DR30 series WWW.ASTRODYNE.COM

DR30
3 0 W S i n g l e O u t put Industrial DIN Rail Power Supply
series
Universal AC input
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
Isolation class II
LED indicator for power on
Model Number Output Volts Output Amps Min Load
Efficiency Ripple and Noise DC Volt Adjust
OVP
SINGLE OUTPUT
DR30-5
DR30-12
DR30-15
DR30 -24
74%
81%
82%
83%
5.75~6.75V
13.8~16.2V
17.25~20.25V
27.6~32.4V
5 Volts(DC)
12 Volts(DC)
15 Volts(DC)
24 Volts(DC)
WWW.ASTRODYNE.COM
3 Amps
2 Amps
2 Amps
1.5 Amps
0 ~ 3Amps
0 ~ 2Amps
0 ~ 2Amps
0 ~ 1.5Amps
80mVpk-pk
120mVpk-pk
120mVpk-pk
150mVpk-pk
4.75~5.5V
10.8~13.2V
13.5~16.5V
21.6~26.4V
ASTRODYNE USA: 1-800-823-8082
ASTRODYNE PACIFIC: 886-2-26983458
DR30
3 0 W S i n g l e O u t put Industrial DIN Rail Power Supply
INPUT SPECIFICATIONS
Input Voltage Range
Frequency Range
Inrush Current, typ: (cold start)
Input Current
Leakage current
DC Voltage Adjust
GENERAL SPECIFICATIONS
90~264VAC / 120-370 Volts (DC) 47-63 Hz
15 Amps @ 115VAC
30 Amps @ 230VAC
0.88 Amps. @ 115VAC
0.48 Amps. @ 230VAC < 1mA / 240VAC
See Selection Chart
OUTPUT SPECIFICATIONS
Voltage and Current
Line Regulation
Load Regulation
Voltage Tolerance (Note 2)
Ripple/Noise (Note 1)
Hold Up Time @ FL
Setup, Rise Time @ FL
Over Current Protection
Over Voltage Protection
DC Voltage Adjust
series
See Selection Chart
±1%
±1%
±2% 5Volts(DC) only
±1% 12~24Volts(DC)
See Selection Chart
100mS @ 230VAC
21mS @115VAC
500ms, 30ms/230VAC
500mS, 30mS/115VAC
105~160% rated output power
Constant current limit,auto recover
See Selection Chart
Shut down o/p voltage, re-power
See Selection Chart
Astrodyne products are not authorized or warranteed for use
as critical components in life support systems, equipment used
in hazardous environments, nuclear controls systems, or other
mission-critical applications.
All specifications are typical at nominal input, full load, and 25°C unless otherwise noted
WWW.ASTRODYNE.COM
Safety
UL60950-1
TUV EN60950-1 approved
Design refer to EN50178 Insulation Resistance
≥ 100MΩ / 500Volts(DC)
EMI
Compliance to EN55022B (CISPR22B)
Harmonic Current
Compliance to EN61000-3-2,-3
Isolation
3000VAC Input - Output
EMS
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3,heavy industry level,criteria A
ENVIRONMENTAL SPECIFICATIONS
Oper. Temperature
Storage Temperature
Relative Humidity
Temperature Coefficient
MTBF
Vibration
-20°C to +60°C (See derate curve)
-40°C to +85°C, 10~95% RH
20 to +90% RH non cond 0.03% / °C (0-50°C) 441.5K Hrs min, MIL-HDBK-217F(25°C )
10~500Hz, 2G10min./1cycle, period for 60min. each along X, Y, Z axes Mounting: Compliance to IEC60068-2-6
PHYSICAL SPECIFICATIONS
Size
Millimeters
78 x 93 x 56 Inches
3.07” x 3.66 ” x 2.20 ”
Weight
9.52 oz (270g) NOTE
1. Ripple & Noise are measured at 20MHz of bandwidth by using a 12”
twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
2. Tolerance: includes set up tolerance , line regulation and load regulation.
ASTRODYNE USA: 1-800-823-8082
ASTRODYNE PACIFIC: 886-2-26983458