Data Sheet DB EN PSI-REP-PROFIBUS/12MB

PSI-REP-PROFIBUS/12MB
Repeater for PROFIBUS Systems up to 12 Mbps
INTERFACE
Data Sheet
102986_02_en
1
© PHOENIX CONTACT - 03/2007
Description
The PSI-REP-PROFIBUS/12MB DIN rail-mountable
modular PROFIBUS repeater is designed to meet the high
requirements associated with the use of PROFIBUS
systems. The device is snapped onto standard EN DIN rails
in the control cabinet and supplied with 24 V. The main
areas of application are:
– Electrical isolation/bus segmentation
– Increasing system availability
– Increasing the range
– Increasing transmission speeds
– Extending the number of devices to n x 32
– Implementing hybrid/network structures
– Modular PROFIBUS hubs
The following features of the repeater are particularly
outstanding:
– Transmission speed of up to 12 Mbps
– Automatic transmit/receive changeover
– High-quality 4-way isolation
– Integrated surge protection with transient discharge to
the DIN rail
– 24 V DC control cabinet supply voltage, with
user-friendly connection via COMBICON plug-in screw
terminals
– Bit retiming
– Bit oversampling
– Modular station structure, even with PSI-MOS-... fiber
optic converters
If you have any technical problems, which you cannot resolve with the aid of this documentation, please contact
us during the usual office hours at:
PSI hotline: +49 - 52 35 - 31 98 90
Fax: +49 - 52 35 - 33 09 99
E-mail: [email protected]
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
PSI-REP-PROFIBUS/12MB
1.1
Bit Retiming
PROFIBUS signals with a bit distortion of up to 35% can be
reliably detected using the bit retiming function and are
converted to their original bit form before being transferred
to the next segment. This data processing function means
that a virtually unlimited number of repeaters can be
aligned without an impermissible level of bit distortion.
2
1.2
Bit Oversampling
The bit oversampling function can be used to detect and
filter malfunctions so that they are not transferred to the
next segment.
Ordering Data
Repeater
Description
Modular PROFIBUS repeater, for electrical isolation and increasing the range
in PROFIBUS systems, 4-way isolation, DIN-rail mountable
Accessories
Description
Type
Order No.
Pcs./Pck.
PSI-REP-PROFIBUS/12MB
2708863
1
Type
Order No.
Pcs./Pck.
System power supply unit for supplying a modular star coupler configuration MINI-SYS-PS 100-240AC/24DC/1.5
2866983
1
End bracket
3022218
50
CLIPFIX 35
DIN rail connector, power supply and data (2 per device)
ME 17,5 TBUS 1,5/ 5-ST-3,81 GN
2709561
10
PROFIBUS cable, Fast Connect type, up to 12 Mbps
PSM-CABLE-PROFIB/FC
2744652
1
Small, angled PROFIBUS connector with screw connection
SUBCON-PLUS-PROFIB/SC2
2708232
1
Small, angled PROFIBUS connector with screw connection and additional
PG connection
SUBCON-PLUS-PROFIB/PG/SC2
2708245
1
3
Technical Data
Interface
Power supply
24 V DC (±20% via COMBICON plug-in screw terminal)
Frequency
DC
Nominal current consumption
90 mA (at 24 V DC)
Ready-to-operate indicator
"VCC" LED (green)
Maximum star coupler expansion
10
Serial RS-485 Interface
PROFIBUS according to IEC 61158, 2-wire
Transmission channels
2 (1/1), TD, RD
Operating mode
Half duplex
Data format/encoding
UART (11, NRZ)
Data direction changeover
Automatic, minimum station response time 2 bits
Transmission speed (manual adjustment)
9.6/19.2/45.45/93.75/187.5/500/1500/3000/6000/12000 kbps; autobaud
Transmission length
1200 m, maximum (depending on transmission speed, bus system, and cable
type)
Transmission medium
2-wire twisted pair, shielded
Connection
9-pos. D-SUB female connector
General Data
Bit distortion input
±35%, maximum
Bit distortion output
< 6.25%
Bit delay
≤ 11 bits
Electrical isolation
PROFIBUS (A) // PROFIBUS (B) // power supply // DIN rail connector
Test voltage
1.5 kVrms, 50 Hz, 1 min.
102986_02_en
PHOENIX CONTACT
2
PSI-REP-PROFIBUS/12MB
General Data (Continued)
Alarm output
60 V DC/42 V AC, 1 A, maximum
Status and diagnostic indicators
Power supply (VCC), transmit/receive data (port A)
Housing material
PA V0, green
Conductor cross section
0.2 mm2 ... 2.5 mm2
Ambient temperature
Operation
-20°C ... +60°C
Storage/transport
-40°C ... +85°C
Humidity
10% ... 95%, no condensation
Dimensions (W x H x D)
35 mm x 99 mm x 105 mm
Degree of protection
IP20
Weight
200 g, approximately
MTBF according to Telcordia standard
Ambient temperature 25°C
878,000 h
Ambient temperature 40°C
489,000 h
Chloroform test
Free from substances which would hinder coating with paint or varnish
(according to VW/Audi/Seat specification)
Vibration resistance
5g according to IEC 60068-2-6, 2.5 h each in x, y, and z direction, criterion A
Shock resistance
15g according to IEC 60068-2-27 with 11 ms pulse length, criterion C
Free fall
1 m without packaging according to IEC 60068-2-32
Air and creepage distances
DIN EN 50178, DIN EN 60950
Tests/Approvals
CE
c
UL
In preparation
Ex
X II 3G Ex nAC IIC T4 X
Conformance With EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC
Noise Immunity Test According to EN 61000-6-21
Electrostatic discharge (ESD)
EN 61000-4-2
Criterion B2
Electromagnetic HF field
EN 61000-4-3
Criterion A3
8 kV air discharge
6 kV contact discharge
10 V/m
Amplitude modulation
10 V/m
Pulse modulation
Fast transients (burst)
EN 61000-4-4
Criterion B2
Signal
2 kV/5 kHz
Power supply
2 kV/5 kHz
Surge current load (surge)
EN 61000-4-5
Criterion B2
1 kV/12 Ω
Signal
0.5 kV/2 Ω
Power supply
Conducted interference
EN 61000-4-6
Criterion A3
Amplitude modulation
10 V 80% AM 1 kHz
Noise Emission Test According to EN 61000-6-4
Noise emission of housing
EN 550114
Class A5
1
EN 61000 corresponds to IEC 61000
2
Criterion B:
Temporary adverse effects on the operating behavior, which the device corrects automatically.
3
Criterion A:
Normal operating behavior within the specified limits.
4
EN 55011 corresponds to CISPR11
5
Class A:
102986_02_en
Industrial application, without special installation measures.
PHOENIX CONTACT
3
PSI-REP-PROFIBUS/12MB
Block Diagram
DC
24V (1)
DC
0V (2)
DC
DC
Port A
VP
6
GND
5
DATA (P)
3
DATA (N)
8
gn
DATA
RATE
DIN rail connector
DIN rail bus
Bus
management
Retiming
gn
Retiming
Port B
6
VP
5
GND
3
DATA (P)
8
DATA (N)
Retiming
ye
24V 0V GND D(P) D(N)
DIN
railrail
connector
DIN
bus
Figure 1
Block diagram
Housing Dimensions
35
105
99
PSI-REP-PROFIB/12MB
Ord.-No. 27 08 863
VCC
TD
RD
ERR A
Port A
PORT B
ERR B
102986A001
Figure 2
102986_02_en
Housing dimensions (in mm)
PHOENIX CONTACT
4
PSI-REP-PROFIBUS/12MB
4
Safety Instructions
Installation, operation, and maintenance may only be carried out by qualified electricians. When
installing and operating the device, the applicable safety directives (including national safety
directives), accident prevention regulations, as well as general technical regulations, must be
observed.
Notes on Explosion Protection
The device is a category 3 item of electrical equipment. Follow the instructions provided here during
installation.
The device must be installed in housing with IP54 protection according to EN 60529. The specified
limits for mechanical strain or thermal loads for the device must not be exceeded.
Temporary malfunctions (transients) must not exceed the rated voltage by more than 40%.
Repairs must not be carried out by the user.
Cables may only be snapped on and connected in potentially explosive areas when the power is
disconnected.
5
Function Elements
1
5
6
7
9
2
3
1
2
3
4
5
6
7
8
9
10
11
4
PSI-REP-PROFIB/12MB
Ord.-No. 27 08 863
VCC
TD
RD
8
24 V DC supply voltage connection
0 V DC supply voltage connection
Switch contact connection 1
Switch contact connection 2
"VCC" LED: Ready-to-operate
"TD" LED: Transmit data dynamic port A (yellow)
"RD" LED: Receive data dynamic port A (green)
9-pos. D-SUB: PROFIBUS interface port A
"ERR A" LED: Transmission error port A
"ERR B" LED: Transmission error port B
9-pos. D-SUB: PROFIBUS interface port B
ERR A
Port A
Port B
10
ERR B
11
102964A002
Figure 3
102986_02_en
Function elements
PHOENIX CONTACT
5
PSI-REP-PROFIBUS/12MB
6
Applications
Stub line
The PSI-REP-PROFIBUS/12MB repeater can be used to
create network topologies that are ideally adapted to the
relevant application.
The limits set by the PROFIBUS standard, which specifies
the electrical properties of PROFIBUS, are thus extended.
This standard defines the following basic specifications:
1. Maximum of 32 devices per potential segment
2. Only (linear) bus structure permitted
3. Maximum bus cable length 1200 m
4. Maximum branch line length of 5 m without termination
resistor (depending on the transmission speed)
5. Bus cable termination at the start and end of the bus
cable
PROFIBUS 12 MBit/s
100m
100m
Max. 31 devices
= Switch on bus termination resistor
Linear structure
Example Applications for Repeaters
A segment can be created as an active branch, which can
comprise the full bus cable length and a maximum of 31
devices.
Electrical isolation and bus segmentation using repeaters
enables the permissible bus cable length to be multiplied
and the number of devices to be extended to n x 32, since
the total number of devices of the PROFIBUS specification
applies in each potential segment.
The repeater supports higher transmission speeds by
subdividing into shorter segment lengths. For example, a
200 m PROFIBUS system can only be operated at a
transmission speed of 1.5 Mbps. The use of a repeater after
100 m means that 8 times the performance can be
achieved, i.e., 12 Mbps.
Hybrid/network structures, star, and tree structures can be
created using the PSI-REP-PROFIBUS/12MB modular
repeater. A freely selectable installation concept,
independent of the restrictive linear structure, is thus
possible. The repeaters can be extended using
PSI-MOS-PROFIB/FO... fiber optic converters for
PROFIBUS systems.
In addition, the repeaters can be combined and thus
configured to form a modular PROFIBUS hub.
Max. 30 devices
Max. 30 devices
= Switch on bus termination resistor
Star structure
= Switch on bus termination resistor
Tree structure
= Switch on bus termination resistor
102986_02_en
PHOENIX CONTACT
6
PSI-REP-PROFIBUS/12MB
7
DIP Switches
The DIP switches (1) are located under the cap (2) on the
port B interface (see Figure 4).
•
Insert a small screwdriver into the slot on the bottom of
the cap and lever it off.
TD
B
R
ER
1
Setting the Transmission Speed
2
3
4
5
rt A
Po
6
A
R
ER
ON
Set the transmission speed using DIP switches 1 to 4.
ON
1
2
3
S1...S6
4
B
T
O
P
4
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
R
DIP Switch
2
3
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
6
AUTO (default)
12000
6000
3000
1500
500
187.5
93.75
45.45
19.2
9.6
1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
5
Transmission
Speed (kbps)
102986B003
Figure 4
DIP switches (default upon delivery: all DIP
switches set to OFF)
DIP switches 5 and 6 are reserved and have no
function.
102986_02_en
PHOENIX CONTACT
7
PSI-REP-PROFIBUS/12MB
8
Connection Notes
Only mount and remove devices when the
power supply is disconnected.
8.1
Combined Assembly With a System Power
Supply (Modular Star Coupler)
1.
Connect together the required number of DIN rail
connectors for the connection station. Two DIN rail
connectors are required for each device (see A in
Figure 5). A maximum of ten devices are permitted in a
connection station.
Push the connected DIN rail connectors onto the DIN
rail (B and C).
Place the device onto the DIN rail from above. The
upper holding keyway of the device must be hooked
onto the top edge of the DIN rail (see Figure 6 on
page 9). Make sure that it is aligned correctly with the
DIN rail connectors.
Once the device has been snapped on properly, check
that it is fixed securely on the DIN rail.
Warning
Disregarding this warning may result in
damage to equipment and/or serious personal
injury. Only qualified personnel may start up
and operate this device. According to the
safety instructions in this text, qualified
personnel are persons who are authorized to
start up, to ground, and to mark devices,
systems, and equipment according to the
standards of safety technology. In addition,
these persons must be familiar with all warning
instructions and maintenance measures in this
text.
PSI-REP-PROFIBUS/12MB devices are
designed exclusively for SELV operation
according to IEC 60950/EN 60950/
VDE 0805.
•
Install the device on a 35 mm DIN rail according to
DIN EN 60715. To avoid contact resistance only use
clean, corrosion-free DIN rails. End brackets should be
mounted on both sides of the device to stop the
devices from slipping on the DIN rail (for ordering data
see page 2).
2.
3.
4.
A
B
C
101973A003
Figure 5
102986_02_en
Combined assembly
PHOENIX CONTACT
8
PSI-REP-PROFIBUS/12MB
8.2
1.
2.
3.
Assembly as an Individual Device in the Control
Cabinet (Stand-Alone)
Place the device onto the DIN rail from above. The
upper holding keyway of the device must be hooked
onto the top edge of the DIN rail (see Figure 6).
Push the device from the front towards the mounting
surface.
Once the device has been snapped on properly, check
that it is fixed securely on the DIN rail.
9
Cabling Notes
9.1
Connecting the Supply Voltage
The device is operated with a +24 V DC SELV.
Operation as an Individual Device
Supply the supply voltage to the module via terminal
blocks 1 (24 V) and 2 (0 V).
Redundant
supply
Individual
supply
24 V
0V
24 V
0 V 24 V
0V
102964A006
Figure 7
Individual/redundant supply
Operation in a Star Coupler Configuration
102964B005
Figure 6
8.3
1.
2.
3.
4.
Assembly in the control cabinet
Removal
Pull the locking latch down using a screwdriver,
needle-nose pliers or similar.
Pull the bottom edge of the module away from the
mounting surface.
Pull the module diagonally upwards away from the DIN
rail.
If removing a complete star distributor, remove the DIN
rail connectors from the DIN rail as well.
102986_02_en
When the devices are operated in a star coupler
configuration, the supply voltage must only be supplied to
the first device in the station. The remaining devices are
supplied via the DIN rail connector. A redundant supply
concept can be created by connecting a second power
supply unit to another device in the configuration.
Using the MINI-SYS-PS-... System Power Supply Unit
As an alternative, the star coupler configuration can also be
supplied using the MINI-SYS-PS 100-240AC/24DC/1.5
power supply unit (Order No. 2866983). It is connected via
two DIN rail connectors.
Usually the system power supply unit is mounted as the first
device in a configuration. A second power supply unit can
be used to create a redundant supply concept.
PHOENIX CONTACT
9
PSI-REP-PROFIBUS/12MB
9.2
Wiring the Switch Contact
24 V DC
PSI-REP-PROFIBUS/12MB repeaters are equipped with a
floating switch contact for error diagnostics (connection
terminal blocks 3 and 4 in Figure 3 on page 5). This contact
opens on the relevant device in the event of a transmission
error at port A or port B.
The switch contact is an N/C contact and can be linked to a
local digital input, e.g., on the PLC, to support error
detection.
If devices are combined (in a modular star coupler
configuration), the individual contacts can be linked to
separate input points (Figure 8) or the individual contacts
can be looped to generate a group message (Figure 9).
The maximum load capacity of the relay
contact is 60 V DC/42 V AC, 1 A.
101973A006
Figure 8
Individual message
24 V DC
Group message
101973A007
Figure 9
102986_02_en
Group message
PHOENIX CONTACT
10
PSI-REP-PROFIBUS/12MB
9.3
Connecting the Data Cables
Attention
Use shielded twisted pair data cables.
Connect the cable shielding at both ends of
the transmission path.
1.
Use a suitable connector (e.g., SUBCON-PLUSPROFIB..., see page 2) to connect the bus cable to the
D-SUB connection on the repeater.
If the repeater is located at the start or end of an
electrical PROFIBUS segment, activate termination in
the connector.
VC
B
C
RD
TD
R
Port A
A
ER
tA
r
Po
R
B
Port B
ER
DGND
6
VP
8
RxD/TxD-N
R
5
Meaning
Receive/transmit data, positive
B cable
Data transmission potential/
(reference potential to VP)
Supply voltage, positive (P5V)
(50 mA, maximum)
Receive/transmit data, negative
A cable
O
Signal
RxD/TxD-P
P
Pin
3
T
B
2.
2M
IB/1
OF 63
-PR 8 8
EP 7 0
I-R . 2
PS .-No
rd
O
102986A004
Figure 10
D-SUB connections for port A and port B
© PHOENIX CONTACT 03/2007
102986_02_en
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49 - 52 35 - 30 0 • Fax: +49 - 52 35 - 34 12 00
www.phoenixcontact.com
11