Download

Datasheet
connectPower PRO DC/DC Converter
The new electrically isolated PRO DC/DC Converter from
Weidmuller compliments the PROmax power supply series.
Optimized for the Process, Transportation and Machinery
Industry, this converter provides a host of advantages including
avoidance of critical earth loops. From an unregulated or
distorted input voltage, it generates a stable, low-distortion
output voltage.
The DC/DC Converter is a versatile solution for all 24 V DC
power supply applications. With its HazLoc and Class III
protection, it’s also ideal for use in floating ground systems,
such as battery backup systems found in marine technology.
Integrated features such as LED indicators, status relay and
transistor outputs facilitate status and rapid error analysis,
monitors the status of the 24V output voltage, and a LED that
indicates DC OK status for the output voltage; all providing clear
visual aids making trouble shooting quick and easy and optimize
machine up-time.
• HazLoc C1D2 and ATEX
• High efficiency up to 94%
• High shock and vibration immunity
• Narrow housing
• Galvanic isolation: Protection Class III
• Super boost with more than 600% * IN for 16ms
• Integrated status relay and active switching outputs
• Comprehensive international approvals: TUV, UL, GL, DNV,
ABS, BV, RINA, LR
LISTED
Weidmuller, Canada
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (877) 300-5635
Email: [email protected]
Website: www.weidmuller.ca
Weidmuller, Mexico
Blvd. Hermanos Serdán 698,
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: [email protected]
Website: www.weidmuller.com.mx
Weidmuller, United States
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: [email protected]
Website: www.weidmuller.com
connectPower PRO DC/DC Converter
connectPower PRO
DC/DC Converter
DC voltage converter for preparation and
potential isolation in 24 V DC systems
• Overvoltage category III
• Class III protection
• Status of relay contact
• DC OK transistor output
Technical data
Nominal output current [%]
Temperature derating
120
100
80
60
40
20
0
0
-25
10
20
30
40
50
60
70
Nominal output voltage [%]
Ambient Temperature [°C]
General technical specifications
Current limiting
Housing version
Operating temperature
Humidity
Humidity at operating temperature
Max. perm. air humidity (operational)
Storage temperature
MTBF
Protection against reverse voltages from the load
Protective circuit
Start-up
Clip-in foot
Degree of efficiency
Mounting position, installation notice
100
75
50
25
0
0
20
40
60
80
100
120
140
160
Nominal output current [%]
LED (Gr/Ye/Rd)
g r = “DC OK”
Ye = “i > 90% iN” LED (Ye)
Event
Input
Output
UIN < 14 V
–
I < 90 % IN
UIN = 14…19.2 V
I > 90 % IN
*1)
U < 20.4 V
I < 90 % IN
UIN > 19.2 V
Rd = “FAul T”
“l ow u IN”
Transistor status outputs
Status
DC OK i > 90% iN l ow u IN
relay
OFF
ON
Low
Low
Low
Gr
ON
High
Low
Low
Ye
ON
High
High
Low
ON
Rd
ON
Low
Low
Low
OFF
Gr
High
OFF
ON
OFF
High
Low
I > 90 % IN
Ye
OFF
High
High
High
ON
U < 20.4 V
Rd
OFF
Low
Low
High
OFF
ON
Gr = grün / green / verte / verde / verde / verde / ৕਩
Ye = gelb / yellow / jaune / giallo / amarillo / amarelo / ௰਩
Rd = rot / red / rouge / rosso / rojo / vermelho / ঱਩
*1) während des Betriebes / during operations / en cours de fonctionnement / durante l’esercizio /
durante el servicio / durante a operação / ଍੧ଋ३И
Short-circuit protection
Protection against over-heating
Protection degree
Surge voltage category
EMC / shock / vibration
Limiting of mains voltage harmonic currents
Vibration resistance IEC 60068-2-6
Shock resistance IEC 60068-2-27
Noise emission acc. to EN55022
Interference immunity test acc. to
Insulation coordination
Class of protection
Insulation voltage input / earth
Insulation voltage output / earth
Insulation voltage, input / output
Surge voltage category
Pollution severity
Electrical safety (applied standards)
Electrical machine equipment
Protection against dangerous shock currents
Safety extra-low voltage
For use with electronic equipment
Protective separation / protection against electrical shock
Safety transformers for switch-mode power supplies
Accessories
Diode module 10A for redundancy power
Diode module 20A for redundancy power
DC UPS for 10A/20A
DC UPS for 40A
2
150% Iout
Metal, corrosion resistant
-25°C...70°C
5 … 95%, no condensation
5 … 95%, no condensation
5% … 95% RH
-40°C … 85°C
1,250,000 h
33 … 34 V DC
Overtemperature, Short-circuit, Inverse voltage
≥ -40°C
Metal
typ. 92%
Horizontal on TS35 mounting rail. 50mm of clearance
at top and bottom for air circulation. Can mount side by
side with no space in between. 50mm clearance at top
and bottom for free air circulation, mountable side by
side without clearance
Yes
Yes
IP20
III
in accordance with EN 61000-3-2
2.3 g (15 Hz …150 Hz)
30 g in all directions
Class B
EN 61000-4-2 (ESD), EN 61000-4-4 (burst),
EN 61000-4-5 (surge), EN 61000-4-6 (conducted),
EN61000-4-3 (HF field)
III, with no ground connection, for SELV
1.5 kV
0.5 kV
1.5 kV
III
2
Acc. to EN60204
Acc. to VDE0106-101
SELV acc. to EN60950, PELV acc. to EN60204
Acc. to EN50178 / VDE0160
VDE0100-410 / acc. to DIN57100-410
nach EN61558-2-16
Type
CP DM 10
CP M DM 20
CP DC UPS 24V 20A/10A
CP DC UPS 24V 40A
Qty.
1
1
1
1
Part No.
8710620000
1222210000
1370050010
1370040010
connectPower PRO DC/DC Converter
connectPower PRO
DC/DC Converter
D
PRO DCDC 120W 24V 5A
+
–
DC
H
DC
W
+
+
–
–
–
DC OK
I > 90 % IN
Low UIN
Technical data
Input data
Rated input voltage
DC input voltage range
Inrush current
Input fuse (internal)
Turn-on current limit
Recommended back-up fuse
Output data
Capacitive load
Output current
Output voltage
Parallel connection option
Protection against inverse voltage
Rated output voltage
Continuous output current @ URated
Output power
Short-circuit protection
Overload protection
Power boost @ URated
Ramp-up time
Residual ripple, breaking spikes
General data
AC failure bridging time @ INom
Power loss, nominal load
Power loss, idling
Protection against reverse voltages from the load
Width x Height x Depth
in. (mm)
Net weight
Signaling
Contact Load (NO contact)
Floating contact
Relay on/off
Transistor output, positive-switching
Connection data
Connection system
Number of terminals
Conductor cross-section, AWG/kcmil, min/max
Conductor cross-section, flexible, min/max
mm²
Conductor cross-section, rigid, min/max
mm²
Tightening torque
Wire connection cross section, flexible (input), max.
Reverse polarity protection
Approvals
Classifications
Approvals
Ordering data
24 V DC
14…32 V (during operation), 18…32 V (commissioning)
max. 10 A
Yes
Yes
10 A, Char. B circuit breaker, 10 A, Char. C circuit breaker
unrestricted
5A
22.5...29.5 V
Yes, max. 5 (without diode module)
Yes
24 V DC ± 1%
5 A @ 60°C, 6 A @ 45°C, 3.75 A @ 70°C
120W
Yes
Yes
600% IN for 16 ms
≤ 9 ms (Uout: 10%...90%)
max. 20 mVpp @ 24 V DC, IN
> 10 ms @ 24 V DC
11 W
2W
33...34 V DC
1.26” x 5.118” x 4.724” (32 x 130 x 120)
791 g
DC OK: 20 mA max., short-circuit-proof, I > 90%: 20 mA max., short-circuit-proof, Low
UIN: 20 mA max., short-circuit-proof
Input
Output
Screw connection pluggable
2 for (+, -)
8 (+ / - / signal)
30 / 12
24 / 14
0.2 / 4
0.2 / 2.5
0.2 / 4
0.2 / 2.5
0.4 … 0.5 Nm
4 mm²
Yes
eClass 6.2, 27-14-91-90
ROHS Conform
Type
PRO DCDC 120W 24V 5A
Qty.
1
Part No.
2001800000
3
connectPower PRO DC/DC Converter
connectPower PRO
DC/DC Converter
D
PRO DCDC 240W 24V 10A
+
–
+
+
–
–
–
DC OK
I > 90 % IN
Low UIN
13
14
DC
H
PRO DCDC 480W 24V 20A
DC
W
+
–
+
+
–
–
–
DC OK
I > 90 % IN
Low UIN
13
14
DC
DC
Technical data
Input data
Rated input voltage
DC input voltage range
Inrush current
Input fuse (internal)
Turn-on current limit
Recommended back-up fuse
Output data
Capacitive load
Output current
Output voltage
Parallel connection option
Protection against inverse voltage
Rated output voltage
Continuous output current @ URated
Output power
Short-circuit protection
Overload protection
Power boost @ URated
Ramp-up time
Residual ripple, breaking spikes
General data
AC failure bridging time @ INom
Power loss, nominal load
Power loss, idling
Protection against reverse voltages from the load
Width x Height x Depth
in. (mm)
Net weight
Signaling
Contact Load (NO contact)
Floating contact
Relay on/off
Transistor output, positive-switching
Connection data
Connection system
Number of terminals
Conductor cross-section, AWG/kcmil, min/max
Conductor cross-section, flexible, min/max
mm²
Conductor cross-section, rigid, min/max
mm²
Tightening torque
Wire connection cross section, flexible (input), max.
Reverse polarity protection
Approvals
Classifications
Approvals
Ordering data
4
24 V DC
14…32 V (during operation),
18…32 V (commissioning)
max. 15 A
Yes
Yes
25 A, Char. B circuit breaker,
25 A, Char. C circuit breaker
24 V DC
14…32 V (during operation),
18…32 V (commissioning)
max. 30 A
Yes
Yes
40 A, Char. B circuit breaker,
40 A, Char. C circuit breaker
unrestricted
10 A
22.5...29.5 V
Yes, max. 5 (without diode module)
Yes
24 V DC ± 1%
10 A @ 60°C, 12 A @ 45°C, 7.5 A @ 70°C
240W
Yes
Yes
600% IN for 16 ms
≤ 9 ms (Uout: 10%...90%)
max. 20 mVpp @ 24 V DC, IN
unrestricted
20 A
22.5...29.5 V
Yes, max. 3
Yes
24 V DC ± 1%
20 A @ 60°C, 24 A @ 45°C, 15 A @ 70°C
480W
Yes
Yes
600% IN for 16 ms
≤ 9 ms (Uout: 10%...90%)
max. 20 mVpp @ 24 V DC, IN
> 12 ms @ 24 V DC
22 W
2W
33...34 V DC
1.693” x 5.118” x 4.724” (43 x 130 x 120)
1,112 g
> 10 ms @ 24 V DC
40 W
3W
33...34 V DC
2.953” x 5.118” x 4.724” (75 x 130 x 120)
1,300 g
max. 30 V / 0.5 A
Yes
Output voltage > 21.6 V / < 20.4 V
DC OK: 20 mA max., short-circuit-proof, I > 90%: 20
mA max., short-circuit-proof, Low UIN: 20 mA max.,
short-circuit-proof
Input
Output
Screw connection pluggable
2 for (+, -)
10 (+ / - / signal)
30 / 12
24 / 14
0.8 / 4
0.2 / 2.5
0.8 / 4
0.2 / 2.5
0.4 … 0.5 Nm
4 mm²
Yes
max. 30 V / 0.5 A
Yes
Output voltage > 21.6 V / < 20.4 V
DC OK: 20 mA max., short-circuit-proof, I > 90%: 20
mA max., short-circuit-proof, Low UIN: 20 mA max.,
short-circuit-proof
Input
Output
Screw connection pluggable
2 for (+, -)
10 (+ / - / signal)
22 / 8
26 / 10
0.5 / 16
0.18 / 6
0.5 / 16
0.18 / 6
0.4 … 0.5 Nm
16 mm²
Yes
eClass 6.2, 27-14-91-90
ROHS Conform
eClass 6.2, 27-14-91-90
ROHS Conform
Type
PRO DCDC 240W 24V 10A
Qty.
Part No.
1 2001810000
Type
PRO DCDC 480W 24V 20A
Qty.
Part No.
1 2001820000
Subject to technical changes · 04/16 · LIT1606E