Download

Datasheet
connectPower PROeco
Single- and three-phase switched-mode power supply units
NEW
The new switch-mode power supply units of the PROeco
series fit optimally in machine construction applications
where space, ease of use and efficiency are top priorities.
Direct parallel operation, a status relay and adjustable
output voltage are basic features required for most every
application. A visual display indicates the upper load limit
from 90% and makes servicing and integrating the PROeco
power supplies particularly easy. With an extremely low
depth profile of only 100 mm, the supplies are ideal for use
in the smallest of spaces, such as electrical cabinets and low
profile distribution enclosures.
The efficiency levels of up to 93% level is considerably
higher than conventional power supplies in this class and,
thanks to the associated reduced heat generation, use in
small cabinets is easy.
Features:
• Slim design with extremely narrow housing depth
of 100 mm
• Wide operating temperature range: –25°C…+70°C
• The output voltage can be precisely adjusted via a
potentiometer on supply front
• Remote monitoring via integrated status relay
• Three-colored LED indicators for simple error detection
• Advanced visual warning indication at 90% of rated
output current
• High efficiency of up to 93% on selected models
• International approvals: CE, TÜV and cULus
Weidmuller, Canada
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (877) 300-5635
Email: [email protected]
Website: www.weidmuller.ca
Weidmuller, Mexico
Blvd. Hermanos Serdán 698,
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: [email protected]
Website: www.weidmuller.com.mx
Weidmuller, United States
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: [email protected]
Website: www.weidmuller.com
connectPower PROeco
PROeco power supplies with
basic functionality and a high
level of reliability
•Single- and three-phase switchedmode power supply units
•Slim design
•Large temperature range from –25 °C
to 70 °C
•The output voltage can be precisely
adjusted via the potentiometer on the
front
•Remote monitoring via integrated
status relay
•Three-colored LED indicators for
simple error detection
•Advanced visual warning at 90%
rated output current
• International approvals
%
Short-circuit protection
Overload protection
Overtemperature protection
EMC / shock / vibration
Noise emission acc. to EN55022
Noise immunity tests acc. to
Limiting of mains voltage harmonic currents
Resistance against vibration and shock
Electrical safety (applied standards)
Electrical equipment of machines
Safety transformers for switched-mode power units
Machinery with electronic equipment
Safety extra-low voltage
Protective separation / protection against
electrical shock
Protection against dangerous shock currents
–25 °C…+70 °C / –40 °C…+85 °C
5 %…95 % RH
IP 20
I, with PE connection
2
3 kV I/O / 2 kV I/earth / 0.5 kV O/earth
> 500.000 h acc. to IEC 1709 (SN29500)
yes, max. 5 without diode module
metal, corrosion resistant
horizontal on mounting rail TS 35, 50 mm spacing
top and bottom for free air circulation, can be mounted
side-by-side with 15 mm space between units.
Yes, automatic restart
Yes, IU characteristic curve
Yes, automatic restart
Class B
EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8
(Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge),
EN61000-4-6 (conducted), EN61000-4-11 (Dips)
Acc. to EN61000-3-2
1 g acc. to EN50178, shock: 15 g in all directions
80
60
40
20
0
–25
75
50
25
0
80
100
60
70
960 Watt
60
40
20
0
–25
0
20
30
40
50
Ambient temperature (°C)
Voltage derating
90
80
70
50
60
70
60
100
40
60
80
190
20
20
30
40
50
Ambient temperature (°C)
100
VDE0100-410 / acc. to DIN57100-410
0
0
120
110
IU Characteristic curve
2
100
Acc. to EN60204
Acc. to EN61558-2-17
Acc. to EN50178 / VDE0160
SELV acc. to EN60950-1, PELV acc. to EN60204-1
Acc. to VDE0106-101
≤ 480 Watt
120
Ioutput (% IN)
Ambient temp. operating / storage temperature
Max. perm. air humidity (operation)
Degree of protection
Class of protection
Pollution degree
Insulation voltage input/output
MTBF
Parallel connection option
Housing version
Mounting position, installation notice
Derating curves
Pout [% Pn]
General data
Ioutput (% IN)
Technical Data
\
120
140
160
40
80
120 160 200 240 280 320 360 400 440
DC Input [V]
connectPower PROeco
PROeco
PRO ECO 72W 24V 3A
L (+)
N (–)
AC
PE
PRO ECO 120W 24V 5A
DC
+
L (+)
–
–
13
14
N (–)
AC
PE
+
+
–
–
13
14
DC
Pay attention to polarity of DC connection
Pay attention to polarity of DC connection
Technical Data
Input
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Ramp-up time / residual ripple, switching peaks
Rated output current @ Urated
Continuous output current @ 24 V DC
Capacitive load
Protection against reverse voltages from the load
Protection against internal surge voltage
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact /
contact load
On/Off relay
General data
Efficiency
Power loss @ idling / nominal load
Earth discharge current
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Height x width x depth / weight
Approvals
Approvals
Connection data
Conductor connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil
Min./max. tightening torque range
Stripping length
Note
Ordering Data
Note
mm²
mm²
min/max
Nm
mm
100 … 240 V AC
85 … 264 V AC (Derating @ 100 V AC)
47 … 63 Hz
80 … 370 DC (Derating @ 120 V DC)
0.55 A @ 230 V AC / 1.04 A @ 110 V AC
0.22 A @ 370 V DC / 0.68 A @ 120 V DC
Yes / max. 40
2 A / DI, Safety fuse
6 A, Char. B, Circuit breaker
2...4 A, Char. C, Circuit breaker
100 … 240 V AC
85 … 264 V AC (Derating @ 100 V AC)
47 … 63 Hz
80 … 370 DC (Derating @ 120 V DC)
1.26 A @ 230 V AC / 2.24 A @ 110 V AC
0.39 A @ 370 V DC / 1.16 A @ 120 V DC
Yes / max. 40
4 A / DI, Safety fuse
6 A, Char. B, Circuit breaker
3...5 A, Char. C, Circuit breaker
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
3 A up to 55 °C
3 A @ 55 °C, 2.25 A @ 70 °C
Unrestricted
30…35 V DC
35 V DC
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
5 A up to 55 °C
5 A @ 55 °C, 3.75 A @ 70 °C
Unrestricted
30…35 V DC
35 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit,
Uoutput < 20.4 V DC)
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit,
Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
Output voltage > 21.6 V DC / < 20.4 V DC
> 87 % @ 230 V AC & 3 A
4 W / 9.5 W
< 1 mA
> 0.42 @ 230 V AC / > 0.45 @ 115 V AC
> 100 ms @ 230 V AC / > 20 ms @ 115 V AC
yes, max. 5
125 / 34 / 100 mm / 0.5 kg
> 87 % @ 230 V AC & 5 A
4 W / 15 W
< 1 mA
> 0.47 @ 230 V AC / > 0.56 @ 115 V AC
> 80 ms @ 230 V AC / > 20 ms @ 115 V AC
yes, max. 5
125 / 40 / 100 mm / 0.6 kg
CE, TÜV (EN/IEC 60950-1), cULus
Input
Output
Screw connection
Screw connection
3 for L/N/PE
5 (13,14,+, - -)
0.5/6
0.5/6
0.5/2.5
0.5/2.5
26/12
26/12
0.5/0.6
0.5/0.6
6
6
CE, TÜV (EN/IEC 60950-1), cULus
Input
Output
Screw connection
Screw connection
3 for L/N/PE
6 (13,14,+,+, - -)
0.5/6
0.5/6
0.5/2.5
0.5/2.5
26/12
26/12
0.5/0.6
0.5/0.6
6
6
Type
PRO ECO 72W 24V 3A
Type
PRO ECO 120W 24V 5A
Qty.
1
Part No.
1469470000
The internal varistor found in a switch-mode power unit does
not replace the necessary surge protection in a system.
Qty.
1
Part No.
1469480000
The internal varistor found in a switch-mode power unit does
not replace the necessary surge protection in a system.
3
connectPower PROeco
PROeco
PRO ECO 240W 24V 10A
L (+)
N (–)
AC
PE
PRO ECO 480W 24V 20A
+
+
–
–
13
14
DC
L (+)
N (–)
AC
PE
+
+
–
–
–
13
14
DC
Pay attention to polarity of DC connection
Pay attention to polarity of DC connection
Technical Data
Input
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Ramp-up time / residual ripple, switching peaks
Rated output current @ Urated
Continuous output current @ 24 V DC
Capacitive load
Protection against reverse voltages from the load
Protection against internal surge voltage
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact / contact load
On/Off relay
General data
Efficiency
Power loss @ idling / nominal load
Earth discharge current
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Height x width x depth / weight
Approvals
Approvals
Connection data
Conductor connection system
Number of terminals
Wire cross-section, rigid min/max
mm²
Wire cross-section, flexible min/max
mm²
Wire cross-section, AWG/kcmil
min/max
Min./max. tightening torque range
Nm
Stripping length
mm
Note
Ordering Data
Note
4
100 … 240 V AC
85 … 264 V AC (Derating @ 100 V AC)
47 … 63 Hz
80 … 370 DC (Derating @ 120 V DC)
1.23 A @ 230 V AC / 2.47 A @ 110 V AC
1.18 A @ 370 V DC / 2.4 A @ 120 V DC
Yes / max. 15 A
4 A / DI, Safety fuse
10 A, Char. B, Circuit breaker
3...4 A, Char. C, Circuit breaker
100 … 240 V AC
85 … 264 V AC (Derating @ 100 V AC)
47 … 63 Hz
80 … 370 DC (Derating @ 120 V DC)
2.37 A @ 230 V AC / 5.2 A @ 110 V AC
1.55 A @ 370 V DC / 4.65 A @ 120 V DC
Yes / max. 3 A
6 A / DI, Safety fuse
16 A, Char. B, Circuit breaker
6…8 A, Char. C, Circuit breaker
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
10 A up to 55 °C
10 A @ 55 °C, 7.5 A @ 70 °C
Unrestricted
30…35 V DC
35 V DC
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
20 A up to 55 °C
20 A @ 55 °C, 15 A @ 70 °C
Unrestricted
30…35 V DC
35 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit,
Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit,
Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
> 90 % @ 230 V AC & 10 A
3 W / 24 W
< 1 mA
> 0.93 @ 230 V AC / > 0.99 @ 115 V AC
> 20 ms @ 230 V AC / > 20 ms @ 115 V AC
yes, max. 5
125 / 60 / 100 mm / 1 kg
> 91 % @ 230 V AC & 20 A
5 W / 43 W
< 1 mA
> 0.97 @ 230 V AC / > 0.99 @ 115 V AC
> 20 ms @ 230 V AC / > 20 ms @ 115 V AC
yes, max. 3
125 / 100 / 120 mm / 1.6 kg
CE, TÜV (EN/IEC 60950-1), cULus
Input
Output
Screw connection
Screw connection
3 for L/N/PE
6 (13,14,+,+, - -)
0.5/6
0.5/6
0.5/2.5
0.5/2.5
26/12
26/12
0.5/0.6
0.5/0..6
6
6
CE, TÜV (EN/IEC 60950-1), cULus
Input
Output
Screw connection
Screw connection
3 for L/N/PE
7 (13,14,+,+, - ,-,-)
0.5/6
0.18/6
0.5/2.5
0.5/2.5
26/12
26/10
0.5/0.6
0.5/0.6
6
7
Type
PRO ECO 240W 24V 10A
Type
PRO ECO 480W 24V 20A
Qty.
1
Part No.
1469490000
The internal varistor found in a switch-mode power unit does
not replace the necessary surge protection in a system.
Qty.
1
Part No.
1469510000
The internal varistor found in a switch-mode power unit does
not replace the necessary surge protection in a system.
connectPower PROeco
PROeco
PRO ECO 960W 24V 40A
L (+)
N (–)
AC
PE
+
+
–
–
–
13
14
DC
Pay attention to polarity of DC connection
Technical Data
Input
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Ramp-up time / residual ripple, switching peaks
Rated output current @ Urated
Continuous output current @ 24 V DC
Capacitive load
Protection against reverse voltages from the load
Protection against internal surge voltage
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact / contact load
On/Off relay
General data
Efficiency
Power loss @ idling / nominal load
Earth discharge current
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Height x width x depth / weight
Approvals
Approvals
Connection data
Conductor connection system
Number of terminals
Wire cross-section, rigid min/max
mm²
Wire cross-section, flexible min/max
mm²
Wire cross-section, AWG/kcmil
min/max
Min./max. tightening torque range
Nm
Stripping length
mm
Note
Ordering Data
Note
100 … 240 V AC
85 … 264 V AC (Derating @ 100 V AC)
47 … 63 Hz
80 … 370 DC (Derating @ 120 V DC)
4.6 A @ 230 V AC / 9.9 A @ 110 V AC
2.9 A @ 370 V DC / 9 A @ 120 V DC
Yes / max. 3 A
16 A / DI, Safety fuse
20 A, Char. B, Circuit breaker
16 A, Char. C, Circuit breaker
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
40 A up to 50 °C
40 A @ 50 °C, 24 A @ 70 °C
Unrestricted
30…35 V DC
35 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit,
Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
> 93 % @ 230 V AC & 40 A
6 W / 76 W
< 1 mA
> 0.97 @ 230 V AC / > 0.99 @ 115 V AC
> 20 ms @ 230 V AC / > 20 ms @ 115 V AC
yes, max. 3
125 / 160 / 120 mm / 2.9 kg
CE, TÜV (EN/IEC 60950-1), cULus
Input
Output
Screw connection
Screw connection
3 for L/N/PE
7 (13,14,+,+,+, - -)
0.18/6
0.5/16
0.5/2.5
2.5/10
26/10
22/8
0.5/0.6
1.2/1.5
7
12
Type
PRO ECO 960W 24V 40A
Qty.
1
Part No.
1469520000
The internal varistor found in a switch-mode power unit does
not replace the necessary surge protection in a system.
5
connectPower PROeco
PROeco
PRO ECO3 120W 24V 5A
L1 (+)
L2 (–)
AC
L3
PE
PRO ECO3 240W 24V 10A
+
+
–
–
13
14
DC
Pay attention to polarity of DC connection
L1 (+)
L2 (–)
AC
L3
PE
+
+
–
–
13
14
DC
Pay attention to polarity of DC connection
Technical Data
Input
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Ramp-up time / residual ripple, switching peaks
Rated output current @ Urated
Continuous output current @ 24 V DC
Capacitive load
Protection against reverse voltages from the load
Protection against internal surge voltage
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact / contact load
On/Off relay
General data
Efficiency
Power loss @ idling / nominal load
Earth discharge current
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Height x width x depth / weight
Approvals
Approvals
Connection data
Conductor connection system
Number of terminals
Wire cross-section, rigid min/max
mm²
Wire cross-section, flexible min/max
mm²
Wire cross-section, AWG/kcmil
min/max
Min./max. tightening torque range
Nm
Stripping length
mm
Note
Ordering Data
Note
6
3 x 400...3 x 500 V AC (Wide-range input)
3 x 340...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC in accordance
with UL 508)
0.3 A @ 3 x 500 V AC / 0.4 A @ 3 x 400 V AC
0.2 A @ 800 V DC / 0.4 A @ 450 V DC
Yes / max. 40 A
2 A / DI, Safety fuse
2...3 A, Char. C, Circuit breaker
3 x 400...3 x 500 V AC (Wide-range input)
3 x 340...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC in accordance
with UL 508)
0.6 A @ 3 x 500 V AC / 0.8 A @ 3 x 400 V AC
0.4 A @ 800 V DC / 0.7 A @ 450 V DC
Yes / max. 50 A
2 A / DI, Safety fuse
2...3 A, Char. C, Circuit breaker
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
5 A up to 55 °C
5 A @ 55 °C, 3.75 A @ 70 °C
Unrestricted
30…35 V DC
35 V DC
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
10 A up to 55 °C
10 A @ 55 °C, 7.5 A @ 70 °C
Unrestricted
30…35 V DC
35 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit,
Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit,
Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
87 % @ 3 x 500 V AC / 88 % @ 3 x 400 V AC
6 W / 13 W
< 1 mA
> 0.4 @ 3 x 500 V AC / > 0.45 @ 3 x 400 V AC
> 40 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes, max. 5
125 / 40 / 100 mm / 0.6 kg
88 % @ 3 x 500 V AC / 89 % @ 3 x 400 V AC
8 W / 26 W
< 0.5 mA
> 0.45 @ 3 x 500 V AC / > 0.5 @ 3 x 400 V AC
> 40 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes, max. 5
125 / 60 / 100 mm / 1 kg
CE, TÜV (EN/IEC 60950-1), cULus
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
6 (13,14,+,+, - -)
0.18/6
0.5/6
0.5/2.5
0.5/2.5
26/10
26/12
0.5/0.6
0.5/0.6
8
6
CE, TÜV (EN/IEC 60950-1), cULus
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
6 (13,14,+,+, - -)
0.18/6
0.5/6
0.5/2.5
0.5/2.5
26/10
26/12
0.5/0.6
0.5/0.6
7
6
Type
PRO ECO3 120W 24V 5A
Type
Qty.
1
PRO ECO3 240W 24V 10A
Qty.
1
Part No.
1469530000
The internal varistor found in a switch-mode power unit does
not replace the necessary surge protection in a system.
Part No.
1469540000
The internal varistor found in a switch-mode power unit does
not replace the necessary surge protection in a system.
connectPower PROeco
PROeco
PRO ECO3 480W 24V 20A
L1 (+)
L2 (–)
AC
L3
PE
PRO ECO3 960W 24V 40A
+
+
–
–
–
13
14
DC
Pay attention to polarity of DC connection
L1 (+)
L2 (–)
AC
L3
PE
+
+
–
–
–
13
14
DC
Pay attention to polarity of DC connection
Technical Data
Input
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Ramp-up time / residual ripple, switching peaks
Rated output current @ Urated
Continuous output current @ 24 V DC
Capacitive load
Protection against reverse voltages from the load
Protection against internal surge voltage
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact / contact load
On/Off relay
General data
Efficiency
Power loss @ idling / nominal load
Earth discharge current
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Height x width x depth / weight
Approvals
Approvals
Connection data
Conductor connection system
Number of terminals
Wire cross-section, rigid min/max
mm²
Wire cross-section, flexible min/max
mm²
Wire cross-section, AWG/kcmil
min/max
Min./max. tightening torque range
Nm
Stripping length
mm
Note
Ordering Data
Note
3 x 400...3 x 500 V AC (Wide-range input)
3 x 340...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC in accordance
with UL 508)
1.2 A @ 3 x 500 V AC / 1.5 A @ 3 x 400 V AC
0.7 A @ 800 V DC / 1.2 A @ 450 V DC
Yes / max. 50 A
4 A / DI, Safety fuse
3...5 A, Char. C, Circuit breaker
3 x 400...3 x 500 V AC (Wide-range input)
3 x 340...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC in accordance
with UL 508)
2.15 A @ 3 x 500 V AC / 2.68 A @ 3 x 400 V AC
1.37 A @ 800 V DC / 2.37 A @ 450 V DC
Yes / max. 40 A
6 A / DI, Safety fuse
10 A, Char. B, Circuit breaker
6...8 A, Char. C, Circuit breaker
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
20 A up to 55 °C
20 A @ 55 °C, 15 A @ 70 °C
Unrestricted
30…35 V DC
35 V DC
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
40 A up to 50 °C
40 A @ 50 °C, 24 A @ 70 °C
Unrestricted
30…35 V DC
35 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit,
Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit,
Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
89 % @ 3 x 500 V AC / 90 % @ 3 x 400 V AC
8 W / 48 W
< 0.5 mA
> 0.41 @ 3 x 500 V AC / > 0.43 @ 3 x 400 V AC
> 30 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes, max. 3
125 / 100 / 120 mm / 1.3 kg
90 % @ 3 x 500 V AC / 91 % @ 3 x 400 V AC
5 W / 95 W
< 1 mA
> 0.56 @ 3 x 500 V AC / > 0.56 @ 3 x 400 V AC
> 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes, max. 3
125 / 160 / 120 mm / 2.5 kg
CE, TÜV (EN/IEC 60950-1), cULus
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
7 (13,14,+,+, - ,-,-)
0.18/6
0.18/6
0.5/2.5
0.5/2.5
26/10
26/10
0.5/0.6
0.5/0.6
7
7
CE, TÜV (EN/IEC 60950-1), cULus
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
7 (13,14,+,+, - ,-,-)
0.18/6
0.5/16
0.5/2.5
2.5/10
26/10
22/8
0.5/0.6
1.2/1.5
7
12
Type
PRO ECO3 480W 24V 20A
Type
PRO ECO3 960W 24V 40A
Qty.
1
Part No.
1469550000
The internal varistor found in a switch-mode power unit does
not replace the necessary surge protection in a system.
Qty.
1
Part No.
1469560000
The internal varistor found in a switch-mode power unit does
not replace the necessary surge protection in a system.
7
connectPower PROeco
8
Subject to technical changes • 04/14 • 1M • LIT1402