(Y)TED hygienic

(Y)TED
hygienic pressure switch
Main Features
„„
-1 … 0 bar up to 0 … 25 bar
„„
Robust stainless steel housing for severe industrial environments
„„
Intrinsically safe version (LCIE 03 ATEX 6300 X)
„„Two threshold outputs (PNP transistors or galvanic isolation)
Applications
„„
Food & Beverage
Main characteristics
Measuring ranges
-1 ... 0 bar up to 0 ... 25 bar
Long term stability
≤ ± 0.2% FS/Year
Accuracy
≤ ± 0.5% FS
Measuring principle Thick film on ceramic
-1 ... 0 bar up to 0 ... 25 bar
Type of pressure
Relative / Absolute
Accuracy
≤ ± 0.5% FS
Thermal drift
≤ ± 0.15% FS/10 K
Long term stability
≤ ± 0.2% FS/Year
Threshold outputs
TED6
Galvanically isolated pressure switch with two
thresholds as static relays, switching capacity of
400 mA at 60 VDC or 40 VAC
Pressure switch with two thresholds as PNP transistors, switching capacity of 400 mA at 24 VDC
TED7
Pressure switch with two thresholds as PNP
transistors,switching capacity of 400 mA at 24 VDC
TEDM
Galvanically isolated pressure switch with Modbus communication with two thresholds as static
relays, switching capacity of 400 mA at 60 VDC
or 40 VAC
Intrinsically safe pressure switch with two thresholds as PNP transistors, switching capacity of 40
mA at 28 VDC
2% to 98% of the measurement range
YTED
Threshold
adjustment range
Typical response
time
Repeatability of
switching points
www.baumer.com
RΩ = (Usupply-10 V) / 0,02 A
Current ouput
(3 wires)
RΩ ≤ 400 Ω
Voltage output
RΩ > 5 kΩ
Insulation resistance >100 MΩ at 500 VDC
Environment
Process connections See page 4
TED5
Load impedance
Current ouput
(2 wires)
Temperature
Storage
Medium
Ambient
-40 ... +85°C
-25 ... +100°C
-25 ... +85°C
Protection rating
IP67 (EN 60529)
Vibration
IEC60068-2-6
1.5 mm p-p (10 – 55 Hz), 20 g (55 Hz – 2 KHz)
Shock
IEC60068-2-27
25 falls from 1 m on concrete ground
Design and specifications subject to change without notice
(includes linearity, hysteresis,
repeatability, error of span
and zero point according limit
point adjustment)
4 … 20 mA (2 wires) / 10 … 32 VDC
4 … 20 mA (3 wires) / 10 … 28 VDC
4 … 20 mA (2 wires - ATEX version) / 10 … 28 VDC
0...10 V / 10 ... 32 VDC
Modbus / 10 ... 32 VDC
Technical specifications
Measuring ranges
Output signal /
Power supply
Material
Process connection SS 1.4404 AISI 316L
Housing
SS 1.4301 AISI 304
Diaphragm
SS 1.4404 AISI 316L
Sealing
NBR
≤ 20 ms
2013-11-21
(includes linearity, hysteresis,
repeatability, error of span
and zero point according limit
point adjustment)
Electrical specification
≤ ± 0.2% FS
Data sheet A31.08
Page 1 / 5
(Y)TED
hygienic pressure switch
Version with galvanically isolated digital thresholds – TED5
and TEDM
The current supply to the pressure switch is electrically isolated from
the threshold outputs and the threshold outputs are isolated from each
other.400 mA at 60 VDC or 40 VAC.
It is possible to have a separate power supply between the TEDM
(≤ 32 VDC) and the threshold contacts (≤ 60 VDC or ≤ 40 VAC).
Configuration
The three keys on the front panel are used to configure the following
operating parameters:
● Switching point value for each threshold
● Switching hysteresis value for each threshold
● Active status for each threshold (NO or NC)
● Time delay of each threshold from 0 to 25 s in 0.1 s steps
● Auto-zero function
● Self test and parameter protection by a 4 digit code
Additional parameter for the TEDM:
● Modbus slave address of the pressure switch
● Parity selection
Maximum and minimum value consultation
When the pressure switch is in the measurement mode it is possible
to display or initialise the maximum and minimum pressure values
saved at any time.
Modbus communication
The TEDM has a RS485 serial port and uses the Modbus RTU communication protocol.
The Modbus protocol is a two-way exchange protocol based on a
hierarchical data base structure between a master and multiple slave
stations. It enables the user to read the pressure and the status of
each threshold (open or closed).
Exchange between the master and one slave: The master sends an
order and waits for a reply.
Exchange between the master and all slave stations: The master
broadcasts a message to all the slaves in the network and they perform the order in the message without sending a reply.
Two slave stations cannot talk together.
Parameter consultation
Parameters for each threshold, Modbus address (TEDM) and parity
(TEDM) can be viewed whithout access code.
Threshold state: Increasing
2013-11-21
Design and specifications subject to change without notice
Threshold state: Decreasing
www.baumer.com
Data sheet A31.08
Page 2 / 5
(Y)TED
hygienic pressure switch
Installations YTED
ATEX
I M1 Ex ia I Ma
Non hazardous area
Hazardous area
(0,1, 2)
Umax = 28 Vcc
Imax = 120 mA
P = 0.8 W
YTED
YTED
II 1 G
Ex ia IIC T6 or T5 Ga
Ci = 13,2 nF
Imax = 120 mA Li = 0
Barrier data
Ui ≤ 28 V
Ii ≤ 120 mA
Pi ≤ 800 mW
Capacity
Ci ≤ 13.2 nF
Inductivity
Li ≤ 0 μH
Ambient temperature Ta
In area 0, the combination of the pressure switch and the safety barrier must be covered by a calculation checked by an approved body.
For the application in Ex zone you have to respect the conditions mentioned in the ATEX Type Examination Certificate (LCIE 03 ATEX 6300 X).
You find the certificates and manuals under http://www.baumer.com/
Ta = +40°C
Ta = +70°C
G: T6
G: T6
(G = Gas)
Approvals
CE conformity
EMC directive 2004/108/CE in accordance with EN
61000-6-2, EN 61000-6-3, EN 61326-1 (Tab. 2)
Pressure directive 97/23/CE
Measuring ranges and overpressure safety
Pressure in bar
Pressure range
-1 ... 0
-1 ... 0.6
-1 ... 1.5
-1 ... 3
-1 ... 5
-1 ... 9
-1 ... 15
-1 ... 24
Over pressure
3
3
4
8
12
20
32
50
80
Burst pressure
6
6
7
12
18
30
48
75
120
-1.000 / 0
-1.000 /
0.600
-1.000 /
1.500
-1.000 /
3.000
-1.000 /
5.000
-1.000 /
9.000
-1.00 /
15.00
-1.00 /
24.00
-1.00 /
39.00
0 ... 4
0 ... 6
0 ... 10
0 ... 16
0 ... 25
50
Display at
measurement
range
-1 ... 39
Pressure in bar
Pressure range
0 ... 1
0 ... 1.6
0 ... 2.5
Over pressure
3
3
4
8
12
20
32
Burst pressure
7
7
7
12
18
30
48
75
0/1.000
0/1.600
0/2.500
0/4.000
0/6.000
0/10.000
0/16.000
0/25.000
2013-11-21
Design and specifications subject to change without notice
Display at
measurement
range
www.baumer.com
Data sheet A31.08
Page 3 / 5
(Y)TED
hygienic pressure switch
Dimensions (mm)
Ø 45
13
connector M12
bar R
S2
103
S1
39
F
DN
ØD
Bar
DN25
Ø 50.5
2.5 ≤ P ≤ 25
DN38
Ø 50.5
0.4 ≤ P ≤ 25
DN51
Ø 64
0.25 ≤ P ≤ 25
Pin assignment
TED7 - Voltage output
TED7
1
TED6/YTED - Current output (4-20 mA, 2 wires)
TED6
+Power supply (+) A
(+) A
1 + Power supply
2 Threshold 2
2 Threshold 2
4-20 mA
4 Threshold 1
3 Measure U
3 4-20 mA measure
4 Threshold 1
5
RL
- Power supply (-) A
(-) A
5 Ground
TED5
1
+ Power supply
7 + Measure
(+) A
TEDM
7
Threshold 1
2
DAT B
1
DAT A
3
RL
5
4
6 Threshold 2
5
2 - Supply / - Measure
(-) A
T
6
8
Threshold 1
Threshold 2
- Power supply
2013-11-21
8 Ground
+ Power supply
4-20 mA
3
4
TEDM - Modbus output RS485
Design and specifications subject to change without notice
TED5 - Current output (4-20 mA, 3 wires)
T
www.baumer.com
Data sheet A31.08
Page 4 / 5
(Y)TED
hygienic pressure switch
Codification (Y)TED
Model
2 galv. Separated switching points, 4...20mA (3 wires)
2 switching points, 4...20mA (2 wires)
2 switching points, 0...10 V
2 switching points,Modbus RS485
2 switching points, 4…20 mA, ATEX Ex ia intrinsic safety
Process connection
CLAMP ISO DN 25
CLAMP ISO DN 38
CLAMP ISO DN 51
P ≥ 2.5 bar
TED5
TED6
TED7
TEDM
YTED
xx .
x
type
type
type
type
type
type
type
type
type
relative
relative
relative
relative
relative
relative
relative
relative
relative
xxx
.
x
/
xxxx
.
3
pressure
pressure
pressure
pressure
pressure
pressure
pressure
pressure
pressure
.
–
15
18
11
Sealing
NBR
Pressure range and unit in bar
Only
-1...0
Only
-1...0.6
Only
-1...1.5
Only
-1...3
Only
-1...5
Only
-1...9
Only
-1...15
Only
-1...24
Only
-1...39
0...1
0...1.6
0...2.5
0...4
0...6
0...10
0...16
0...25
–
.
B59
B72
B74
B76
B77
B79
B81
B82
B1L
B15
B16
B18
B19
B20
B22
B24
B26
Kind of pressure
Relative
Absolute
.
R
A
Options
Drinking water application
Process connection electropolished Ra ≤ 0.4
Capacitive cell (except YTED)
M12, 5 pins with shielded cable, length 2 m
M12, 5 pins with shielded cable, length 5 m
M12, 5 pins with shielded cable, length 10 m
M12, 8 pins with shielded cable, length 2 m
M12, 8 pins with shielded cable, length 5 m
M12, 8 pins with shielded cable, length 10 m
/
2013-11-21
Design and specifications subject to change without notice
0619
0593
0591
0604
0605
0606
0607
0608
0609
www.baumer.com
Data sheet A31.08
Page 5 / 5