NEW These compact and efficient power supplies are optimized for machinery, with features that include overload resistance and high performance reserves. They also provide an increased level of reliability. Should one phase fail, the three-phase PRO-M power supply modules continue to work reliably in a two-phase operation. The PRO-M Series power supplies are available in single-phase and three-phase versions from 70 W to 1000 W, making them particularly suited for use in many automation applications. The wide-ranging AC and DC inputs, broad operating temperature range and international approvals make the PRO-M supplies a strong choice. Weidmuller’s new PRO-M Series Switchmode Power Supplies offer a host of advantages. Available in 10 different versions, the 24 VDC PRO-M power supplies all feature a solid ultra-slim metal housing, and are designed to mount on a DIN-rail with no ventilation gap required between multiple units. This feature provides up to a 50% savings in space and allows the PRO-M to fit into the tightest spaces in control cabinets or machines. • Slim housings for space saving installation in the cabinet • DIN-rail mountable without any gap (no clearance necessary) • Operating temperature range of -25°C to +70°C • Autoselect Input for wide input range without any switch; for DC and AC voltages • Power boost of 120% enables inductive and capacitive loads; additional starting capacity with up to a 2-minute boost • Parallel connections allow simple power increase for up to five units without diode module • MTBF > 500,000 Hours Canada Mexico United States Weidmuller, Canada 10 Spy Court Markham, Ontario L3R 5H6 Telephone: (800) 268-4080 Facsimile: (877) 300-5635 Email: [email protected] Website: www.weidmuller.ca Weidmuller, Mexico Blvd. Hermanos Serdán 698 Col. San Rafael Oriente Puebla, Puebla, Mexico C.P. 72029 Telephone: 01 222 2686267 Facsimile: 01 222 2686219 Email: [email protected] Website: www.weidmuller.com.mx Weidmuller 821 Southlake Blvd. Richmond, Virginia 23236 Telephone: (800) 849-9343 Facsimile: (804) 379-2593 Email: [email protected] Website: www.weidmuller.com PRO-M SERIES Single Phase Input Power Supplies Technical Data General Specifications L (+) AC N (–) + DC PE – Two-Phase operation also possible L1 (+) AC L2 (–) L3 + DC PE – Permissible maximum continuous current [A] Max. limiting average on state current [A] Type\Temp. 1ph 24V / 3A 1ph 24V / 5A 1ph 24V / 7.5A 45°C 3.6 6 9 1ph 24V / 10A 1ph 24V / 20A 1ph 24V / 40A 3ph 24V / 5A 3ph 24V / 10A 3ph 24V / 20A 3ph 24V / 40A 12 24 48 6 12 24 48 50°C 55°C 60°C65°C70°C 3.3 3.0 2.6 2.2 1.8 5.5 5.0 4.4 3.8 3.1 8.6 8.25 7.5 6.75 5.6 11.5 23 46 5.75 11.5 23 46 11 22 44 5.5 11 22 44 10 20 40 5 10 20 40 9 18 36 4.5 9 18 36 7.5 15 30 3.7 7.5 15 30 Current limiting > 120 % IN Ambient temp. operating / storage –25 °C … +70 °C / –40 °C … +85 °C Max. perm. air humidity (operation) Protection class Class of protection Overvoltage category 20 %…95 % RH IP20 I, with PE connection II Pollution severity Insulation voltage MTBF Protection against reverse voltages from the load Parallel connection option Housing version Indication 2 4 kV I/O / 2 kV I/ground / 0.5 kV O/ground > 500,000 h acc. to IEC 1709 (SN29500) 30…35 V DC yes, without diode module metal, corrosion resistant operation, green LED Mounting position, installation notice horizontal on mounting rail TS35, 50 mm spacing top and bottom for free air circulation, can be mounted side by side with no space in between EMC / shock / vibration Noise emission acc. to EN55022 Noise immunity tests acc. to Limiting of mains voltage harmonic currents Class B EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted), EN61000-4-11 (Dips) Acc. to EN 61000-3-2 Resistance against vibration and shock Electrical safety (applied standards) Acc. to EN50178, shock: 5g in all directions Electrical equipment of machines Safety transformers for switched-mode power units Machinery with electronic equipment Safety extra-low voltage Protective separation / protection against electrical shock Acc. to EN60204 Acc. to EN61558-2-17 Acc. to EN50178 / VDE0160 SELV acc. to EN60950, PELV acc. to EN60204 VDE0100-410 / acc. to DIN57100-410 Protection against dangerous shock currents Acc. to VDE0106-101 Project Planning Data Type Rated input voltage Mains voltage range Mains input current (max/min) Rec. fuse [char..] Efficiency @ 230VAC Rated power loss [W] Installation width mm 24 V / 3 A 24 V / 5 A 1.9...0.6 A 2 A / D I 6 A, [B] 2...4 A, [C] 88% 10 W 33 3.2...1.0 A 4 A / D I 6 A, [B] 3...5 A, [C] 89 % 15 W 40 24 V / 7.5 A 24 V / 10 A 1 - phase 100...240 V AC 85...264 V AC 4.7...1.6 A 3.2...1.1 A 6 A / D I 6 A / D I 16 A, [B] 16 A, [B] 5...10 A, [C] 5...10 A, [C] 90 % 90 % 20 W 27 W 50 60 Input terminals Conductor, solid min/max mm2 0.5...6 Conductor, flexible min/max mm2 0.5...2.5 Conductor, AWG/kcmil min/max 26 / 12 Output terminals Number plus/minus 2 / 2 Conductor, solid min/max mm2 0.5...6 2 Conductor, flexible min/max mm 0.5...2.5 Conductor, AWG/kcmil min/max 26 / 12 2 24 V / 20 A 24 V / 40 A 24 V / 5 A 6.4...2.1 A 12.7...4.1 A 0.4...0.2 A 10 A / D I 16 A / D I 2 A / D I 20 A, [B] 25 A, [B] - 10...12 A, [C] 14...16 A, [C] 1...2 A, [C] > 90 % > 90 % 90 % 53 W 106 W 13 W 121 180 40 24 V / 10 A 24 V / 20 A 3 - phase 3 x 400...500 V AC 3 x 320...575 V AC 0.7...0.4 A 1.3...0.7 A 2 A / D I 2 A / D I - - 2...3 A, [C] 3...5 A, [C] > 90 % > 90 % 26 W 53 W 60 121 24 V / 40 A 2.6...1.2 A 4A/DI 10 A, [B] 6...8 A, [C] > 90 % 107 W 180 Screw connection 0.5...60.5...6 0.5...6 0.5...2.50.5...2.5 0.5...2.5 26 / 10 26 / 12 26 / 12 Screw connection 2/3 0.5...6 0.5...16 0.5...2.52.5...10 26 / 10 26 / 6 0.5...6 0.5...2.5 26 / 12 0.5...60.5...16 0.5...2.5 2.5...0 26 / 10 26 / 6 Single Phase Input Power Supplies PRO-M SERIES CP M SNT 70W 24V 3A CP M SNT 120W 24V 5A Derating Curve Ordering Data Type CP M SNT 70W 24V 3A Part No. 8951330000 Type CP M SNT 120W 24V 5A Part No. 8951340000 Technical Data Input Specifications Rated input voltage AC input voltage range AC frequency range 100...240 V AC (wide-range input) 85...264 V AC 47...63 Hz 80...370 V DC 0.80 A @ 230 V AC / 1.5A @ 115 V AC 100...240 V AC (wide-range input) 85...264 V AC 47...63 Hz 80...370 V DC 1.3 A @ 230 V AC / 2.4 A @ 115 V AC 0.25 A @ 370 V DC / 1.1 A @ 80 V DC yes/max. 20 A 0.5 A @ 370 V DC / 1.8 A @ 80 V DC yes/max. 30 A 2 A / DI, safety fuse 6 A, Char. B, Circuit breaker 2...4 A, Char. C, Circuit breaker 4 A / DI, safety fuse 6 A, Char. B, Circuit breaker 3...5 A, Char. C, Circuit breaker Power boost @ 24 V DC, 60 °C 24 V DC ± 1 % 22.5…29.5 V DC (adjustable via potentiometer on front) 100 mVss @ 24 V DC, IN 3 A @ 55 °C 3.6 A @ 45 °C 3.3 A @ 50 °C 1.8 A @ 70 °C 3.6 A for 1 min, ED=5 % 24 V DC ± 1 % 22.5…29.5 V DC (adjustable via potentiometer on front) 100 mVss @ 24 V DC, IN 5 A @ 55 °C 6.0 A @ 45 °C 5.5 A @ 50 °C 3.1 A @ 70 °C 6 A for 1 min, ED=5 % General Specifications Efficiency Power factor (approx.) Mains buffering @ Irated Parallel connection option Length x Width x Height Weight 88 % @ 230 V AC / > 85 % @ 115 V AC > 0.5 @ 230 V AC / > 0.53 @ 115 V AC > 100 ms @ 230 V AC / > 20 ms @ 100 V AC yes 125 x 33 x 130 0.69 kg 89 % @ 230 V AC / > 85 % @ 115 V AC > 0.5 @ 230 V AC / > 0.53 @ 115 V AC > 100 ms @ 230 V AC / > 20 ms @ 100 V AC yes 125 x 40 x 130 0.8 kg CE, cURus, UL508, CSA22.2 no.107 CE, cURus, UL508, CSA22.2 no.107 InputOutput Screw connection Screw Connection 3 for L/N/PE 4 (++/--) 0.5 / 6 0.5 / 6 0.5 / 2.5 0.5 / 2,.5 26 / 12 26 / 12 InputOutput Screw connection Screw Connection 3 for L/N/PE 5 (++/---) 0.5 / 6 0.5 / 6 0.5 / 2.5 0.5 / 2.5 26 / 12 26 / 26 * Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! * Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! DC input voltage range AC current consumption DC current consumption Input fuse (internal)/Inrush current Circuit Protection Output Specifications Rated output voltage Output voltage Residual ripple, switching peaks Rated output current @ Vrated Continuous output current @ 24 V DC mm Approvals/Certifications Connection Data Type of connection Number of terminals Conductor cross-section, rigid min/max Conductor cross-section, flexible min/max Conductor cross-section, AWG/kcmil min/max mm² mm² 3 PRO-M SERIES Single-Phase Input Power Supplies CP M SNT 180W 24V 7.5A CP M SNT 250W 24V 10A Derating Curve Temperature De-Rating % of Nominal Current 120% 100% 80% 60% 40% 20% 0% 0% 10% 20% 30% 40% 50% 60% 65% 70% Ambient Temperature (°C) Ordering Data Type CP M SNT 180W 24V 7.5A Part No. 8951350000 Type CP M SNT 250W 24V 10A Part No. 8951360000 Technical Data Input Specifications Rated input voltage AC input voltage range AC frequency range DC input voltage range AC current consumption DC current consumption Input fuse (internal)/Inrush current Circuit Protection Output Specifications Rated output voltage Output voltage Residual ripple, switching peaks Rated output current @ Vrated Continuous output current @ 24 V DC Power boost @ 24 V DC, 60 °C General Specifications Efficiency Power factor (approx.) Mains buffering @ Irated Parallel connection option Length x Width x Height Weight mm 100...240 V AC (wide-range input) 85...264 V AC 47...63 Hz 80...370 V DC 1.9 A @ 230 V AC / 3.6 A @ 115 V AC 100...240 V AC (wide-range input) 85...264 V AC 47...63 Hz 80...370 V DC 1.3 A @ 230 V AC / 2.5 A @ 115 V AC 0.6 A @ 370 V DC / 2.6 A @ 80 V DC yes 6 A / DI, safety fuse 16 A, Char. B, Circuit breaker 5...10 A, Char. C, Circuit breaker 0.9 A @ 370 V DC / 3.4 A @ 80 V DC yes 6 A / DI, safety fuse 16 A, Char. B, Circuit breaker 5...10 A, Char. C, Circuit breaker 24 V DC ± 1 % 22.5…29.5 V DC (adjustable via potentiometer on front) 24 V DC ± 1 % 22.5…29.5 V DC (adjustable via potentiometer on front) 100 mVss @ 24 V DC, IN 7.5 A @ 60 °C 9.0 A @ 45 °C 8.2 A @ 55 °C 5.6 A @ 70 °C 9 A for 1 min, ED=5 % 100 mVss @ 24 V DC, IN 10 A @ 60 °C 12 A @ 45 °C 11 A @ 55 °C 7.5 A @ 70 °C 12 A for 1 min, ED=5 % 90 % @ 230 V AC / > 85 % @ 115 V AC > 0.5 @ 230 V AC / > 0.53 @ 115 V AC > 40 ms @ 230 V AC / > 20 ms @ 100 V AC yes 150 x 50 x 130 1.0 kg 90 % @ 230 V AC / > 85 % @ 115 V AC > 0.98 @ 230 V AC / > 0.98 @ 115 V AC > 40 ms @ 230 V AC / > 20 ms @ 100 V AC yes 150 x 60 x 130 1.2 kg CE, cURus, UL508, CSA22.2 no.107 CE, cURus, UL508, CSA22.2 no.107 InputOutput Screw connection Screw Connection 3 for L/N/PE 5 (++/---) 0.5 / 6 0.5 / 6 0.5 / 2.5 0.5 / 2.5 26 / 12 26 / 12 InputOutput Screw connection Screw Connection 3 for L/N/PE 5 (++/---) 0.5 / 6 0.5 / 6 0.5 / 2.5 0.5 / 2.5 26 / 12 26 / 12 * Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! * Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! Approvals/Certifications Connection Data Type of connection Number of terminals Conductor cross-section, rigid min/max Conductor cross-section, flexible min/max Conductor cross-section, AWG/kcmil min/max 4 mm² mm² Single Phase Input Power Supplies PRO-M SERIES CP M SNT 500W 24V 20A CP M SNT 1000W 24V 40A Derating Curve Temperature De-Rating % of Nominal Current 120% 100% 80% 60% 40% 20% 0% 0% 10% 20% 30% 40% 50% 60% 65% 70% Ambient Temperature (°C) Ordering Data Type CP M SNT 500W 24V 20A Technical Data Part No. 8951370000 Type CP M SNT 1000W 24V 40A Part No. 8951380000 Input Specifications Rated input voltage AC input voltage range AC frequency range 100...240 V AC wide-range input) 85...264 V AC 47...63 Hz 80...370 V DC 2.5 A @ 230 V AC / 4.9 A @ 115 V AC DC input voltage range AC current consumption DC current consumption Input fuse (internal)/Inrush current Circuit Protection 1.6 A @ 370 V DC / 6.8 A @ 80 V DC yes 10 A / DI, safety fuse 20 A, Char. B, Circuit breaker 10...12 A, Char. C, Circuit breaker 100...240 V AC (wide-range input) 85...264 V AC 47...63 Hz 80...370 V DC 4.9 A @ 230 V AC / 9.6 A @ 115 V AC 3.0 A @ 370 V DC / 13.5 A @ 80 V DC yes 16 A / DI, safety fuse 25 A, Char. B, Circuit breaker 14...16 A, Char. C, Circuit breaker Output Specifications Rated output voltage Output voltage Residual ripple, switching peaks Rated output current @ Vrated Continuous output current @ 24 V DC Power boost @ 24 V DC, 60 °C General Specifications Efficiency Power factor (approx.) Mains buffering @ Irated Parallel connection option Length x Width x Height Weight mm 24 V DC ± 1 % 22.5…29.5 V DC (adjustable via potentiometer on front) 100 mVss @ 24 V DC, IN 20 A @ 60 °C 24 A @ 45 °C 22 A @ 55 °C 15 A @ 70 °C 24 A for 1 min, ED=5 % 24 V DC ± 1 % > 90 % @ 230 V AC / > 85 % @ 115 V AC > 0.98 @ 230 V AC / > 0.98 @ 115 V AC > 40 ms @ 230 V AC / > 20 ms @ 100 V AC yes 150 x 121 x 130 1.5 kg > 90 % @ 230 V AC / > 85 % @ 115 V AC > 0.98 @ 230 V AC / > 0.98 @ 115 V AC > 40 ms @ 230 V AC / > 20 ms @ 100 V AC yes 150 x 180 x 130 1.5 kg CE, cURus, UL508, CSA22.2 no.107 CE, cURus, UL508, CSA22.2 no.107 InputOutput Screw connection Screw Connection 3 for L/N/PE 5 (++/---) 0.5 / 6 0.5 / 6 0.5 / 2.5 0.5 / 2.5 26 / 10 26 / 10 InputOutput Screw connection Screw Connection 3 for L/N/PE 5 (++/---) 0.5 / 6 0.5 / 16 0.5 / 2.5 2.5 / 10 26 / 10 26 / 6 * Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! * Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! 22.5…29.5 V DC (adjustable via potentiometer on front) 100 mVss @ 24 V DC, IN 40 A @ 60 °C 48 A @ 45 °C 44 A @ 55 °C 30 A @ 70 °C 48 A for 1 min, ED=5 % Approvals/Certifications Connection Data Type of connection Number of terminals Conductor cross-section, rigid min/max Conductor cross-section, flexible min/max Conductor cross-section, AWG/kcmil min/max mm² mm² 5 PRO-M SERIES Three-Phase Input Power Supplies CP M SNT3 120W 24V 5A CP M SNT3 250W 24V 10A Derating Curve Temperature De-Rating % of Nominal Current 120% 100% 80% 60% 40% 20% 0% 0% 10% 20% 30% 40% 50% 60% 65% 70% Ambient Temperature (°C) Ordering Data Type CP M SNT3 120W 24V 5A Part No. 8951390000 Type CP M SNT3 250W 24V 10A Part No. 8951400000 Technical Data Input Specifications Rated input voltage AC input voltage range AC frequency range DC input voltage range AC current consumption DC current consumption Input fuse (internal) Circuit Protection Output Specifications Rated output voltage Output voltage Residual ripple, switching peaks Rated output current @ Vrated Continuous output current @ 24 V DC Power boost @ 24 V DC, 60 °C General Specifications Efficiency Power factor (approx.) Mains buffering @ Irated Parallel connection option Length x Width x Height Weight mm 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0.25 A @ 3 x 500 V AC / 0.3 A @ 3 x 400 V AC 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0.5 A @ 3 x 500 V AC / 0.6 A @ 3 x 400 V AC 0.2 A @ 800 V DC / 0.4 A @ 450 V DC no 0.4 A @ 800 V DC / 0.7 A @ 450 V DC no 2 A / DI, safety fuse 1...2 A, Char. C, Circuit breaker 2 A / DI, safety fuse 2...3 A, Char. C, Circuit breaker 24 V DC ± 1 % 22.5…29.5 V DC (adjustable via potentiometer on front) 100 mVss @ 24 V DC, IN 5 A @ 60 °C 6.0 A @ 45 °C 5.5 A @ 55 °C 3.7 A @ 70 °C 6 A for 1 min, ED=5 % 24 V DC ± 1 % 22.5…29.5 V DC (adjustable via potentiometer on front) 100 mVss @ 24 V DC,IN 10 A @ 60 °C 12 A @ 45 °C 11 A @ 55 °C 7.5 A @ 70 °C 12 A for 1 min, ED=5 % 90 % @ 3 x 500 V AC / > 90 % @ 3 x 400 V AC > 0.75 @ 3 x 500 V AC / > 0.78 @ 3 x 400 V AC > 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC yes 125 x 40 x 130 0.55 kg 90 % @ 3 x 500 V AC / > 90 % @ 3 x 400 V AC > 0.75 @ 3 x 500 V AC / > 0.78 @ 3 x 400 V AC > 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC yes 150 x 60 x 130 0.9 kg CE, cURus, UL508, CSA22.2 no.107 CE, cURus, UL508, CSA22.2 no.107 InputOutput Screw connection Screw Connection 4 for L1/L2/L3/PE 5 (++/---) 0.5 / 6 0.5 / 6 0.5 / 2.5 0.5 / 2.5 26 / 12 26 / 12 InputOutput Screw connection Screw Connection 4 for L1/L2/L3/PE 5 (++/---) 0.5 / 6 0.5 / 6 0.5 / 2.5 0.5 / 2.5 26 / 12 26 / 12 * Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! * Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! Approvals/Certifications Connection Data Type of connection Number of terminals Conductor cross-section, rigid min/max Conductor cross-section, flexible min/max Conductor cross-section, AWG/kcmil min/max 6 mm² mm² Three Phase Input Power Supplies PRO-M SERIES CP M SNT3 500W 24V 20A CP M SNT3 1000W 24V 40A Derating Curve Temperature De-Rating % of Nominal Current 120% 100% 80% 60% 40% 20% 0% 0% 10% 20% 30% 40% 50% 60% 65% 70% Ambient Temperature (°C) Ordering Data Type CP M SNT3 500W 24V 20A Part No. 8951410000 Type CP M SNT3 1000W 24V 40A Part No. 8951420000 Technical Data Input Specifications Rated input voltage AC input voltage range AC frequency range DC input voltage range 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0.9 A @ 3 x 500 V AC / 1.1 A @ 3 x 400 V AC 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 1.8 A @ 3 x 500 V AC / 2.1A @ 3 x 400 V AC 0.7 A @ 800 V DC / 1.3 A @ 450 V DC no 1.4 A @ 800 V DC / 2.5A @ 450 V DC no 2 A / DI, safety fuse 3...5 A, Char. C, Circuit breaker 4 A / DI, safety fuse 10 A, Char. B, Circuit breaker 6...8 A, Char. C, Circuit breaker Power boost @ 24 V DC, 60 °C 24 V DC ± 1 % 22.5…29.5 V DC (adjustable via potentiometer on front) 100 mVss @ 24 V DC, IN 20 A @ 60 °C 24 A @ 45 °C 22 A @ 55 °C 15 A @ 70 °C 24 A for 1 min, ED=5 % 24 V DC ± 1 % 22.5…29.5 V DC (adjustable via potentiometer on front) 100 mVss @ 24 V DC, IN 40 A @ 60 °C 48 A @ 45 °C 44 A @ 55 °C 30 A @ 70 °C 48 A for 1 min, ED=5 % General Specifications Efficiency Power factor (approx.) Mains buffering @ Irated Parallel connection option Length x Width x Height Weight > 90 % @ 3 x 500 V AC / > 91 % @ 3 x 400 V AC > 0.75 @ 3 x 500 V AC / > 0.78 @ 3 x 400 V AC > 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC yes 150 x 121 x 130 1.5 kg > 90 % @ 3 x 500 V AC / 92 % @ 3 x 400 V AC > 0.75 @ 3 x 500 V AC / > 0.78 @ 3 x 400 V AC > 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC yes 150 x 180 x 130 2.9 kg CE, cURus, UL508, CSA22.2 no.107 CE, cURus, UL508, CSA22.2 no.107 InputOutput Screw connection Screw Connection 4 for L1/L2/L3/PE 5 (++/---) 0.5 / 6 0.5 / 6 0.5 / 2.5 0.5 / 2.5 26 /10 26 / 10 InputOutput Screw connection Screw Connection 4 for L1/L2/L3/PE 5 (++/---) 0.5 / 6 0.5 / 16 0.5 / 2.5 0.5 / 10 26 / 10 26 / 6 * Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! * Recommendation applies only for AC operation; the max. permissible operating voltage is to be observed in all cases! AC current consumption DC current consumption Input fuse (internal) Circuit Protection Output Specifications Rated output voltage Output voltage Residual ripple, switching peaks Rated output current @ Vrated Continuous output current @ 24 V DC mm Approvals/Certifications Connection Data Type of connection Number of terminals Conductor cross-section, rigid min/max Conductor cross-section, flexible min/max Conductor cross-section, AWG/kcmil min/max mm² mm² 7 PRO-M SERIES Diode Modules PRO-M: Diode Modules CP M DM20 CP DM40 L H W 1+ 3+ 4+ 1+ 11 3+ 4+ 11 12 14 12 14 12- 34- 12- 34- 21 21 22 24 22 24 2+ 2+ Ordering Data Type Part No. 1222210000 CP M DM20 Type Part No. 1222220000 CP M DM40 Technical Data Input Specifications Rated input voltage Input voltage range AC 24 V DC 18…30 V DC 2 x 10 A or 1 x 20 A 24 V DC 18…30 V DC 2 x 20 A or 1 x 40 A 24 V DC Input voltage - 0.7 V 20 A DC @ 60 °C 24 A @ 45 °C 22.5 A @ 55 °C 15 A @ 70 °C yes, in both inputs 21.6 V DC, relay is on for Power Good 20.4 V DC, relay is off for Power Fail Max. 30 V DC / 1 A, CO contact 24 V DC Input voltage - 0.7 V 40 A @ 60 °C 48 A @ 45 °C 45 A @ 55 °C 30 A @ 70 °C yes, in both inputs 21.6 V DC, relay is on for Power Good 20.4 V DC, relay is off for Power Fail Max. 30 V DC / 1 A, CO contact > 97 % @ 24 V input voltage 150 x 34 x 130 0.3 kg -25…+70 °C / -40 °C…+85 °C 5 %…95 % RH IP20 III, without PE connection, for SELV 2 0.5 kV > 500.000 h according to IEC 1709 (SN29500) Horizontal on TS35 mounting rail, with 50 mm space at top and bottom. Direct side by side mounting allowed. > 97 % @ 24 V input voltage 150 x 60 x 130 0.6 kg -25…+70 °C / -40 °C…+85 °C 5 %…95 % RH IP20 III, without PE connection, for SELV 2 0.5 kV > 500.000 h according to IEC 1709 (SN29500) Horizontal on TS35 mounting rail, with 50 mm space at top and bottom. Direct side by side mounting allowed. Class B EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted) Class B EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted) Resistance against vibration and shock 1 g according to EN50178 / 15 g in all directions 1 g according to EN50178 / 15 g in all directions Electrical safety (applied standards) Electrical equipment of machines Safety transformers for switched-mode power units Safety extra low voltage according to EN60204 according to EN50178 / VDE0160 SELV according to EN60950, PELV according to EN60204 according to EN60204 according to EN50178 / VDE0160 SELV according to EN60950, PELV according to EN60204 Approvals Pending CE, TUV, cCSAus, GL, GOST CE, TUV, cULus, GL, GOST Connection data Conductor connection system Number of terminals Conductor cross section, rigid min/maxmm² Conductor cross section, flexible min/maxmm² Conductor cross section, AWG/kcmil min/max Input Screw connection 4 (1+, 2+, 1-, 2-) 0.5 / 6 0.5 / 2.5 26 / 12 Input current Output Specifications Rated output voltage Output voltage Rated (nominal) output current @ UN Continous output current @ 24 V DC Voltage monitoring Switching thresholds Potential free, floating contacts General Specifications Degree of efficiency Length x width x height Weight Ambient temperature (operational) / Storage temperature Max. permitted humidity (operational) Degree of protection Class of protection Pollution degree Insulation voltage I/O to housing MTBF Mounting position, installation notice mm EMC / shock / vibration Noise emission acc. to EN55022 Noise immunity tests acc. to 8 Output Screw connection 4 (3+, 4+, 3-, 4-) 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 4 (1+, 2+, 1-, 2-) 0.5 / 16 2.5 / 10 22 / 6 Output Screw connection 4 (3+, 4+, 3-, 4-) 0.5 / 16 2.5 / 10 22 / 6 Relay Module PRO-M SERIES PRO-M: Relay Module CP M RM24 H L W red + black – 11 12 14 Ordering Data Type Part No. 1222230000 CP M RM24 Technical Data Input Specifications Rated input voltage Input voltage range DC 24 V DC 18…30 V DC Output Specifications Voltage monitoring yes Switching thresholds 21.6 V DC, relay is on for Power Good 20.4 V DC, relay is off for Power Fail Potential free, floating contacts Max. 30 V DC / 1 A, CO contact General Specifications Length x width x height Weight Ambient temperature (operational) / Storage temperature Max. permitted humidity (operational) Degree of protection Class of protection Pollution degree Insulation voltage I/O to housing MTBF Mounting position, installation notice mm EMC / shock / vibration Noise emission acc. to EN55022 Noise immunity tests acc. to 22 x 33 x 28 75 g -25…+70 °C / -40 °C…+85 °C 5 %…95 % RH IP20 III, without PE connection, for SELV 2 0.5 kV > 500.000 h according to IEC 1709 (SN29500) Plugged in to the front of the PRO-M power supply Class B EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted), EN61000-4-11 (Dips) Resistance against vibration and shock 1 g according to EN50178 / 15 g in all directions Electrical safety (applied standards) Electrical equipment of machines Safety transformers for switch mode power units Safety extra low voltage according to EN60204 according to EN50178 / VDE0160 SELV according to EN60950, PELV according to EN60204 Approvals Pending CE, TUV, cULus, GL, GOST Connection data Conductor connection system Number of terminals Conductor cross section, rigid min/maxmm² Conductor cross section, flexible min/maxmm² Conductor cross section, AWG/kcmil min/max Input 10 cm cable (red/black) with ferrules Output PUSH IN 3 (Changeover contact) 0.2 / 1.5 0.2 / 1.5 24 / 16 9 PRO-M SERIES Capacity Module PRO-M: Capacity Module CP M CAP Pulse triggering for cable circuit breakers: with the Weidmuller capacitance module The following conditions apply to the table entries: • Ambient temperature of 20 °C • Inner resistance of the circuit breakers is taken into account • Half of the rated current flows to a neighbouring circuit before the short circuit is formed • DC-compatible circuit breakers: Siemens 5SY series + 11 12 14 12- Distance in m Fuse Tripping Ordering Data Type Part No. 1222240000 CP M CAP Technical Data Input Specifications Rated input voltage 24 V DC Input voltage range DC 18…30 V DC Output Specifications Peak current output Recovery time for the capacitor Voltage monitoring Depending on load approx. 1 s yes Conductor cross section 0.75 mm2 1.0 mm2 1.5 mm2 2.5 mm2 4 mm2 6 mm2 B6 10 m 14 m 20 m 30 m 50 m B10 6m 9m 15 m 24 m B16 Switching thresholds 21.6 V DC, relay is on for Power Good 20.4 V DC, relay is off for Power Fail Max. 30 V DC / 1 A, CO contact Potential free, floating contacts General Specifications Length x width x height Weight Ambient temperature (operational) / Storage temperature Max. permitted humidity (operational) Degree of protection Class of protection Pollution degree Insulation voltage I/O to housing MTBF Mounting position, installation notice Load Power supply + CAP module 1+ 2+ mm EMC / shock / vibration Noise emission acc. to EN55022 Noise immunity tests acc. to 150 x 34 x 130 0.4 kg -25…+70 °C / -40 °C…+85 °C 5 %…95 % RH IP20 III, without PE connection, for SELV 2 0.5 kV > 500.000 h according to IEC 1709 (SN29500) Horizontal on TS35 mounting rail, with 50 mm space at top and bottom. Direct side by side mounting allowed Resistance against vibration and shock Class B EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted), EN61000-4-11 (Dips) 1 g according to EN50178 / 15 g in all directions Electrical safety (applied standards) Electrical equipment of machines Safety transformers for switch mode power units Safety extra low voltage according to EN60204 according to EN50178 / VDE0160 SELV according to EN60950, PELV according to EN60204 0.75 mm2 1.0 mm2 1.5 mm2 2.5 mm2 4 mm2 6 mm2 0.75 mm2 1.0 mm2 1.5 mm2 2.5 mm2 4 mm2 6 mm2 0.75 mm2 1.0 mm2 1.5 mm2 2.5 mm2 4 mm2 6 mm2 4m 6m 10 m 16 m C2 11 m 14 m 21 m 34 m C4 6m 8m 12 m 19 m 32 m C6 3m 3,5 m 5,5 m 9m 14 m C10 2m 3m 5m 8m 12 m Approvals CE, TUV, GL Pending cULus, GOST Connection data Conductor connection system Number of terminals Conductor cross section, rigid min/maxmm² Conductor cross section, flexible min/maxmm² Conductor cross section, AWG/kcmil min/max Input Screw connection 4 (++--) 0.5 / 6 0.5 / 4 26 / 12 10 Output Screw connection 3 (Changeover contact) 0.5 / 6 0.5 / 2.5 26 / 12 Subject to technical changes • 2/12-XM-LIT0924