Highly compact signal conditioners MINI Analog Pro

Highly compact
signal conditioners
with plug-in connection technology
MINI Analog Pro
Bro IE Mini Analog Pro Rev01.indd 1
26.02.14 15:30
Easier than ever but slim as before
MINI Analog Pro
The highly compact MINI Analog Pro signal
conditioners offer the easiest installation
and startup in a confined space.
Selectable connection
technology
Wiring with screw connection or fast
and tool-free push-in technology.
Easy maintenance
Large-surface marking areas for
complete loop identification
using standard marking material.
Easy installation
Easily visible
and accessible
terminal points
and FASTCON Pro
plug-in connection
terminal blocks.
Consistent
diagnostics
Consistently visible
status LEDs in each
signal conditioner.
Rapid power
bridging and
error messages
Easily connect
devices via the
modular DIN rail
connector.
2
Measure current
signals easily
Measure current signals
during operation
without disconnecting
the current loop.
PHOENIX CONTACT
Bro IE Mini Analog Pro Rev01.indd 2
26.02.14 15:32
Bro
MINI Analog Pro product overview
Analog IN/
Analog OUT
2-wire
3-wire
Signal conditioners
• Universal signal conditioners
• Standard signal conditioners
• Repeater power supplies
Page 8
4-wire
Easy startup and service
Interrupt signal and supply circuits with just
a twist thanks to the integrated disconnect
function.
Temperature
Temperature transducers
• Universal temperature
transducers for resistance
thermometers and
thermocouples
Page 9
Potentiometers
Potentiometer measuring
transducers
• Potentiometer measuring
transducers with automatic
potentiometer detection
Numerous parameterization options
Easy configuration via DIP switches as well
as extended configuration via software
or smartphone app without additional
accessories.
Page 9
Accessories
+ 70 °C
• Supply components
• Fault monitoring module
• Marking material
- 40 °C
Page 9
Optimum signal quality
The latest switching technology with
multi-functional device types, safe electrical
isolation, and extended supply voltage and
operating temperature range.
Universal use
thanks to the international approval package
PHOENIX CONTACT
15:32
Bro IE Mini Analog Pro Rev01.indd 3
3
26.02.14 15:32
The easiest installation and
startup in a confined space
Installation and startup of MINI Analog Pro
is incredibly easy:
Now it's within your reach
Thanks to the design, all connections
and operating elements are clearly
visible and easily accessible. This not
only saves space above and below the
device, it saves time during installation.
Insert the wires in any order, even in a
confined space.
Everything at a glance
Large-surface marking areas for standard
marking material permit complete loop
identification despite the compact design.
Status and error indicators are always visible
and provide you with an instant on-site
overview.
Unique in the 6 mm class
MINI Analog Pro is the first 6 mm range with
plug-in connection technology. The FASTCON
Pro connection terminal blocks can even be
independently inserted and removed from the device
system. Interrupt signal and supply circuits easily
during service and startup with the disconnect
function.
Measure current signals
without disconnection
Measure current signals without
disconnecting the signal circuit.
With just a single measurement,
you can record the entire current
loop from the sensor to the
controller.
4
PHOENIX CONTACT
Bro IE Mini Analog Pro Rev01.indd 4
26.02.14 15:32
Bro
Numerous parameterization options
Many of the MINI Analog Pro signal conditioner device types can
be configured for optimal adaptation to your application.
Choose from a wide range of configuration types:
Easy DIP switch configuration
You can easily set the standard functions via the DIP switches
on the device - without using any software. Here, the calibrated
measuring range switchover guarantees a consistent level of
accuracy without additional adjustment.
DIP switches on the housing side
PC configuration for extended function and monitoring
For extended functionality and monitoring, you can also configure the
multi-function modules conveniently via PC using one of the free software
solutions available for download:
• ANALOG-CONF standalone software
• FDT/DTM software package
• Standalone DTMs, allowing you to use your existing FDT frame
application
Smart configuration without additional accessories
ANALOG-CONF standalone software
Place your smartphone on the device and establish a wireless
connection via Near Field Communication (NFC). Depending
on the device type, the free MINI Analog Pro app offers a wide
range of functions:
NFC
Module information
• Call up module information
NFC
DIP switch setting aid
• Call up module information
• DIP switch setting aid
NFC
Configuration
• Call up module information
• DIP switch setting aid
• Module configuration
Install the MINI Analog
Pro app now, in no
time at all!
Order configuration
Order your devices easily and flexibly with the required
configuration ex works:
• Using order keys from the catalog or
• In the user-guided e-shop: phoenixcontact.com
PHOENIX CONTACT
15:32
Bro IE Mini Analog Pro Rev01.indd 5
5
26.02.14 15:33
Optimum signal quality
State-of-the-art
switching technology
High-quality contacts
The connection terminal
blocks make contact by
means of robust direct
insertion. There are no metal
pins that can be damaged.
Maximum electrical
isolation
Flexible supply
The latest transmission
technology and safe electrical
isolation between the
input, output, and supply
with a 3 kV test voltage:
MINI Analog Pro offers you
unrivalled isolation quality in
the 6 mm class.
The extended supply
voltage range from
9.6 to 30 V DC ensures
high availability and enables
flexible use, for example in
12 V applications.
Hot, cold? No problem!
Quality from a single source – Made in Germany
The wide operating temperature range
from - 40 °C to + 70 °C enables use even
under extreme ambient conditions.
It is only when you keep sight of every
little detail that you can be sure of the
quality. This is why we develop and
produce everything ourselves for
MINI Analog Pro.
We produce high-quality “Made in
Germany” signal conditioners at our
own plastic, metal, and SMD production
facilities. Another advantage for you: short
delivery times, even for high quantities.
+ 70 °C
- 40 °C
MINI Analog Pro signal conditioners are safe
and reliable even at - 40 °C
6
Modern production processes ensure high quality and short delivery times
PHOENIX CONTACT
Bro IE Mini Analog Pro Rev01.indd 6
26.02.14 15:33
Bro
Flexible and simple power supply
MINI Analog Pro signal conditioners offer a flexible
system solution for supplying devices. The supply
voltage is bridged by the modular DIN rail connector.
This simplifies wiring, system expansion or module
replacement, even during operation.
Power IN 2
Power IN 1
Power
module
The DIN rail connector gives you three device supply
options:
Power IN
1. Direct DC supply at any MINI Analog Pro module:
• For up to 16 MINI Analog Pro modules
• No additional accessories required other than
the DIN rail connector
2. Via a power module of the same shape
• For up to 115 MINI Analog Pro modules
• Also allows redundant supply and supply
monitoring
Power IN 2
3. Via the system power supply with
85 to 264 V AC wide-range input:
• When a DC supply is not available
• For up to 60 MINI Analog Pro modules
Power supply
Power IN
Power IN 3
Convenient error evaluation with fault monitoring
Fault monitoring is a modular solution for convenient
error evaluation in multi-channel applications.
Depending on the module type, the following errors
can be indicated by means of a group error message:
•
•
•
•
•
Measuring range overshot
Measuring range undershot
Open circuit
Short circuit
Module error
It is also possible to detect and indicate the failure
of a supply voltage at the power terminal block. The
modularity is characterized by the ability to freely
adjust the error evaluation, both on the device side
and in the evaluation module.
Error
message
contact
Fault
monitoring
module
Power IN
Power
module
Power IN
Group
error message
for up to
115 devices
Supply voltage monitoring
PHOENIX CONTACT
15:33
Bro IE Mini Analog Pro Rev01.indd 7
7
26.02.14 15:35
MINI Analog Pro product overview
Analog IN / Analog OUT
Analog IN / Analog OUT
Analog IN / Analog OUT
U,I
IN
U,I
NFC
OUT
IN
U,I
U,I
NFC
OUT
IN
U,I
FM
POWER
FM
POWER
Universal 4-way signal conditioner
with relay contact,
configurable
U,I
OUT
NFC
FM
POWER
3-way signal conditioner,
configurable
3-way signal conditioner,
with fixed signal combinations
IN
0 … 24 mA (freely adjustable,
min. 1 mA interval)
0 … 12 V (freely adjustable,
min. 0.5 V interval)
Can be set via DIP switch, software or app
0 … 20 mA, 4...20 mA, -20...20 mA,
0 … 5 V, 1 … 5 V, -5 … 5 V,
0 … 10 V, 2 … 10 V, -10 … 10 V,
0 … 20 V, 4 … 20 V, -20 … 20 V,
0 … 24 V, 4.8 … 24 V, -24 … 24 V,
0 … 30 V, 6 … 30 V, -30 … 30 V
Can be set via DIP switch
1) 0 … 20 mA, 4 … 20 mA; IN = OUT
2) 0 … 10 V, -10 … 10 V; IN = OUT
OUT
0 … 21 mA (freely adjustable,
min. 1 mA interval)
0 … 10.5 V (freely adjustable,
min. 0.5 V interval)
With fault signaling
Supports fault monitoring
Can be set via DIP switch, software or app
0 … 20 mA, 4 … 20 mA,
0 … 5 V, 1 … 5 V, -5 … 5 V,
0 … 10 V, 2 … 10 V, -10 … 10V
Supports fault monitoring
Can be set via DIP switch
1) 0 … 20 mA, 4 … 20 mA; IN = OUT
2) 0 … 10 V, -10 … 10 V; IN = OUT
Supports fault monitoring
Screw
connection
MINI MCR-2-UNI-UI-UIRO *)
2902026
MINI MCR-2-UI-UI *)
2902037
1) MINI MCR-2-I-I
2901998
2) MINI MCR-2-U-U
2902042
Push-in
connection
MINI MCR-2-UI-UI-PT *)
2902040
MINI MCR-2-UNI-UI-UIRO-PT *)
2902028
1) MINI MCR-2-I-I-PT
2901999
2) MINI MCR-2-U-U-PT
2902043
Analog IN / Analog OUT
U
IN
I
NFC
OUT
Analog IN / Analog OUT
IN
U
I
Analog IN / Analog OUT
NFC
OUT
POWER
I
I
OUT
NFC
IN
FM
POWER
FM
POWER
FM
POWER
3-way signal conditioner,
with fixed signal combinations
3-way signal conditioner,
with fixed signal combinations
Repeater power supply,
HART-transparent
IN
1) 0 … 10 V
2) 0 … 10 V
1) 0 … 20 mA
2) 4 … 20 mA
Isolator operation: 0 … 20 mA, 4 … 20 mA;
IN = OUT
Repeater power supply 4 … 20 mA;
IN = OUT
OUT
1) 0 … 20 mA
2) 4 … 20 mA
Supports fault monitoring
1) 0 … 10 V
2) 0 … 10 V
Supports fault monitoring
0 … 20 mA, 4 … 20 mA; IN = OUT
Supports fault monitoring
Screw
connection
Push-in
connection
1) MINI MCR-2-I0-U
2902000
2) MINI MCR-2-U-I4
2902029
2) MINI MCR-2-I4-U
2902002
1) MINI MCR-2-U-I0-PT
2902023
1) MINI MCR-2-I0-U-PT
2902001
2) MINI MCR-2-U-I4-PT
2902030
2) MINI MCR-2-I4-U-PT
2902003
*)
8
PHOENIX CONTACT
Bro IE Mini Analog Pro Rev01.indd 8
MINI MCR-2-RPSS-I-I
2902014
1) MINI MCR-2-U-I0
2902022
Versions can also be ordered
pre-configured ex-works
T-Connector
Compatible
MINI MCR-2-RPSS-I-I-PT
2902015
The module can be snapped onto the DIN rail
connector.
26.02.14 15:36
Bro
MINI Analog Pro product overview
Temperature
U,I
IN
Temperature
NFC
OUT
IN
U,I
FM
POWER
OUT
Potentiometer
NFC
U,I
OUT
NFC
FM
POWER
FM
POWER
Universal measuring transducer for
resistance thermometers, configurable
Universal measuring transducer for
thermocouples, configurable
Potentiometer measuring transducer,
configurable
IN
2, 3 or 4-wire
IEC 751: Pt100, Pt200, Pt500, Pt1000
GOST 6651-2009: Pt100, Pt1000, Cu50,
Cu100, Cu53
JIS C1604-1997: Pt100, Pt1000
DIN 43760: Ni100, Ni1000
-200°C … 850°C (sensor-dependent)
Linear resistance: 0 … 4 kΩ
Can be set via DIP switch, software or app
IEC 584-1: B, E, J, K, N, R, S, T
DIN 43710: L, U
GOST 8.585: A-1, A-2, A-3, M, L
-250°C … 2500°C (sensor-dependent)
Can be set via DIP switch, software or app
3-wire potentiometer
100 ohms … 100 kΩ
Automatic detection
Can be set via DIP switch, software or app
OUT
0 … 21 mA (freely adjustable,
min. 1 mA interval)
0 … 10.5 V (freely adjustable,
min. 0.5 V interval)
With fault signaling
Supports fault monitoring
Can be set via DIP switch, software or app
0 … 21 mA (freely adjustable,
min. 1 mA interval)
0 … 10.5 V (freely adjustable,
min. 0.5 V interval)
With fault signaling
Supports fault monitoring
Can be set via DIP switch, software or app
0 … 21 mA (freely adjustable,
min. 1 mA interval)
0 … 10.5 V (freely adjustable,
min. 0.5 V interval)
With fault signaling
Supports fault monitoring
Can be set via DIP switch, software or app
Screw
connection
MINI MCR-2-RTD-UI *)
2902049
MINI MCR-2-TC-UI *)
2902055
MINI MCR-2-POT-UI *)
2902016
Push-in
connection
MINI MCR-2-RTD-UI-PT *)
2902052
MINI MCR-2-TC-UI-PT *)
2905249
MINI MCR-2-POT-UI-PT *)
2902017
Accessories
Accessories
Accessories
IN
POWER POWER
IN
NFC
IN PTB
POWER
MONITORING POWER
OUT
NFC
OUT FM
Description
For redundant supply on the DIN rail
connector
Inputs: 9.9 … 30 V DC
Output: max. 3.2 A; 9.6 … 29.7 V DC
Monitoring of the supply possible in
combination with fault monitoring
Fault monitoring module for evaluating
and reporting group errors from the fault
monitoring system
Monitoring of supply voltages of
MINI MCR-2-PTB(-PT) power terminal
blocks
Feed-through terminal block for 1:1
forwarding of signals that are already
electrically isolated in the MINI Analog Pro
group
MINI MCR-2-TB
2902068
MINI MCR-2-FM-RC
2904504
Push-in
connection
MINI MCR-2-PTB-PT
2902067
MINI MCR-2-FM-RC-PT
2904508
Bro IE Mini Analog Pro Rev01.indd 9
NFC
Feed-through terminal block
1:1 connection
MINI MCR-2-PTB
2902066
DIP switch setting aid
NFC • Call up module information
• DIP switch setting aid
OUT
Fault monitoring module
Screw
connection
Module information
NFC • Call up module information
1:1
IN
OUT
Power terminal block
IN
FM
POWER
POWER
15:36
R
IN
NFC
Configuration
• Call up module information
• DIP switch setting aid
• Module configuration
PHOENIX CONTACT
9
26.02.14 15:36
Accessories for MINI Analog Pro
DIN rail connector
ME 6,2 TBUS-2 1,5/5-ST-3,81 GY
Order No. 2695439
• Gray, for two MINI Analog Pro modules
each
ME 17,5 TBUS 1,5/5-ST-3,81 GN
Order No. 2709561
• Green, for MINI-SYS system power supply
(2 required)
System power supply
MINI-SYS-PS-100-240AC/24DC/1.5
Order No. 2866983
MINI-PS-100-240AC/24DC/1.5/EX
Order No. 2866653 (Ex n-capable)
• Wide range input:
85 … 264 V AC (45 – 65 Hz)
• Output voltage:
24 V DC ±1%
• Output current:
1.5 A at 60°C/2 A at 40°C
Programming adapter
IFS-USB-PROG-ADAPTER
Order No. 2811271
• Programming adapter with USB interface,
for programming via PC.
NFC-USB-PROG-ADAPTER
Order No. 2900013
• Programming adapter with NFC interface,
for wireless programming via PC.
Flexible printing
Easily generate your own
marking: we have the right
printing system for your
requirements.
Marking labels
UCT-EM (30x5)
Order No. 0801505
UCT-EM (30x5) CUS Order No. 0801589
UCT-EM (30x5) YE
Order No. 0830340
UC-EMLP (15x5)
Order No. 0819301
UC-EMLP (15x5) CUS Order No. 0824550
• For snapping or sticking onto module cover
• Can be marked with THERMOMARK CARD
or BLUEMARK printer
• Lettering field size: 30 x 5 mm/15 x 5 mm
10
PHOENIX CONTACT
Bro IE Mini Analog Pro Rev01.indd 10
Adhesive labels
SK 5,0 WH:REEL
Order No. 0805221
• Self-adhesive marker strips, unprinted,
continuous
• Roll material for marking
with THERMOMARK ROLL
thermal transfer printer
You can find other marking materials,
printers, and printing accessories on
our website:
phoenixcontact.com
26.02.14 15:36
Bro
Isolating, converting, filtering, and amplifying – the functions at a glance
Electrical isolation
The most important task of a signal
conditioner is the electrical isolation of
signals. MINI Analog Pro offers consistent
isolation of input, output, and supply.
As such, ground current loops can be
prevented in the event of potential
differences, which would otherwise lead
to a distortion of the measured process
values.
I1 = 20 mA
I2 = 18 mA
Ig = 2 mA
Ground current loop
Sensor
2,000 mA
Potential 2
Potential 1
I1 = 20 mA
I2 = 20 mA
Ig = 0 mA
No ground current
loop
Sensor
0.000 mA
Potential 1
Potential 2
Converting signals
An advantage of signal conversion is
the conversion of sensor signals into a
signal that can be read by the controller.
In addition, signals susceptible to
interference can be converted into less
sensitive signals.
4 – 20 mA
0 – 10 V
Sensor
Amplifying signals
Signals always need to be amplified when
cables are long or if high loads need to
be driven. It is here where the signal
conditioners of the MINI Analog Pro
range provide a high output power at a
low input power.
Can only drive loads
of up to 300 Ω
Can amplify loads
up to 600 Ω
4 – 20 mA
4 – 20 mA
+ 24 V DC
Sensor
Filtering signals
U
In industrial environments, interference
often occurs as a result of high-frequency
signals. The input filters of the MINI
Analog Pro signal conditioners therefore
reliably filter out such interference signals.
U
t
0 – 10 V
t
0 – 10 V
Sensor
PHOENIX CONTACT
15:36
Bro IE Mini Analog Pro Rev01.indd 11
11
26.02.14 15:36
Always up-to-date, always available to you. Here
you'll find everything on our products, solutions
and service:
phoenixcontact.net
Product range
• Industrial communication technology
• Industrial Ethernet
• Installation and mounting material
• Lighting and signaling
• Marking and labeling
• Measurement and control technology
• Modular terminal blocks
• Monitoring
• PCB terminal blocks and
PCB connectors
• Power supply units and UPS
• Protective devices
• Relay modules
• Sensor/actuator cabling
• Software
• Surge protection and interference filters
• System cabling for controllers
• Tools
• Wireless data communication
PHOENIX CONTACT GmbH & Co. KG
32825 Blomberg, Germany
Phone: +49 (0) 52 35 3-00
Fax:
+49 (0) 52 35 3-4 12 00
phoenixcontact.net
Bro IE Mini Analog Pro Rev01.indd 12
IF 04-13.000.L3.2013
MNR 52005212/2014-02-01/01
Printed in Germany
© PHOENIX CONTACT 2014
• Cables and wires
• Connectors
• Controllers
• Electronics housing
• Electronic switchgear and
motor control
• Fieldbus components and systems
• Functional safety
• HMIs and industrial PCs
• I/O systems
26.02.14 15:36