PSI-REP-PROFIBUS/12MB Repeater for PROFIBUS Systems up to 12 Mbps INTERFACE Data Sheet 102986_02_en 1 © PHOENIX CONTACT - 03/2007 Description The PSI-REP-PROFIBUS/12MB DIN rail-mountable modular PROFIBUS repeater is designed to meet the high requirements associated with the use of PROFIBUS systems. The device is snapped onto standard EN DIN rails in the control cabinet and supplied with 24 V. The main areas of application are: – Electrical isolation/bus segmentation – Increasing system availability – Increasing the range – Increasing transmission speeds – Extending the number of devices to n x 32 – Implementing hybrid/network structures – Modular PROFIBUS hubs The following features of the repeater are particularly outstanding: – Transmission speed of up to 12 Mbps – Automatic transmit/receive changeover – High-quality 4-way isolation – Integrated surge protection with transient discharge to the DIN rail – 24 V DC control cabinet supply voltage, with user-friendly connection via COMBICON plug-in screw terminals – Bit retiming – Bit oversampling – Modular station structure, even with PSI-MOS-... fiber optic converters If you have any technical problems, which you cannot resolve with the aid of this documentation, please contact us during the usual office hours at: PSI hotline: +49 - 52 35 - 31 98 90 Fax: +49 - 52 35 - 33 09 99 E-mail: [email protected] Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf. PSI-REP-PROFIBUS/12MB 1.1 Bit Retiming PROFIBUS signals with a bit distortion of up to 35% can be reliably detected using the bit retiming function and are converted to their original bit form before being transferred to the next segment. This data processing function means that a virtually unlimited number of repeaters can be aligned without an impermissible level of bit distortion. 2 1.2 Bit Oversampling The bit oversampling function can be used to detect and filter malfunctions so that they are not transferred to the next segment. Ordering Data Repeater Description Modular PROFIBUS repeater, for electrical isolation and increasing the range in PROFIBUS systems, 4-way isolation, DIN-rail mountable Accessories Description Type Order No. Pcs./Pck. PSI-REP-PROFIBUS/12MB 2708863 1 Type Order No. Pcs./Pck. System power supply unit for supplying a modular star coupler configuration MINI-SYS-PS 100-240AC/24DC/1.5 2866983 1 End bracket 3022218 50 CLIPFIX 35 DIN rail connector, power supply and data (2 per device) ME 17,5 TBUS 1,5/ 5-ST-3,81 GN 2709561 10 PROFIBUS cable, Fast Connect type, up to 12 Mbps PSM-CABLE-PROFIB/FC 2744652 1 Small, angled PROFIBUS connector with screw connection SUBCON-PLUS-PROFIB/SC2 2708232 1 Small, angled PROFIBUS connector with screw connection and additional PG connection SUBCON-PLUS-PROFIB/PG/SC2 2708245 1 3 Technical Data Interface Power supply 24 V DC (±20% via COMBICON plug-in screw terminal) Frequency DC Nominal current consumption 90 mA (at 24 V DC) Ready-to-operate indicator "VCC" LED (green) Maximum star coupler expansion 10 Serial RS-485 Interface PROFIBUS according to IEC 61158, 2-wire Transmission channels 2 (1/1), TD, RD Operating mode Half duplex Data format/encoding UART (11, NRZ) Data direction changeover Automatic, minimum station response time 2 bits Transmission speed (manual adjustment) 9.6/19.2/45.45/93.75/187.5/500/1500/3000/6000/12000 kbps; autobaud Transmission length 1200 m, maximum (depending on transmission speed, bus system, and cable type) Transmission medium 2-wire twisted pair, shielded Connection 9-pos. D-SUB female connector General Data Bit distortion input ±35%, maximum Bit distortion output < 6.25% Bit delay ≤ 11 bits Electrical isolation PROFIBUS (A) // PROFIBUS (B) // power supply // DIN rail connector Test voltage 1.5 kVrms, 50 Hz, 1 min. 102986_02_en PHOENIX CONTACT 2 PSI-REP-PROFIBUS/12MB General Data (Continued) Alarm output 60 V DC/42 V AC, 1 A, maximum Status and diagnostic indicators Power supply (VCC), transmit/receive data (port A) Housing material PA V0, green Conductor cross section 0.2 mm2 ... 2.5 mm2 Ambient temperature Operation -20°C ... +60°C Storage/transport -40°C ... +85°C Humidity 10% ... 95%, no condensation Dimensions (W x H x D) 35 mm x 99 mm x 105 mm Degree of protection IP20 Weight 200 g, approximately MTBF according to Telcordia standard Ambient temperature 25°C 878,000 h Ambient temperature 40°C 489,000 h Chloroform test Free from substances which would hinder coating with paint or varnish (according to VW/Audi/Seat specification) Vibration resistance 5g according to IEC 60068-2-6, 2.5 h each in x, y, and z direction, criterion A Shock resistance 15g according to IEC 60068-2-27 with 11 ms pulse length, criterion C Free fall 1 m without packaging according to IEC 60068-2-32 Air and creepage distances DIN EN 50178, DIN EN 60950 Tests/Approvals CE c UL In preparation Ex X II 3G Ex nAC IIC T4 X Conformance With EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC Noise Immunity Test According to EN 61000-6-21 Electrostatic discharge (ESD) EN 61000-4-2 Criterion B2 Electromagnetic HF field EN 61000-4-3 Criterion A3 8 kV air discharge 6 kV contact discharge 10 V/m Amplitude modulation 10 V/m Pulse modulation Fast transients (burst) EN 61000-4-4 Criterion B2 Signal 2 kV/5 kHz Power supply 2 kV/5 kHz Surge current load (surge) EN 61000-4-5 Criterion B2 1 kV/12 Ω Signal 0.5 kV/2 Ω Power supply Conducted interference EN 61000-4-6 Criterion A3 Amplitude modulation 10 V 80% AM 1 kHz Noise Emission Test According to EN 61000-6-4 Noise emission of housing EN 550114 Class A5 1 EN 61000 corresponds to IEC 61000 2 Criterion B: Temporary adverse effects on the operating behavior, which the device corrects automatically. 3 Criterion A: Normal operating behavior within the specified limits. 4 EN 55011 corresponds to CISPR11 5 Class A: 102986_02_en Industrial application, without special installation measures. PHOENIX CONTACT 3 PSI-REP-PROFIBUS/12MB Block Diagram DC 24V (1) DC 0V (2) DC DC Port A VP 6 GND 5 DATA (P) 3 DATA (N) 8 gn DATA RATE DIN rail connector DIN rail bus Bus management Retiming gn Retiming Port B 6 VP 5 GND 3 DATA (P) 8 DATA (N) Retiming ye 24V 0V GND D(P) D(N) DIN railrail connector DIN bus Figure 1 Block diagram Housing Dimensions 35 105 99 PSI-REP-PROFIB/12MB Ord.-No. 27 08 863 VCC TD RD ERR A Port A PORT B ERR B 102986A001 Figure 2 102986_02_en Housing dimensions (in mm) PHOENIX CONTACT 4 PSI-REP-PROFIBUS/12MB 4 Safety Instructions Installation, operation, and maintenance may only be carried out by qualified electricians. When installing and operating the device, the applicable safety directives (including national safety directives), accident prevention regulations, as well as general technical regulations, must be observed. Notes on Explosion Protection The device is a category 3 item of electrical equipment. Follow the instructions provided here during installation. The device must be installed in housing with IP54 protection according to EN 60529. The specified limits for mechanical strain or thermal loads for the device must not be exceeded. Temporary malfunctions (transients) must not exceed the rated voltage by more than 40%. Repairs must not be carried out by the user. Cables may only be snapped on and connected in potentially explosive areas when the power is disconnected. 5 Function Elements 1 5 6 7 9 2 3 1 2 3 4 5 6 7 8 9 10 11 4 PSI-REP-PROFIB/12MB Ord.-No. 27 08 863 VCC TD RD 8 24 V DC supply voltage connection 0 V DC supply voltage connection Switch contact connection 1 Switch contact connection 2 "VCC" LED: Ready-to-operate "TD" LED: Transmit data dynamic port A (yellow) "RD" LED: Receive data dynamic port A (green) 9-pos. D-SUB: PROFIBUS interface port A "ERR A" LED: Transmission error port A "ERR B" LED: Transmission error port B 9-pos. D-SUB: PROFIBUS interface port B ERR A Port A Port B 10 ERR B 11 102964A002 Figure 3 102986_02_en Function elements PHOENIX CONTACT 5 PSI-REP-PROFIBUS/12MB 6 Applications Stub line The PSI-REP-PROFIBUS/12MB repeater can be used to create network topologies that are ideally adapted to the relevant application. The limits set by the PROFIBUS standard, which specifies the electrical properties of PROFIBUS, are thus extended. This standard defines the following basic specifications: 1. Maximum of 32 devices per potential segment 2. Only (linear) bus structure permitted 3. Maximum bus cable length 1200 m 4. Maximum branch line length of 5 m without termination resistor (depending on the transmission speed) 5. Bus cable termination at the start and end of the bus cable PROFIBUS 12 MBit/s 100m 100m Max. 31 devices = Switch on bus termination resistor Linear structure Example Applications for Repeaters A segment can be created as an active branch, which can comprise the full bus cable length and a maximum of 31 devices. Electrical isolation and bus segmentation using repeaters enables the permissible bus cable length to be multiplied and the number of devices to be extended to n x 32, since the total number of devices of the PROFIBUS specification applies in each potential segment. The repeater supports higher transmission speeds by subdividing into shorter segment lengths. For example, a 200 m PROFIBUS system can only be operated at a transmission speed of 1.5 Mbps. The use of a repeater after 100 m means that 8 times the performance can be achieved, i.e., 12 Mbps. Hybrid/network structures, star, and tree structures can be created using the PSI-REP-PROFIBUS/12MB modular repeater. A freely selectable installation concept, independent of the restrictive linear structure, is thus possible. The repeaters can be extended using PSI-MOS-PROFIB/FO... fiber optic converters for PROFIBUS systems. In addition, the repeaters can be combined and thus configured to form a modular PROFIBUS hub. Max. 30 devices Max. 30 devices = Switch on bus termination resistor Star structure = Switch on bus termination resistor Tree structure = Switch on bus termination resistor 102986_02_en PHOENIX CONTACT 6 PSI-REP-PROFIBUS/12MB 7 DIP Switches The DIP switches (1) are located under the cap (2) on the port B interface (see Figure 4). • Insert a small screwdriver into the slot on the bottom of the cap and lever it off. TD B R ER 1 Setting the Transmission Speed 2 3 4 5 rt A Po 6 A R ER ON Set the transmission speed using DIP switches 1 to 4. ON 1 2 3 S1...S6 4 B T O P 4 OFF ON OFF ON OFF ON OFF ON OFF ON OFF R DIP Switch 2 3 OFF OFF OFF OFF OFF ON OFF ON ON OFF ON OFF ON ON ON ON OFF OFF OFF OFF OFF ON 6 AUTO (default) 12000 6000 3000 1500 500 187.5 93.75 45.45 19.2 9.6 1 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON 5 Transmission Speed (kbps) 102986B003 Figure 4 DIP switches (default upon delivery: all DIP switches set to OFF) DIP switches 5 and 6 are reserved and have no function. 102986_02_en PHOENIX CONTACT 7 PSI-REP-PROFIBUS/12MB 8 Connection Notes Only mount and remove devices when the power supply is disconnected. 8.1 Combined Assembly With a System Power Supply (Modular Star Coupler) 1. Connect together the required number of DIN rail connectors for the connection station. Two DIN rail connectors are required for each device (see A in Figure 5). A maximum of ten devices are permitted in a connection station. Push the connected DIN rail connectors onto the DIN rail (B and C). Place the device onto the DIN rail from above. The upper holding keyway of the device must be hooked onto the top edge of the DIN rail (see Figure 6 on page 9). Make sure that it is aligned correctly with the DIN rail connectors. Once the device has been snapped on properly, check that it is fixed securely on the DIN rail. Warning Disregarding this warning may result in damage to equipment and/or serious personal injury. Only qualified personnel may start up and operate this device. According to the safety instructions in this text, qualified personnel are persons who are authorized to start up, to ground, and to mark devices, systems, and equipment according to the standards of safety technology. In addition, these persons must be familiar with all warning instructions and maintenance measures in this text. PSI-REP-PROFIBUS/12MB devices are designed exclusively for SELV operation according to IEC 60950/EN 60950/ VDE 0805. • Install the device on a 35 mm DIN rail according to DIN EN 60715. To avoid contact resistance only use clean, corrosion-free DIN rails. End brackets should be mounted on both sides of the device to stop the devices from slipping on the DIN rail (for ordering data see page 2). 2. 3. 4. A B C 101973A003 Figure 5 102986_02_en Combined assembly PHOENIX CONTACT 8 PSI-REP-PROFIBUS/12MB 8.2 1. 2. 3. Assembly as an Individual Device in the Control Cabinet (Stand-Alone) Place the device onto the DIN rail from above. The upper holding keyway of the device must be hooked onto the top edge of the DIN rail (see Figure 6). Push the device from the front towards the mounting surface. Once the device has been snapped on properly, check that it is fixed securely on the DIN rail. 9 Cabling Notes 9.1 Connecting the Supply Voltage The device is operated with a +24 V DC SELV. Operation as an Individual Device Supply the supply voltage to the module via terminal blocks 1 (24 V) and 2 (0 V). Redundant supply Individual supply 24 V 0V 24 V 0 V 24 V 0V 102964A006 Figure 7 Individual/redundant supply Operation in a Star Coupler Configuration 102964B005 Figure 6 8.3 1. 2. 3. 4. Assembly in the control cabinet Removal Pull the locking latch down using a screwdriver, needle-nose pliers or similar. Pull the bottom edge of the module away from the mounting surface. Pull the module diagonally upwards away from the DIN rail. If removing a complete star distributor, remove the DIN rail connectors from the DIN rail as well. 102986_02_en When the devices are operated in a star coupler configuration, the supply voltage must only be supplied to the first device in the station. The remaining devices are supplied via the DIN rail connector. A redundant supply concept can be created by connecting a second power supply unit to another device in the configuration. Using the MINI-SYS-PS-... System Power Supply Unit As an alternative, the star coupler configuration can also be supplied using the MINI-SYS-PS 100-240AC/24DC/1.5 power supply unit (Order No. 2866983). It is connected via two DIN rail connectors. Usually the system power supply unit is mounted as the first device in a configuration. A second power supply unit can be used to create a redundant supply concept. PHOENIX CONTACT 9 PSI-REP-PROFIBUS/12MB 9.2 Wiring the Switch Contact 24 V DC PSI-REP-PROFIBUS/12MB repeaters are equipped with a floating switch contact for error diagnostics (connection terminal blocks 3 and 4 in Figure 3 on page 5). This contact opens on the relevant device in the event of a transmission error at port A or port B. The switch contact is an N/C contact and can be linked to a local digital input, e.g., on the PLC, to support error detection. If devices are combined (in a modular star coupler configuration), the individual contacts can be linked to separate input points (Figure 8) or the individual contacts can be looped to generate a group message (Figure 9). The maximum load capacity of the relay contact is 60 V DC/42 V AC, 1 A. 101973A006 Figure 8 Individual message 24 V DC Group message 101973A007 Figure 9 102986_02_en Group message PHOENIX CONTACT 10 PSI-REP-PROFIBUS/12MB 9.3 Connecting the Data Cables Attention Use shielded twisted pair data cables. Connect the cable shielding at both ends of the transmission path. 1. Use a suitable connector (e.g., SUBCON-PLUSPROFIB..., see page 2) to connect the bus cable to the D-SUB connection on the repeater. If the repeater is located at the start or end of an electrical PROFIBUS segment, activate termination in the connector. VC B C RD TD R Port A A ER tA r Po R B Port B ER DGND 6 VP 8 RxD/TxD-N R 5 Meaning Receive/transmit data, positive B cable Data transmission potential/ (reference potential to VP) Supply voltage, positive (P5V) (50 mA, maximum) Receive/transmit data, negative A cable O Signal RxD/TxD-P P Pin 3 T B 2. 2M IB/1 OF 63 -PR 8 8 EP 7 0 I-R . 2 PS .-No rd O 102986A004 Figure 10 D-SUB connections for port A and port B © PHOENIX CONTACT 03/2007 102986_02_en PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany Phone: +49 - 52 35 - 30 0 • Fax: +49 - 52 35 - 34 12 00 www.phoenixcontact.com 11