MEDICAL PM100 Series 3 7 - 6 4 W AT T S - A C / D C S I N G L E O U T P U T FEATURES • • • • • • • Medical and ITE approvals Compact size High power density 10 W/cubic inch 100 W output with convection cooling up to +50℃ Low earth leakage current EN55011 /55022 class B emissions RoHS compliant SPECIFICATIONS INPUT Voltage range Frequency Inrush current Input current Earth leakage current Isolation OPERATING 90-132 /180-264 VAC (Universal mains supply operation) 47-63 Hz 40 A @ 115 VAC or 80 A @ 230 VAC, at 25°C cold start 1.9 A (rms) for 100-120 VAC 1.1 A (rms) for 200-240 VAC 150 µA max. @ 264 VAC, 63 Hz MTBF 270,000 hours at full load at 25℃ ambient temperature, calculated per MILHDBK-217F Efficiency 88-90% @ 230 VAC full load Switching frequency 100 KHz (typical) Operating temperature: -10°C to +70°C Input – Output: 4000VAC Input – Case:1500VAC Output – Case: 500VAC Storage temperature: -40°C to +85°C Relative humidity: Derating: 5% to 95% non-condensing Derate from 100% to +50°C linearly to 50% at +70°C ENVIRONMENT OUTPUT Output voltage STANDARDS AND APPROVALS See table 150 mV peak to peak on 5.0 V model, 1% peak to peak on other models ±0.2% maximum at full load Safety UL 60601-1, CSA C22.2 No. 601.1, TÜV EN 60601-1, UL 60950-1, CSA C22.2 No. 60950-1, TÜV EN 60950-1 C-Tick AS/NZS CISPR11 Group1, Class A Load regulation See table EMC standards Transient response Maximum excursion of 4% or better on all models, recovering to 1% of final value within 500 us after a 25% step load change IEC60601-1-2, EN55011 / EN55022 and FCC, VCCI: Class B conducted . class B radiated Immunity standards EN61000-3-2, EN61000-3-3, EN61000-42, EN61000-4-3, EN61000-4-4, EN610004-5, EN61000-4-6, EN61000-4-8, EN61000-4-11 Output current Ripple and noise Line regulation Overvoltage protection Temperature coefficient Provided on output; set at 110-140% of itsnominal output voltage All outputs protected to short circuit conditions All outputs ±0.04% /°C maximum Hold-up time 12 ms minimum at 110 VAC Overcurrent protection 400 See table MECHANICAL Dimensions 101x50.8x32mm Weight 190g Doc. No. PBC9 Rev.C 28-4-11 PM100 Series MEDICAL 3 7 - 6 4 W AT T S - A C / D C S I N G L E O U T P U T SELECTION TABLE OUTPUT MODEL(1) V1 PM100-10A PM100-12A PM100-13A PM100-13-1A PM100-14A PM100-15A PM100-17A PM100-18A 5V 12 V 15 V 18 V 24 V 28 V 36 V 48 V MIN. CURRENT MAX. CURRENT TOL. RIPPLE & NOISE (2) 0A 0A 0A 0A 0A 0A 0A 0A 20.00 A 8.34 A 6.70 A 5.56 A 4.20 A 3.58 A 2.78 A 2.10 A ±2% ±2% ±2% ±2% ±2% ±2% ±2% ±2% 150 mV 120 mV 150 mV 180 mV 240 mV 280 mV 360 mV 480 mV AVERAGE ACTIVE EFFICIENCY (TYPICAL) @ 115 / 230 VAC 100 W 100 W 100 W 100 W 100 W 100 W 100 W 100 W 85/88% 86/89% 86/89% 86/89% 87/90% 87/90% 87/89% 87/89% NOTES: 1. Safety approvals are for PCB form only. To order models with metallic L-bracket or box, change suffix “A” to “B” for L-bracket form, to “C” for enclosed form (see Outline Drawing of Cased Internal Switchers), e.g. PM100-14C. 2. Ripple and noise is maximum peak-to-peak voltage value measured at output within 20 MHz bandwidth, at rated line voltage and output load ranges, and with a 10 µF tantalum capacitor in parallel with a 0.1 µF ceramic capacitor across the output. OUTPUT POWER DERATING CURVE MECHANICAL SPECIFICATIONS NOTES: 1. 2. 3. 4. 5. 6. Dimensions shown in inches [mm] Tolerance 0.02 [0.5] maximum Connector P1: Molex header 09-65-2038 or equivalent, mating with Molex housing 09-50-1031 or equivalent. Connector P2: Molex header 09-65-2068 or equivalent, mating with Molex housing 09-50-1061 or equivalent. To ensure compliance with level B emissions, connect the three “* “ marked mounting holes with metallic standoffs to chassis. Weight: 190 grams (0.44 lbs.) approx. PIN CHART MODEL PIN PM100-10A PM100-13-1A PM100-17A PM100-12A PM100-14A PM100-18A PM100-13A PM100-15A Doc. No. PBC9 Rev.C 28-4-11 1 2 3 4 5 6 V1 Return V1 Return V1 Return +V1 +V1 +V1 Powering Progress – www.powerbox.com.au 401