functional safety characteristics

FUNCTIONAL SAFETY
CHARACTERISTICS
Safety characteristics of
Phoenix Contact safety products
Application note
105016_en_03
1
© PHOENIX CONTACT 2014-01-22
Aim of this document
2
Table of contents
This application note is a central data source for all safety
characteristics of Phoenix Contact safety products.
1
Aim of this document ..........................................................1
2
Table of contents ................................................................1
It provides characteristics for:
– Machine building according to EN ISO 13849 and
EN 62061
– Process automation according to IEC 61508
3
Safety switching devices.....................................................2
3.1
Safety relays........................................................2
3.2
Modular safety relays ..........................................4
3.3
Downtime and speed monitors ............................5
3.4
Forcibly guided coupling relays ...........................6
4
PSR-TRISAFE configurable safety module.........................7
5
SafetyBridge technology network solutions ........................9
Phoenix Contact supports you here with the SISTEMA tool
by providing you with a SISTEMA library containing all
components that have already been certified according to
the latest standards.
You can find the current SISTEMA library on our website
under the keyword SISTEMA.
This document also contains the characteristics required to
calculate safety loops in the process industry.
6
Safe control technology ....................................................10
7
CONTACTRON solid-state contactors .............................11
8
Safe coupling relays..........................................................12
9
Signal conditioners ...........................................................13
9.1
Analog IN/analog OUT ......................................13
9.2
Temperature......................................................14
9.3
Digital IN ............................................................15
10
Ex-i signal conditioners .....................................................16
10.1
Analog IN/analog OUT ......................................16
10.2
Temperature......................................................17
10.3
Digital IN/digital OUT .........................................18
11
Explanation of terms .........................................................19
12
Revision history ................................................................20
Make sure you always use the latest documentation.
It can be downloaded at phoenixcontact.net/products.
Should you have any further questions, please contact the Safety service team.
+ 49 5281 9-462777
[email protected]
Delayed contacts up to PL d, category 3
Note
In conjunction with a suitable evaluating device
2)
tM
(years)
Order No.
1)
PFHd
(1/h)
Safety relays
EN 62061
SILCL
3.1
EN ISO 13849-1
PL
Safety switching devices
Short designation
3
Category
FUNCTIONAL SAFETY CHARACTERISTICS
2963802
PSR-ESA2-B
2963954
c
1
SILCL 1
4.05E-10
8766 switching cycles per year
B10d = 230,000 at 3 A AC 15
Up to PL e/SILCL 3 possible
depending on the application
2963750
PSR-ESA4
2963938
2963763
PSR-ESA4-B
2963941
e
4
SILCL 3
5.05E-10
8766 switching cycles per year
B10d = 300,000 at 5 A DC 13
2.42E-10
8760 switching cycles per year
B10d = 300,000 at 5 A DC 13
Up to PL e/SILCL 3 possible
depending on the application
2901430
PSR-ESAM2/3x
2901431
2900525
2900526
2981114
2981127
2900509
2900510
2963912
2963996
2901416
2901417
2901426
2901427
2901422
2901425
2901428
2901429
c
1
SILCL 1
PSR-ESAM4/2x1
5.05E-10
PSR-ESAM4/3x1
1.26E-10
PSR-ESAM4/3x1B
5.05E-10
PSR-ESAM4/8x1
5.06E-10
8766 switching cycles per year
B10d = 230,000 at 3 A AC 15
3.60E-10
8760 switching cycles per year
B10d = 300,000 at 5 A DC 13
1.80E-09
8766 switching cycles per year
B10d = 400,000 at 3 A
AC 15 DC 13
e
PSR-ESAM4 AC
2981800
PSR-ESD-30
2981813
105016_en_03
4
20
8766 switching cycles per year
B10d = 300,000 at 5 A DC 13
SILCL 3
PHOENIX CONTACT
2
2981428
2981431
2981125
2981198
2981059
2981062
2963718
2963705
2963776
2963925
2981020
2981017
2981978
2981981
2986960
2986957
2981486
2981499
2963721
2963983
2963734
2964005
2981677
2981680
2981033
2981046
2903583
2903584
PSR-ESD-300 2)
PSR-ESD-T
Note
tM
(years)
PFHd
(1/h)
EN 62061
SILCL
Category
EN ISO 13849-1
PL
Order No.
Short designation
FUNCTIONAL SAFETY CHARACTERISTICS
1.89E-09
8766 switching cycles per year
B10d = 230,000 at 3 A AC 15
2)
1.67E-09
PSR-ESL4-B
5.56E-10
8766 switching cycles per year
B10d = 300,000 at 5 A DC 13
PSR-ESM4
5.05E-10
PSR-ESM4_B
PSR-ESP4
1.16E-10
PSR-FSP 1x1 1)
2.02E-11
PSR-FSP 2x1 1)
2.02E-11
PSR-SDC4
2.53E-10
PSR-THC4
1.21E-09
PSR-URM4/5x1 1)
e
4
SILCL 3
1.47E-09
PSR-URM4-B 4x1 1)
9.70E-11
PSR-URM4-B 5x1 1)
1.02E-10
PSR-URML4
5.56E-10
2902935
PSR-URM4 42-230UC 1)
2902936
4.69E-11
2902725
2902726
2903253
2903254
2903255
2903256 PSR-MXF
2903257
2903258
2903259
2903260
2903261
1.93E-10
105016_en_03
20
8766 switching cycles per year
B10d = 160,000 at 5 A AC 15
8766 switching cycles per year
B10d = 1,000,000 at 5 A DC 13
8766 switching cycles per year
B10d = 1,000,000 at 5 A DC 13
8766 switching cycles per year
B10d = 300,000 at 5 A DC 13
8766 switching cycles per year
B10d = 300,000 at 5 A DC 13
8766 switching cycles per year
B10d = 230,000 at 3 A AC 15
8766 switching cycles per year
B10d = 300,000 at 5 A DC 13
8766 switching cycles per year
B10d = 230,000 at 3 A AC 15
8766 switching cycles per year
B10d = 300,000 at 5 A DC 13
8766 switching cycles per year
B10d = 200,000 at 2.5 A DC 13
or 3 A AC 15
8766 switching cycles per year
B10d = 780,000 at 5 A DC 13 or
3 A AC 15
PHOENIX CONTACT
3
FUNCTIONAL SAFETY CHARACTERISTICS
PSR-SDC4
Note
3
tM
(years)
d
PFHd
(1/h)
4
EN 62061
SILCL
e
8766 switching cycles per year
B10d = 300,000 at 5 A DC 13
2.53E-10
PSR-URD3/T2 1)
1.35E-09
PSR-URD3-3 1)
SILCL 3
20
8766 switching cycles per year
B10d = 300,000 at 5 A DC 13
PSR-URD3-30 1)
1.39E-09
PSR-URM4/B 1)
e
4
PSR-SIM4
-
-
-
-
-
-
-
-
-
-
2981871 PSR-SACB-4/4-L2981884 5,0PUR-SD
1)
Category
2981486
2981499
2981703
2981729
2981732
2981745
2981512
2981525
2981677
2981680
2981936
2981949
EN ISO 13849-1
PL
Short designation
Modular safety relays
Order No.
3.2
9.70E-11
Due to the series connection of
safety door switches, the
possible diagnostic coverage is
reduced as are the maximum
achievable safety
classifications.
In conjunction with a suitable evaluating device
105016_en_03
PHOENIX CONTACT
4
FUNCTIONAL SAFETY CHARACTERISTICS
105016_en_03
Category
EN 62061
SILCL
PFHd
(1/h)
tM
(years)
e
4
SILCL 3
7.90E-09
20
Note
EN ISO 13849-1
PL
2981538
PSR-RSM4
2981541
Short designation
Downtime and speed monitors
Order No.
3.3
PHOENIX CONTACT
5
FUNCTIONAL SAFETY CHARACTERISTICS
2963747
2963970
2981402
2981415
2981839
2981842
2981952
2981965
2981363
2981376
2981444
2981457
2981460
2981473
Note
B10d
Short designation
Forcibly guided coupling relays
Order No.
3.4
PSR-URM/5x1/2x2
230,000
3 A AC 15 / 230 V
2.5 A DC 13
PSR-URM/3x1
300,000
5 A DC 13
PSR-URM/5x1/1x2
230,000
PSR-URM/2x21
180,000
PSR-URM/4x1
300,000
105016_en_03
3 A AC 15 / 230 V
2.5 A DC 13
3 A AC 15 / 250 V
3 A DC 13
5 A DC 13
PHOENIX CONTACT
6
FUNCTIONAL SAFETY CHARACTERISTICS
TBUS-Safe
105016_en_03
2
4
4
SILCL 2
SILCL 3
SILCL 3
1.20E-10
1.20E-10
1.09E-08
e
4
SILCL 3
7.00E-10
e
4
SILCL 3
7.00E-10
d
e
e
2
4
4
SILCL 2
SILCL 3
SILCL 3
1.20E-10
1.20E-10
1.09E-08
e
4
SILCL 3
7.00E-10
e
4
SILCL 3
7.00E-10
e
4
SILCL 3
1.00E-09
Note
d
e
e
tM
(years)
PFHd
(1/h)
-
EN 62061
SILCL
2986012
2986025
Category
2986229
2986232
PSR-TRISAFE-S - 1CH IN
PSR-TRISAFE-S - 2CH IN
Logic
PSR-TRISAFE-S - 1CH
OUT
PSR-TRISAFE-S - 2CH
OUT
PSR-TRISAFE-M - 1CH IN
PSR-TRISAFE-M - 2CH IN
Logic
PSR-TRISAFE-M - 1CH
OUT
PSR-TRISAFE-M - 2CH
OUT
EN ISO 13849-1
PL
Short designation
PSR-TRISAFE configurable safety module
Order No.
4
Cat. 4 can only be achieved if
cross circuit is prevented
20
Cat. 4 can only be achieved if
cross circuit is prevented
TBUS must be taken into
account once per system
PHOENIX CONTACT
7
2
SILCL 2
1.10E-10
e
4
SILCL 3
1.10E-10
e
4
SILCL 3
1.30E-09
e
4
SILCL 3
3.00E-10
e
4
SILCL 3
3.00E-10
e
4
SILCL 3
6.10E-10
Switchable I/O contacts can
only achieve Cat. 2 if clock
signals are used
Cat. 4 can only be achieved if
cross circuit is prevented
20
PSR-TS-SDOR4/4x1 1CH-AC15
PSR-TS-SDOR4/4x1 2986096 1CH-DC13
2986106
PSR-TS-SDOR4/4x1 2CH-AC15
PSR-TS-SDOR4/4x1 2CH-DC13
105016_en_03
c
1
SILCL 2
1.30E-09
c
1
SILCL 2
1.30E-09
e
4
SILCL 3
3.00E-11
e
4
SILCL 3
3.00E-11
Note
PFHd
(1/h)
d
tM
(years)
EN 62061
SILCL
PSR-TS-SDI8-SDIO4 2986038 2CH IN
2986041 Logic
PSR-TS-SDI8-SDIO4 1CH OUT
PSR-TS-SDI8-SDIO4 2CH OUT
Logic
Category
PSR-TS-SDI8-SDIO4 1CH IN
EN ISO 13849-1
PL
Order No.
Short designation
FUNCTIONAL SAFETY CHARACTERISTICS
8766 switching cycles per year
B10d =1,960,000 at 3 A AC 15;
1 N/O
8766 switching cycles per year
B10d = 780,000 at 3 A DC 13;
1 N/O
8766 switching cycles per year
B10d =1,960,000 at 3 A AC 15;
1 N/O
8766 switching cycles per year
B10d = 780,000 at 3 A DC 13;
1 N/O
PHOENIX CONTACT
8
FUNCTIONAL SAFETY CHARACTERISTICS
5
SafetyBridge technology network solutions
Category
EN 62061
SILCL
PFHd
(1/h)
tM
(years)
2916024
d
e
d
e
d
e
d
e
d
e
c
c
e
e
e
e
e
d
e
d
e
3
4
3
4
3
4
3
4
3
4
2
2
4
4
4
4
4
3
4
3
4
SILCL 2
SILCL 3
SILCL 2
SILCL 3
SILCL 2
SILCL 3
SILCL 2
SILCL 3
SILCL 2
SILCL 3
SILCL 2
SILCL 2
SILCL 3
SILCL 3
SILCL 3
SILCL 3
SILCL 3
SILCL 2
SILCL 3
SILCL 2
SILCL 3
1E-08
1E-09
1E-08
1E-09
1E-08
1E-09
1E-08
1E-09
1E-08
1E-09
1E-08
1E-08
1E-09
1E-09
1E-09
1E-09
1E-09
1E-08
1E-09
1E-08
1E-09
2700606
2701625
2916493
2985631
20
2985864
2985688
2700994
105016_en_03
Note
EN ISO 13849-1
PL
IL-LPSDO-8-1CH
IL-LPSDO-8-2CH
IL-LPSDO-8-V2-1CH
IL-PSDO-8-V2-2CH
IL-LPSDO-8-V3-1CH
IL-LPSDO-8-V3-2CH
IL-PSDO-4/4-1CH
IL-PSDO-4/4-2CH
IL-PSDO-8-1CH
IL-PSDO-8-2CH
IL-PSDOR-4-1CH-AC15
IL-PSDOR-4-1CH-DC13
IL-PSDOR-4-2CH-AC15-A
IL-PSDOR-4-2CH-AC15-B
IL-PSDOR-4-2CH-CAP-B
IL-PSDOR-4-2CH-DC13-A
IL-PSDOR-4-2CH-DC13-B
IL-PSDI-8-1CH
IL-PSDI-8-2CH
IL-PSDI-16 1CH
IL-PSDI-16 2CH
Order No.
Short designation
.
The PFHd value is an example
value here. It depends on the
parameterization and wiring.
You can determine the exact
value with the aid of the
product documentation.
PHOENIX CONTACT
9
FUNCTIONAL SAFETY CHARACTERISTICS
105016_en_03
SILCL 3
e
4
SILCL 3
1E-09
20
Note
4
tM
(years)
EN 62061
SILCL
e
PFHd
(1/h)
Category
2985563 SLC400-PND
2916794 RFC 470S PN 3TX
2700651 FL PN/PN SDIO-2TX/2TX
EN ISO 13849-1
PL
Short designation
Safe control technology
Order No.
6
PHOENIX CONTACT
10
FUNCTIONAL SAFETY CHARACTERISTICS
2297031
2297044
2297057
2297060
2900582
2900414
2900421
2900692
2900420
2900422
2900558
2900559
2900561
2900688
2900560
2900562
2900566
2900567
2900569
2900689
2900568
2900570
2900550
2900552
2900554
2900686
2900553
2900555
ELR-W3-24DC/500AC-2l
ELR-W3-230AC/500AC-2l
ELR-W3-24DC/500AC-9l
ELR-W3-230AC/500AC-9l
2.48E-09
4.43E-09
2.48E-09
4.43E-09
ELR-H5_IES-SC-24DC/500AC...
3.31E-09
ELR-H5_IES-SC-230AC/500AC...
6.77E-09
ELR-H5_ES-SC-24DC/500AC...
3.31E-09
e
3
Note
20
ELR-H5_ES-SC-230AC/500AC...
6.77E-09
ELR-H3_IES-SC-24DC/500AC...
2.72E-09
ELR-H3_IES-SC-230AC/500AC...
6.22E-09
ELR-H3_ES-SC-24DC/500AC...
2.72E-09
ELR-H3_ES-SC-230AC/500AC...
6.72E-09
105016_en_03
tM
(years)
PFHd
(1/h)
Category
EN ISO 13849-1
PL
Short designation
CONTACTRON solid-state contactors
Order No.
7
PHOENIX CONTACT
11
FUNCTIONAL SAFETY CHARACTERISTICS
8
Safe coupling relays
2986575
2986588
3)
PSR-FSP2/2x
264.38
319
-
2.02E-11
20
2.09
911.79
113
9.15E-6
-
10
20
99.99
949
58.3
44.5
0.093
1052
106.9
-
9.93E-11
Low
99.56
0
849
0
3.68
853
132.3
1.61E-5
-
9
High
99.99
198
63.9
3.66
0.02
264.38
342
-
2.02E-11
20
Low
99.76
0
1026.9
0
2.42
1029.32
104
1.06E-5
-
5
High
99.61
99
55.7
99
1
254.7
361
-
1E-09
20
0
PSR-ESAM4/3x1/1x2/B
2986711
2986562
PSR-ETP/1x13)
3
2
A
High
1
0
81.97
0
455
0
100
555
185
4.38E-4
-
2.25
99.99
660
1298
26.7
0.359
1985
50.9
-
35.9E-11
20
99.66
0
1723
0
5.876
1729
57.46
2.57E-5
-
6.5
99.64
0
815.86
1.4
2.94
820.19
126.54 1.29E-5
-
11
3
1)
Includes faults that are not part of the safety function. MTTR was set to 8 hours.
2)
For T1 = 1 year
3)
Only in conjunction with a suitable evaluating device
105016_en_03
20
3
Low
Low
tM (years)
PFHd
0.02
0
Low
2901416
2901417
2901426
2901427
2901422
2901425
2901428
2901429
T1max (years)
PFDavg 2)
3.66
909.7
1
PSR-FSP/2x1 3)
MTBF (years) 1)
62.7
0
λDU (FIT)
198
99.77
SIL
99.99
Low
HFT
High
High
2986960
2986957
λTotal (FIT)
Device type
λDD (FIT)
PSR-ESP4
λSU (FIT)
2981020
2981017
λSD (FIT)
PSR-FSP 3)
SFF (%)
2981978
2981981
Demand
Order No.
Short designation
Substitute values for 1001 structure
PHOENIX CONTACT
12
FUNCTIONAL SAFETY CHARACTERISTICS
9
Signal conditioners
Substitute values for 1001 structure
9.1
Analog IN/analog OUT
SFF (%)
λSD (FIT)
λSU (FIT)
λDD (FIT)
λDU (FIT)
MTBF (years)
2
83.50
0
317.3
0
62.9
259
2.76E-04 6.29E-08 0.00
Low/High
A
3)
2
83.00
0
318.2
0
62.1
259
2.83E-04 6.46E-08 0.00
Low/High
A
2)
2
86.10
0
369.8
0
59.5
228
2.61E-04 5.95E-08 0.00
Low/High
A
3)
2
82.80
0
353.7
0
69.7
228
3.19E-04 7.27E-08 0.00
Low/High
A
4)
2
90.60
0
464.9
0
48.4
219
2.12E-04 4.84E-08 0.00
MACX MCR-SL-RPSSI-I-UP(-SP) Low/High
A
4)
2
90.60
0
555
0
57.6
185
2.52E-04 5.76E-06 0.00
MACX MCR-RPSSI-2I(-SP)
Low/High
A
4)
2
85.6
0
250.8
224.1
62.3
197
2.73E-04 6.23E-08 78.3
MACX MCR-SL-IDSI-I(-SP)
Low/High
A
4)
2
94.7
0
496.5
0
57.6
204
1.22E-04 2.79E-08 0.00
MACX MCR-SL-RPSS-2I-2I(-SP) Low/High
A
4)
2
87.6
0
195
198
55.3
254
2.48E-04 5.53E-08 78.1
DC (%)
SIL
2)
PFHd
Operating mode
A
2811284
PFDavg 1)
Device type
Low/High
Order No.
Demand
Short designation
For additional operating modes, please refer to the corresponding data sheet for the relevant product at
phoenixcontact.net/products.
2811572
MACX MCR-UI-UI(-SP)(-NC)
2811446
2811556
2811459
2811585
MACX MCR-UI-UI-UP(-SP)(-NC)
2811297
2811569
2865955
MACX MCR-SL-RPSSI-I(-SP)
2924207
2865968
2924210
2924825
2924838
2865971
2924223
2904089
2904090
1)
For T1 = 1 year
2)
Input isolator I = I (4 … 20 mA)
3)
Output isolator I = I (4 … 20 mA)
4)
Repeater power supply
105016_en_03
PHOENIX CONTACT
13
FUNCTIONAL SAFETY CHARACTERISTICS
9.2
Temperature
λDD (FIT)
λDU (FIT)
MTBF (years)
94.00
0
0
805
43
97
2.95E-04 4.30E-08 94.00
3)
2
93.00
0
0
789
56
97
3.75E-04 5.60E-08 93.00
4)
2
94.00
0
234
543
43
85
2.88E-04 4.30E-08 92.00
5)
2
93.00
0
238
522
56
85
3.67E-04 5.60E-08 90.00
DC (%)
λSU (FIT)
2
PFHd
λSD (FIT)
2)
PFDavg 1)
SFF (%)
Low/High
SIL
2811394
Operating mode
Device type
Demand
Order No.
Short designation
For additional operating modes, please refer to the corresponding data sheet for the relevant product at
phoenixcontact.net/products.
2811860
MACX MCR-T-UI-UP(-SP)(-C)
B
2811873
Low/High
2811970
2811387
Low/High
2811828
2811514
MACX MCR-T-UIREL-UP(-SP)
(-C)
B
Low/High
2811831
2865065
2924317
2865078
MACX MCR-SL-RTD-I(-SP)
(-NC)
Low/High
B
-
2
96.60
461
11.2
318
32.3
105
1.30E-04 3.23E-08 90.80
MACX MCR-SL-TC-I(-NC)
Low/High
B
-
2
96.50
438
11
314
32.4
108
1.31E-04 3.24E-08 90.70
2924320
2924333
2924346
1)
For T1 = 1 year
2)
PT 100 3-wire, output 4...20 mA
3)
Voltage input mV, output 4...20 mA
4)
Pt 100 3-wire, output relay
5)
Voltage input mV, output relay
105016_en_03
PHOENIX CONTACT
14
FUNCTIONAL SAFETY CHARACTERISTICS
9.3
Digital IN
SIL
SFF (%)
λSD (FIT)
λSU (FIT)
λDD (FIT)
λDU (FIT)
MTBF (years)
PFDavg 1)
PFHd
DC (%)
78.9
6
242
7
60
304
2.90E-04
-
10.0
3)
2
78.0
1
249
6
64
304
3.08E-04
-
8.0
2865010
2)
2
79.4
6
244
7
57
223
2.83E-04
-
10.0
2924265
3)
2
78.0
1
251
6
64
223
3.09E-04
-
8.0
2865049
2)
2
78.3
6
249
7
64
204
3.09E-04
-
9.0
2924294
3)
2
78.3
1
248
6
62
204
3.01E-04
-
8.0
2865052
2)
2
86.6
6
403
0
63
226
3.01E-04
-
0.0
2924304
3)
2
86.4
0
413
0
65
226
3.10E-04
-
0.0
2865023
2)
2
83.0
11
203
2
43
336
1.88E-04
-
0.0
2924278
3)
2
85.0
1
201
6
35
336
1.53E-04
-
0.0
2865036
2)
2
81.0
12
251
15
64
269
2.80E-04
-
0.0
3)
2
81.0
2
262
12
64
269
2.80E-04
-
0.0
Device type
2
2924252
Demand
2)
Order No.
Operating mode
Short designation
For additional operating modes, please refer to the corresponding data sheet for the relevant product at
phoenixcontact.net/products.
Low
A
2865997
MACX MCR-SL-NAM-R(-SP)
MACX MCR-SL-NAM-2RO(-SP)
MACX MCR-SL-2NAM-RO(-SP)
MACX MCR-SL-2NAM-R-UP(-SP)
MACX MCR-SL-NAM-2T(-SP)
MACX MCR-SL-2NAM-T(-SP)
2924281
1)
For T1 = 1 year
2)
Non-inverted output (N)
3)
Inverted output (I)
105016_en_03
Low
Low
Low
Low
Low
A
A
A
A
A
PHOENIX CONTACT
15
FUNCTIONAL SAFETY CHARACTERISTICS
10
Ex-i signal conditioners
Substitute values for 1001 structure
10.1
Analog IN/analog OUT
λSD (FIT)
λSU (FIT)
λDD (FIT)
λDU (FIT)
MTBF (years)
90.7
0
486.7
0
49.9
209
2.19E-04 4.99E-08
0.0
MACX MCR-EX-SL-RPSSI-I-UP
(-SP)
Low/High
A
2)
2
90.5
0
558.0
0
58.2
183
2.55E-04 5.82E-08
0.0
MACX MCR-EX-SL-RPSSI-2I
(-SP)
Low/High
A
2)
2
85.6
0
250.8
224.1
62.3
197
2.52E-04 5.76E-08 78.3
MACX MCR-EX-SL-IDSI-I(-SP)
Low/High
A
3)
2
94.7
0
496.5
0
57.6
204
1.22E-04 2.79E-08
MACX MCR-EX-SL-RPSS-2I-2I
(-SP)
Low/High
A
2)
2
92.3
0
316.0
273
55.4
159
2.52E-04 5.53E-08 86.2
DC (%)
SFF (%)
2
PFHd
SIL
2)
2865340
PFDavg 1)
Operating mode
A
Demand
MACX MCR-EX-SL-RPSSI-I(-SP) Low/High
Order No.
Device type
Short designation
For additional operating modes, please refer to the corresponding data sheet for the relevant product at
phoenixcontact.net/products.
2924016
2865793
2924029
2865366
2924236
2865405
0.0
2924032
2865382
2924676
1)
For T1 = 1 year
2)
Repeater power supply
3)
Output isolator I = I (4…20 mA)
105016_en_03
PHOENIX CONTACT
16
FUNCTIONAL SAFETY CHARACTERISTICS
10.2
Temperature
λDD (FIT)
λDU (FIT)
MTBF (years)
2
94.0
0
0
805
43
97
2.95E-04 4.30E-08 94.0
3)
2
93.0
0
0
789
56
97
3.75E-04 5.60E-08 93.0
4)
2
94.0
0
234
543
43
85
2.88E-04 4.30E-08 92.0
5)
2
93.0
0
238
522
56
85
3.67E-04 5.60E-08 90.0
PFHd
DC (%)
λSU (FIT)
2)
PFDavg 1)
λSD (FIT)
2811763
MACX MCR-EX-T-UI-UP(-SP)
(-C)
SFF (%)
Low/High
2924689
SIL
2865654
Operating mode
Device type
Demand
Order No.
Short designation
For additional operating modes, please refer to the corresponding data sheet for the relevant product at
phoenixcontact.net/products.
B
Low/High
2924692
2865751
Low/High
2924799
2865722
MACX MCR-EX-T-UIREL-UP
(-SP)(-C)
B
Low/High
2924809
2865939
2924142
2865573
MACX MCR-EX-SL-RTD-I(-SP)
(-NC)
Low/High
B
-
2
96.6
461
11.2
318
32.3
105
1.30E-04 3.23E-08 90.8
MACX MCR-EX-SL-TC-I(-NC)
Low/High
B
-
2
96.5
438
11
314
32.4
108
1.31E-04 3.24E-08 90.7
2924168
2865942
2865586
2864587
MCR-FL-TS-LP-I-EX
Low/High
B
2
> 75
136
183
17
111
255
4.85E-04
-
13.0
2864545
MCR-HT-TS-I-EX
Low/High
B
2
> 73
136
183
17
111
255
4.69E-04
-
13.0
1)
For T1 = 1 year
2)
Pt 100 3-wire, output 4...20 mA
3)
Voltage input mV, output 4...20 mA
4)
Pt 100 3-wire, output relay
5)
Voltage input mV, output relay
105016_en_03
PHOENIX CONTACT
17
FUNCTIONAL SAFETY CHARACTERISTICS
10.3
Digital IN/digital OUT
2865450
MACX MCR-EX-SL-NAM-2RO
(-SP)
2)
Low
λDD (FIT)
λDU (FIT)
MTBF (years)
PFDavg 1)
PFHd
DC (%)
78.9
6
242
7
60
304
2.90E-04
-
10.0
78.0
1
249
6
64
304
3.08E-04
-
8.0
2
3)
2924045
λSU (FIT)
MACX MCR-EX-SL-NAM-R(-SP)
λSD (FIT)
2)
2865434
SFF (%)
A
SIL
Device type
Low
Operating mode
Demand
Order No.
Short designation
For additional operating modes, please refer to the corresponding data sheet for the relevant product at
phoenixcontact.net/products.
A
79.4
6
244
7
57
223
2.83E-04
-
10.0
0
8.0
2
2924061
3)
78.0
1
251
6
64
223
3.09E-04
-
2865476
2)
78.3
6
249
7
64
204
3.09E-04
-
9.0
78.3
1
248
6
62
204
3.01E-04
-
8.0
2924087
2865984
2924249
MACX MCR-EX-SL-2NAM-RO
(-SP)
Low
MACX MCR-EX-SL-2NAM-R-UP
(-SP)
Low
MACX MCR-EX-SL-NAM-2T(-SP)
Low
A
2
3)
2)
A
2)
2865463
A
3)
2865489
2)
MACX MCR-EX-SL-2NAM-T(-SP)
Low
2866006
2924883
2865492
2924113
2865764
2924139
2865502
2924197
2865609
2924126
2865515
2924100
2924867
2924870
6
403
0
63
226
3.01E-04
-
0.0
0
413
0
65
226
3.10E-04
-
0.0
83.0
11
203
2
43
336
1.88E-04
-
0.0
85.0
1
201
6
35
336
1.53E-04
-
0.0
81.0
12
251
15
64
269
2.80E-04
-
0.0
81.0
2
262
12
64
269
2.80E-04
-
0.0
2
2924074
A
2
3)
2924090
86.6
86.4
2
3)
2)
84.0
0
106
72
32
266
1.74E-04
-
69.0
83.0
0
108
72
36
266
1.74E-04
-
66.0
3
100.0
0
284
0
0
378
0.00E+00
-
0.0
-
3
100.0
0
284
0
0
378
0.00E+00
-
0.0
A
-
3
100.0
0
284
0
0
378
0.00E+00
-
0.0
Low
A
-
3
100.0
0
284
0
0
378
0.00E+00
-
0.0
MACX MCR-EX-SL-SD-21-60-LP
(-SP)
Low
A
-
3
100.0
0
284
0
0
378
0.00E+00
-
0.0
MACX MCR-EX-SL-SD-48-LFD
(-SP)
Low
A
-
3
94.8
0
406
45.1
24.6
167
1.08E-04
2.46E-8
64.7
MACX MCR-EX-SL-NAM-NAM
(-SP)
Low
MACX MCR-EX-SL-SD-21-25-LP
(-SP)
Low
A
-
MACX MCR-EX-SL-SD-21-40-LP
(-SP)
Low
A
MACX MCR-EX-SL-SD-21-45-LP
(-SP)
Low
MACX MCR-EX-SL-SD-24-48-LP
(-SP)
1)
For T1 = 1 year
2)
Non-inverted output (N)
3)
Inverted output (I)
105016_en_03
A
2
3)
PHOENIX CONTACT
18
FUNCTIONAL SAFETY CHARACTERISTICS
11
Explanation of terms
Abbreviation Term
EN ISO 13849-1
PL
Performance level
Category
SILCL
Category
Safety integrity level claim limit
Probability of dangerous failure per
PFHd
hour
Mission time
tM
EN IEC 61508 / 61511 / 62061
HFT
SIL
SFF
λSD
λSU
λDD
λDU
λTotal
DC
MTBF
PFDavg
FIT
T1max
105016_en_03
Explanation
Classification of the ability of safety functions to meet a safety
demand.
Classification of the resistance to faults according to EN ISO 13849-1.
SIL claim limit (suitability)
Probability of dangerous failure per hour
Duration of use
Ability of a function unit to continue with the execution of a demanded
function despite existing faults or deviations.
Safety integrity level
Safety integrity level
Safe failure fraction
Fraction of safe failures
Failure rate - safe detected
Failure rate of safe detected failures
Failure rate - safe undetected
Failure rate of safe undetected failures
Failure rate - dangerous detected
Failure rate of dangerous detected failures
Failure rate - dangerous undetected Failure rate of dangerous undetected failures
Total failure rate
Failure rate of all failures
Diagnostic coverage
Diagnostic coverage
Mean time between failure
Average failure time period
Average probability of failure on
Average probability of failure on demand
demand
Hardware failure tolerance
Failure in time (in 109 hours)
Proof test interval
Failures per unit time (1 failure every 109 hours)
Repeat testing
PHOENIX CONTACT
19
FUNCTIONAL SAFETY CHARACTERISTICS
12
Revision history
Revision
00
01
Date
12/2011
01/2012
02
03
04/2012
01/2014
105016_en_03
Contents
First publication
Layout adjustments
PSR-SIM4 modular safety relay added
PSR-SACB-4/4-L-5,0PUR-SD accessory added
FL PN/PN SDIO-2TX/2TX safe PROFINET gateway added
Layout adjustments
Values for ESA2-B and ESAM2/3x1 corrected in “Safety relays” on page 2 and PSR-URML4,
PSR-URM4 42-230UC, and PSR-MXF added
“Forcibly guided coupling relays” on page 6 in Section 3 “Safety switching devices” moved
(previously Section 6)
Values for order numbers 2986229, 2986232, 2986012, 2986025, 2986038, and 298604
updated in “PSR-TRISAFE configurable safety module” on page 7 and order numbers
2986096 and 2986106 added
Order numbers 2700994 and 2701625 added in “Safe control technology” on page 10, PL and
category for IL-PSDOR-4-1CH-AC15 and IL-PSDOR-4-1CH-DC13 corrected, note text for
order number 2985864 reduced
Designation for order number 2916794 corrected in “Safe control technology” on page 10
“Safe coupling relays” on page 12 renamed (previously “Process technology”), PSR-ETP/1x1
added, and footnote for PSR-FSP and PSR-ETP/1x1 inserted
“Signal conditioners” on page 13 added
“Ex-i signal conditioners” on page 16 added
“Explanation of terms” on page 19 extended