FlexTemp 2321 Universal Transmitter 4...20 mA transmitter with HART® communication. RTD, T/C, mV and R inputs Isolation voltage 2 kVac Configuration via FlexProgrammer or HART® configurator Accuracy < 0.1°C (Pt100) Configurable linearisation, damping and status indication Current-trim and sensor-trim Local, remote or fixed compensation for "cold junction" (CJC) Description FlexTemp 2321 is a 4...20 mA loop-powered, configurable universal transmitter with galvanic isolation between input and output. The input can be configured for RTD or T/C sensors, resistance, current or voltage signals. Either 2-, 3- or 4-wire connection can be selected for the resistance input. The built-in temperature sensor or a remote Pt100 sensor can be used to compensate for "cold junction" (CJC) if thermocouples are connected. www.baumerprocess.com Design and specifications subject to change without notice The HART® communication feature on-line process calibration and adjustment, transmitter configuration and multiple process control in 2-wire networks. The configuration can be established from a standard HART® configurator or the dedicated FlexProgrammer configuring tool connected to a PC. Data Sheet 2321-1 Page 1 Technical Data HART® data Input Digital accuracy See „Measuring ranges“ Protocol HCF standard, Rev.5 CJC-compensation Local < 0.7°C Features {1} RTD measuring current 0.2 mA, continuously Cable resistance 2-wire 3-/4-wire 3-/4-wire Max. 30 Ohm/wire {1} T > 600°C: Max. 10 Ohm/wire T < 600°C: Max. 30 Ohm/wire Protection +/- 35 Vdc Read serial number Read/Change user ID Read/Change configuration Read input signal value Read output signal value Input signal logging 2-point sensor-trim 2-point current-trim Suppression 50 and 60 Hz Resolution 16 bit Repeatability < 0.05°C EMC data Output Signal span 4...20 mA, 2-wire {1} 20...4 mA, 2-wire {1} Characteristic Generic standards EN 61000-6-3, EN61000-6-2 Product standard EN 61326 Mechanical data Dimensions 62 x 88 x 24 mm Linear or customised with max. 30 points {1} Protection class Housing: IP 30; Terminals: IP 10 Accuracy < 0.1% of signal span Isolation Supply range 8...35 Vdc 50 Vac ; test 2 kVac Temperature drift Typ. 0.003% per °C Ripple immunity 3 Vrms Load equation RL < (Vcc - 8)/23 [kOhm] Power-on time 1.8...3.9 sec. Up/Down scaling limits 23 mA/3.5 mA {1} Failure information NE43 Damping 0...15 sec. {1} Response time (t90) Pt100 1.0 sec. ; T/C 1.6 sec. Resolution 12 bit Other data Max. 0.01% per °C Environmental conditions Test conditions Configuration Pt100; 0...100°C Amb. temperature 23°C +/- 2°C Disposal of product and packing Operating temperature -40...85°C Storage temperature -55...90°C Humidity < 90% RH, non-condensing Note Vibrations Lloyds Register, test 2 {1} Configurable {2} The max. temperature is lower for RTD-elements in the range 500...1000, i.e. Pt1000 max. 350°C. According to national laws or by returning to Baumer Measuring Ranges Type Pt25...Pt1000 Pt25...Pt1000 Pt25...Pt1000 Ni25...Ni1000 Cu25...Cu1000 B(PtRh30-Pt) E(NiCr-CuNi) J(Fe-CuNi) K(NiCr-Ni) L(Fe-CuNi) N(NiCrSi-NiSi) R(PtRh13-Pt) S(PtRh10-Pt) T(Cu-CuNi) U(Cu-CuNi) W5-Re (Type C) W3-Re (Type D) Lin. voltage Lin. voltage Lin. resistance Lin. resistance Standard DIN/EN/IEC 60751 a = 0.003902 a = 0.003916 DIN 43760 0.428 Ohm/°C IEC 584 IEC 584 IEC 584 IEC 584 DIN 43710 IEC 584 IEC 584 IEC 584 IEC 584 DIN 43710 ASTM 988 ASTM 988 www.baumerprocess.com Design and specifications subject to change without notice Range -200...850°C {2} -200...850°C {2} -200...850°C {2} -50...250°C {2} -50...200°C 100...1820°C -270...900°C -210...1200°C -250...1370°C -200...900°C -200...1300°C -50...1750°C -50...1750°C -250...400°C -200...600°C 0...2300°C 0...2300°C -10...70 mV -0.1...1.1 V 0...390 Ohm 0...2200 Ohm Min. span 10°C 10°C 10°C 10°C 10°C 50°C 50°C 50°C 50°C 50°C 50°C 100°C 100°C 40°C 50°C 100°C 100°C 2 mV 20 mV 5 Ohm 25 Ohm Accuracy 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 2°C 1°C 1°C 1°C 1°C 1°C 2°C 2°C 1°C 1°C 2°C 2°C 0.04 mV 0.4 mV 0.05 Ohm 0.25 Ohm Resolution 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1°C 0.1 mV 1 mV 0.01 Ohm 0.1 Ohm Data Sheet 2321-1 Page 2 Ordering Details - FlexTemp 2321 2321 000x (x) Type Standard version 5...8´ digit 1 Configuration Configuration according to customer specifications 9´ digit C Application Example T/C Pt100 (3) 230 Vac (4) 3 4 7 8 3 1 1 + 2 - 8 2 3 4 24 Vdc 4...20 mA + HART signals FlexTemp 2321 HART® Configurator Power supply Configuration Note: Disconnect loop supply before connecting the FlexProgrammer to FlexTemp 2321. FlexProgrammer 1 1 2 1 FlexProgrammer 2 2 FlexProgrammer 9701 Red clip 1 2 Black clip Note: Ambient temperature range 0...50°C www.baumerprocess.com Design and specifications subject to change without notice Data Sheet 2321-1 Page 3 Electrical Installation 3 7 T/C 4 8 3 7 No cablecompensation {3} RTD 3 7 4 8 Internal CJCcompensation 3 7 RTD 4 8 4-wire cablecompensation Current measurement 4 8 4 8 3 7 No compensation {3} 3 7 + External CJC-compensation No cable compensation {3} 3 7 Resistance Resistance 4 8 3 7 3-wire compensation for transfer resistance {4} + External CJC-compensation 3-wire cable compensation Resistance 4 8 3 7 4-wire compensation for transfer resistance {4} Voltage measurement 4 8 3-wire cable compensation Potentiometer 3 7 4 8 No compensation {3} Potentiometer T/C 4 8 3 7 + T/C 3-wire cablecompensation 3 7 4 8 Potentiometer UK/2007-06-01 This data sheet may only be reproduced in full. RTD 4 8 4-wire cable compensation Notes {3} Configurable compensation for cable resistance {4} Transfer resistance between element and wiper 3 7 4 8 3 7 + 4 8 Dimensional drawings + [mm] Accessories 65.5 The FlexProgrammer 9701 is a dedicated tool to configure all Baumer configurable products. 88 62 24 Type No. 9701-0001 complies: FlexProgrammer interface unit CD with the FlexProgram software and product drivers (DTM) USB cable Cable with 2 alligator clips www.baumerprocess.com Design and specifications subject to change without notice Data Sheet 2321-1 Page 4