SERIES POWER ENTRY MODULE EMI FILTERS

V
D E
SERIES POWER ENTRY MODULE EMI FILTERS
INTRODUCTIONS
SPECIFICATIONS
1. Power module incorporates an IEC connector, a fuse holder with
optional power on/off switch and voltage selector switch, plus
an EMI filter all-in-one single, easy-to-install unit.
2. Fuse holder designed for one IEC 5x20mm fuse. Safety interlock
prevents fuse removal with line plug inserted (Use only with 250V
fuse).
3. All part numbers are UL recognized, CSA certified and VDE
approved.
4. Switch electrical lifetime: 10,000 cycles.
Maximum inrush current: 70A.
1. Maximum leakage current each
line-to-ground @ 115VAC 60Hz: 0.25mA
@ 250VAC 50Hz: 0.45mA
2. Hipot rating (one minute)
line-to-ground: 2250VDC
line-to-line: 1450VDC
3. Operating frequency: 50/60Hz
4. Rated voltage: 115/250VAC
MINIMUM INSERTION LOSS IN dB
CURRENT
RATING
3A
6A
3A
6A
COMMON MODE (L-G) IN 50 OHM SYSTEM
FREQUENCY-MHz
.15
.50
1.0
5.0
10
30
35
40
35
35
16
25
30
42
45
DIFFERENTIAL MODE (L-L) IN 50 OHM SYSTEM
10
40
45
45
45
6
25
30
42
45
30
35
40
35
40
DELTA PART NO.
115VAC
RATED CURRENT
250VAC
IEC CONNECTOR
FUSE HOLDER
POWER SWITCH
VOLTAGE SELECTOR SW
ELECTRICAL SCHEMATIC
AK1
6A
6A
FIG. A
AK2
6A
6A
AK2D
6A
4A
AK3
6A
6A
AK3D
6A
4A
AK4
6A
6A
AK5
6A
6A
SP1
DP2
SP1
REAR3
FIG. A
DP2
REAR3
FIG. B
REAR3
FIG. A
FRONT4
FIG. C
FIG. A
1. Single-pole UL, CSA & VDE approved
Current rating: UL & CSA-6A both at 125VAC & 250VAC;
VDE-6A at 250VAC.
2. Double-pole UL CSA & VDE approved
Current rating: UL & CSA-6A at 125VAC, 4A at 250VAC;
VDE-4A at 250VAC.
FIG. B
3. Voltage selector SW -UL, CSA & VDE approved
Current rating: 10A at 125VAC; 5A at 250VAC.
4. Voltage selector SW -UL, CSA & VDE approved
Current rating: UL & CSA-6A both at 125VAC & 250VAC;
VDE-6A at 250VAC.
ELECTRICAL SCHEMATIC
AK3/4 ONLY
AK1/4 WITHOUT POWER SW
F
SW
L'
Cy
L
I
N
E
C1 R
L
Cy
N
G
F
L
I
N
E
L
C2 O
A
D
F
L'
Cy
C1 R
L
Cy
N
G
N'
L 110V
O
A 220V
D
L
C2 O
A
D
N'
G'
FIG. B
4-1
1
110V
2
110V
3
220V
110V 4
FIG. C
For transformers with two separate windings
L
L
I
N
E
C2
G'
AK3D ONLY
SW
C1
Cy
N
G
N'
R
Cy
L
G'
FIG. A
SW
L'
L
L
POWER ENTRY MODULE FILTERS
TYPE & RATED CURRENT
Suggested thickness of mounting
panel is from 0.04 to 0.07 inch
Suggested mounting cutout
27.0
1.063 0.003
R0.04Max.
1.0
2.6 0.003
66.0
MECHANICAL CONSTRUCTION
L
1.059
26.9
220
1.15
29.2
G
110
N
L
1
G
2
4
3
N
0.57
0.43
AK5
10.9
2.17
55.1
2.24
56.9
14.48
2.65
67.3
2.57
65.3
2.65
67.3
L
N
G
1.059
26.9
1.15
29.2
N
I
L
2.17
55.1
2.38
60.5
O
G
AK2,AK2D
2.57
65.3
O
G
I
L
2.60
66.0
N
G
0.65
16.5
115V
AK3,AK3D
AK4 (without power switch)
1.059
26.9
1.15
29.2
2.65
67.3
G
N
L
2.17
55.1
2.24
56.9
POWER ENTRY MODULE FILTERS
1.15
29.2
2.65
67.3
G
AK1
2.57
65.3
4-2
1.059
26.9
UNIT:
INCH
mm