Jupiter JM4 Ex ia

1
2
EC-TYPE EXAMINATION CERTIFICATE
Equipment or Protective systems intended for use in Potentially
Explosive Atmospheres - Directive 94/9/EC
3
EC-Type Examination Certificate No:
FM14ATEX0059X
4
Equipment or protective system:
(Type Reference and Name)
Jupiter JM4 Magnetostrictive Level Transmitter
5
Name of Applicant:
Magnetrol International Inc.
6
Address of Applicant:
705 Enterprise Street
Aurora, IL 60504 USA
7
This equipment or protective system and any acceptable variation thereto is specified in the schedule to this
certificate and documents therein referred to.
8
FM Approvals Ltd, notified body number 1725 in accordance with Article 9 of Directive 94/9/EC of 23 March
1994, certifies that this equipment has been found to comply with the Essential Health and Safety Requirements
relating to the design and construction of equipment intended for use in potentially explosive atmospheres given
in Annex II to the Directive.
The examination and test results are recorded in confidential report number:
3051963 dated 30th October 2015
9
Compliance with the Essential Health and Safety Requirements, with the exception of those identified in item 15
of the schedule to this certificate, has been assessed by compliance with the following documents:
EN 60079-0:2012 + A11:2013, EN 60079-11:2012, EN 60079-31: 2014 and EN 60529:1991+ A 1:2000
10
If the sign ‘X’ is placed after the certificate number, it indicates that the equipment is subject to specific
conditions of use specified in the schedule to this certificate.
11
This EC-Type Examination certificate relates only to the design, examination and tests of the specified
equipment or protective system in accordance to the directive 94/9/EC. Further requirements of the Directive
apply to the manufacturing process and supply of this equipment or protective system. These are not covered by
this certificate.
12
The marking of the equipment or protective system shall include:
II 1 G Ex ia IIC T4 Ga Ta = -40ºC to +70ºC, IP67
II 2 D Ex tb IIIC T85°C…T120°C Db Ta = -15ºC to +70ºC, IP67
Digitally signed by Mick Gower
DN: cn=Mick Gower, o=FM Approvals, ou,
[email protected],
c=GB
Date: 2015.11.02 14:57:30 Z
Mick Gower
Certification Manager, FM Approvals Ltd.
Issue date: 02nd November 2015
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals Ltd. 1 Windsor Dials, Windsor, Berkshire, UK. SL4 1RS
T: +44 (0) 1753 750 000 F: +44 (0) 1753 868 700 E-mail: [email protected] www.fmapprovals.com
F ATEX 020 (Apr/14)
Page 1 of 4
SCHEDULE
to EC-Type Examination Certificate No. FM14ATEX0059X
13
Description of Equipment or Protective System:
The Jupiter Model JM4 is a continuous level transmitter for liquid level control, utilizing the engineering
principle of magnetostriction and the effect of a magnetic field on the magnetostrictive wire as the basis for
operation of the instrument. The primary components are the probe assembly, containing the wire and
Preamp PC Board assembly, and the electronics assembly containing all other PC Boards. The Jupiter
JM4 Transmitter is available as the Model JM4-51 normal mode (Entity input version) or JM4-52 Fieldbus
mode (FISCO input version) and only differs in the Digital PC Board and Wiring PC Board.
A low energy pulse which is generated by the Preamp travels the length of the magnetostrictive wire. A
return signal is generated from the location where the magnetic field of the MLI float intersects the wire. A
timer measures the elapsed time between the generation of the pulse and the return of the mechanical or
acoustic signal. This is detected by the acoustic sensor located in the end of the probe. The software is set
up to interpret the time-of-flight data and to display and transmit the process variable data resulting from the
measurement.
The Jupiter Model JM4 is a level transmitter with Fieldbus digital communication. The Jupiter Model JM4
uses a nominal input voltage of 24VDC and it provides Fieldbus digital communication. With the FISCO
concept the input voltage is limited to 17.5V. A digital display and keypad are optional.
The Jupiter Model JM4 is housed in a dual compartment (die-cast aluminum or investment cast 316SS)
enclosure with separate wiring and electronics compartments. The wiring compartment at the top of the
transmitter isolates the power/signal conductors from the electronics compartment beneath it by way of an
environmentally sealed feed-through. A quick disconnect probe coupling allows probes to be installed
without concern for their orientation to the transmitter head. Probe mounting can be provided integrally,
directly to the electronics housing, or can be remotely mounted up to 12 feet from the electronics housing.
Model Code Structure and Parameters:
JM4-51ab-cde / 2fg-hij-klm-n-o. Jupiter JM4 Magnetostrictive Level Transmitter / JM4 Probe.
Entity Parameters:
Ui = 28.6V, Ii = 140mA, Pi = 1W, Ci = 4.4nF, Li = 2.7μH
a = Safety Option: 0, 1 or 2.
b = Accessories/Mounting: A, B, C, 0, 1 or 2.
c = Area Classification: A or D. (If c = D, b = A or 0 only)
d = Housing Material: 1 or 2.
e = Conduit Connection: 0, 1, 2 or 3.
f = Measurement System: A or C.
g = Probe Configuration: 1, 2, 8, E, F, H, K, L, M, R, S or T.
h = Process Connection: 00, 01, 11, 22, 41, 42, 43, 44, 45, 46, 47, 53, 54, 55, 56, 57, 63, 64, 65, 66, 67, CA,
CB, CC, DA, DB, DD, DE, EA, EB, ED, EE, FA, FB, FD, FE, FF or FG.
i = Material of Construction: A, B, C, D, F, L, P or 1.
j = Probe Options: N or V.
k = Installation Considerations: 0, 1, 2, 3, 4, 5, C, E, F, G, H, J or N.
l = Construction Code: 0, K, L, M or N.
m = Level/Interface Measurement: 1, 2 or 3.
n = Float: 00, 11, 12, 13, 21, 22, 23, 31, 32, 41, 42, 51, 52, 61, 62, 99, AA, AB, AC, BA, BB, CA, CB, DA, DB,
DC, FA, FB, FC, MA, MB, NA, NB, PA, PB, QA, QB, RA or RB
o = Probe Length: (3 digit max) in: inches (f = A) or centimeters (f = C).
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals Ltd. 1 Windsor Dials, Windsor, Berkshire, UK. SL4 1RS
T: +44 (0) 1753 750 000 F: +44 (0) 1753 868 700 E-mail: [email protected] www.fmapprovals.com
F ATEX 020 (Apr/14)
Page 2 of 4
SCHEDULE
to EC-Type Examination Certificate No. FM14ATEX0059X
JM4-52ab-cde / 2fg-hij-klm-n-o. Jupiter JM4 Magnetostrictive Level Transmitter / JM4 Probe.
FISCO Parameters:
Ui = 17.5V, Ii = 380mA, Pi = 5.32W, Ci = 440pF, Li = 2.7μH
a = Safety Option: 0, 1 or 2.
b = Accessories/Mounting: A, B, C, 0, 1 or 2.
c = Area Classification: A or D. (If c = D, b = A or 0 only)
d = Housing Material: 1 or 2.
e = Conduit Connection: 0, 1, 2 or 3.
f = Measurement System: A or C.
g = Probe Configuration: 1, 2, 8, E, F, H, K, L, M, R, S or T.
h = Process Connection: 00, 01, 11, 22, 41, 42, 43, 44, 45, 46, 47, 53, 54, 55, 56, 57, 63, 64, 65, 66,
67, CA, CB, CC, DA, DB, DD, DE, EA, EB, ED, EE, FA, FB, FD, FE, FF or FG.
i = Material of Construction: A, B, C, D, F, L, P or 1.
j = Probe Options: N or V.
k = Installation Considerations: 0, 1, 2, 3, 4, 5, C, E, F, G, H, J or N.
l = Construction Code: 0, K, L, M or N.
m = Level/Interface Measurement: 1, 2 or 3.
n = Float: 00, 11, 12, 13, 21, 22, 23, 31, 32, 41, 42, 51, 52, 61, 62, 99, AA, AB, AC, BA, BB, CA, CB,
DA, DB, DC, FA, FB, FC, MA, MB, NA, NB, PA, PB, QA, QB, RA or RB
o = Probe Length: (3 digit max) in: inches (f = A) or centimeters (f = C).
14
Specific Conditions of Use:
1. The enclosure contains aluminum and is considered to present a potential risk of ignition by impact or
friction. Care must be taken during installation and use to prevent impact or friction.
2. To maintain the T4 temperature code care shall be taken to ensure the “Enclosure Temperature” does
not exceed 70ºC
3. The risk of electrostatic discharge shall be minimized at installation, following the direction given in the
instruction.
4. For Installation with ambient temperature of 70ºC, refer to the manufacturer’s instructions for guidance on
proper selection of conductors.
5. Provisions shall be made to provide transient overvoltage protection to a level not to exceed 119Vdc.
6. When equipment is used in explosive dust atmospheres, the end user shall take precautions so that the
thermal effects of the process temperature shall limit the equipment enclosure and probe surface
temperatures to not exceed the required installation location temperature and shall be between T85C and
T120C.
15
Essential Health and Safety Requirements:
The relevant EHSRs that have not been addressed by the standards listed in this certificate have been identified
and assessed in the confidential report identified in item 8.
16
Test and Assessment Procedure and Conditions:
This EC-Type Examination Certificate is the result of testing of a sample of the product submitted, in
accordance with the provisions of the relevant specific standard(s), and assessment of supporting
documentation. It does not imply an assessment of the whole production.
Whilst this certificate may be used in support of a manufacturer’s claim for CE Marking, FM Approvals Ltd
accepts no responsibility for the compliance of the equipment against all applicable Directives in all
applications.
This Certificate has been issued in accordance with FM Approvals Ltd’s ATEX Certification Scheme.
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals Ltd. 1 Windsor Dials, Windsor, Berkshire, UK. SL4 1RS
T: +44 (0) 1753 750 000 F: +44 (0) 1753 868 700 E-mail: [email protected] www.fmapprovals.com
F ATEX 020 (Apr/14)
Page 3 of 4
SCHEDULE
to EC-Type Examination Certificate No. FM14ATEX0059X
17
Schedule Drawings
A list of the significant parts of the technical documentation is annexed to this certificate and a copy has
been kept by the Notified Body.
18
Certificate History
Details of the supplements to this certificate are described below:
Date
Description
02nd November 2015
Original Issue.
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals Ltd. 1 Windsor Dials, Windsor, Berkshire, UK. SL4 1RS
T: +44 (0) 1753 750 000 F: +44 (0) 1753 868 700 E-mail: [email protected] www.fmapprovals.com
F ATEX 020 (Apr/14)
Page 4 of 4
Magnetrol International Inc (1000000020)
Class No
3610
Original Project I.D.
Certificate I.D.
3051963
FM14ATEX0059X
Drawing No.
Revision Level
Drawing Title
Last Report
Electronic Drawing
009-9362
C
Fabrication Digital Board, Model 706
3051963
Yes (pdf)
009-9365
B
Fabrication Display Board, Model 706
3051963
Yes (pdf)
009-9368
A
Fabrication Digital Board, Model 706
3051963
Yes (pdf)
009-9369
A
Fabrication Wiring Board Model 706
3051963
Yes (pdf)
009-9375
B
Foundation Fieldbus Fabrication Wiring Board
3051963
Yes (pdf)
009-9378
A
Fabrication Board, Juniper JM4 Analog
3051963
Yes (pdf)
009-9379
A
Fabrication Board, Juniper JM4 Preamp
3051963
Yes (pdf)
094-6067
L
Eclipse 4X Digital Board
3051963
Yes (pdf)
094-6070
B
Display Board Eclipse 706
3051963
Yes (pdf)
094-6072
D
Digital Board Foundation Fieldbus
3051963
Yes (pdf)
094-6073
D
Wiring Board Eclipse 706
3051963
Yes (pdf)
094-6075
C
Foundation Fieldbus Wiring Board Eclipse 706
3051963
Yes (pdf)
094-6076-001
B
Schematic Jupiter 4X Analog Board
3051963
Yes (pdf)
094-6077-001
B
Schematic Jupiter 4X Preamp Board
3051963
Yes (pdf)
094-6082-001
C
Schematic Jupiter 4X Wiring Board
3051963
Yes (pdf)
099-5074
A
System Drawing Jupiter JM4 Transmitter
3051963
Yes (pdf)
099-6553
V
Jupiter JM4 Agency Drawing
3051963
Yes (pdf)
ORI-46-650
2
Jupiter JM4 Installation and Operation Manual
3051963
Yes (pdf)
02/11/2015
Page 1 of 1