PSC-481 Series
Type
Approved
OUTPUT
E205412
ENERGY
SAVER
Features:
•
•
•
•
•
•
•
•
•
•
Universal AC input (88-264V AC)
Installed on DIN rail TS-35 / 7.5 or 15
Built-in active PFC function, PF > 0.95
150% peak load capability
Protection: SCP, OLP, OVP, OTP
Two selectable peak load modes
Built-in DC OK (Open Collector Signal)
Built-in Remote ON / OFF function
3 years warranty
UL 508
Cat. No.
PSC-48124
PSC-48148
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER
24V
20A
0~20A
480W
30A
720W (3sec.) Two selectable peak load modes
48V
10A
0~10A
480W
15A
RIPPLE & NOISE (max)
240mVp-p
3 seconds or 20% duty cycle Max. The average output power should not exceed the rate power.
480mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
-5% ~ +5%
±1.0%
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
±0.5%
±1.0%
800ms, 100ms / 230VAC / 115VAC at full load
16ms / 230VAC; 16ms / 115VAC at full load
±0.5%
±1.0%
88 ~ 264VAC; 124 ~ 373VDC
Derating may apply in low input voltage. Please check the derating curve for more details.
PROTECTION
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
IMRUSH CURRENT (Typ.)
LEAKAGE CURRENT
47 ~ 63Hz
0.96 / 230VAC / 115VAC at full load
93%
5.0A / 115VAC; 2.5A / 230VAC
33A / 115VAC; 65A / 230VAC
< 1mA/ 240VAC
OVERLOAD
Hiccup mode: when the rated output power is within 105% ~ 150% for more than 3secs.
Constant current limit: > 150% rated power / short circuit
Auto-recovery: If O/P drop to 40% of the rated output voltage, PSU will shut down and auto-recover
5times (If fault condition remains after 5times recovery, PSU will shut down. User must re-power on to recover)
OVER VOLTAGE
29 ~ 33V
94%
56 ~ 65V
Protection type: Latch-off mode.
OVER TEMPERATURE
95 ±5°C (TSW: detect on heatsink of power diode)
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down
ENVIRONMENT
WORKING TEMP.
-20 ~ +70˚C (Refer to output load derating curve)
Installation clearance: 40mm from top, 20mm from the left and right side are recommended when
loaded permanently with full power. In case the adjacent device is a heat sorce, 15mm clearance is recomended.
SAFETY & EMC
WORKING HUMIDITY
STORAGE TEMP. / HUMIDITY
TEMP. COEFFICIENT
VIBRATION
20 ~ 95% RH non-condensing
-40 ~ +85˚C; 10 ~ 95% RH
±0.03% ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
UL 508 / EN 60950-1
I/P-O/P: 4242VDC, I/P-FG: 2121VDC, O/P-FG: 707VDC, O/P-DC OK: 707VDC
I/P-O/P, I/P-FG, O/P-FG: >100M Ohms / 500VDC / 25°C / 70% RH
EN 55022 (CISPR22), EN 61000-6-3
EN61000-3-2, -3-3
IEC 61000-4-2, 3, 4, 5, 6, 8, 11; EN 61000-6-1; EN 61204-3
The power supply is considered a component which will installed into a final equipment. The final equipment must be
re-confirmed that is still meets EMC directives.
OTHERS
DC OK RELAY CONTACT RATINGS (max)
DIMENSION
PACKING
60VDC / 0.3A, 30VDC / 1A, 30VAC / 0.5A resistive load
86.3x124.8x123.4 mm (WxHxD)
1.45kg; 8pcs / 12kg
All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
38
For the latest on Altech Power Supplies please visit www.altechcorp.com/power.
PowerSupplies_2013.QXD_PowerSupplies(v5).QXD 9/18/13 3:43 PM Page 39
PSC-481 Series
Type
Approved
E205412
ENERGY
SAVER
Mechanical Drawings
Unit : mm / inch
Terminal Pin No. Assignment (TB1)
Assignment
Pin NO.
1
2
3
FG
AC/L
AC/N
Te rmina l P in N o. A s s ignme nt ( T B 2)
Assignment
Pin NO.
1-3
4-6
7
8
9,10
86.3
DC+
DCINH+
INHDC OK Singal
123.4
1 2 3 4 5 6 7 8 910
TB2
DC OK
+
+V
ADJ.
Switch No. Assignment
DC ON
ON
OFF
124.8
Assignment
SW NO.
SW1
SW2
SW1
SW2
PEAK LOAD SETTING
REMOTE ON/OFF SETTING
1 2 3
TB1
Block Diagram
I/P
ACTIVE
iNRUSH
CURRENT
LIMITING
EMI FIL TER
&
RECTIFIERS
PFC
CIRCUIT
POWER
SWITCHING
RECTIFIERS
&
FIL TER
+V
-V
O.C.P .
FG
O.L.P .
AC
DETECTION
CIRCUIT
O.L.P .
DETECTION
CIRCUIT
PFC
CONTROL
PWM POWER
CONTROL
MICRO
CIRCUIT
O.V .P.
D C O K S inga l
O.T .P.
REMOTE
CONTROL
INH+
INH-
PEAK LOAD
CONTROL
DC OK Relay Contact
Contact Ratings(max.)
Isolation V oltage
CTR : MIN. 50% at IF = 5mA, V CE = 5V
Between input and output V iso = 3750V rms
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
39
PowerSupplies_2013.QXD_PowerSupplies(v5).QXD 9/18/13 3:43 PM Page 40
PSC-481 Series
E205412
Type
Approved
ENERGY
SAVER
Peak Load SW1 ON (Mode1) Default setting
I
T-peak
I-peak
T-peak presents while the unit is working within 110%~150%
Rating output power. See curve " B " for the variation in
T-peak between output current and holdup time. If T-peak is
more than the time setting in curve "B", the output current will
drop to the constant current limit (I-normal) that is 105% rating
power, meanwhile, I- normal and T-normal will be presenting.
See curve "A" for the timing back to I-Peak of T-normal and
this Mode can use for easy 2-stage battery charger.
I-normal
T-normal
0
T
Peak Load SW2 OFF (Mode2)
I
T-peak
I-peak
T-peak presents while the unit is working within 110%~150%
Rating output power. See curve " B " for the variation in
T-peak between output current and holdup time. If T-peak is
more than the time setting in curve "B", the output current will
be shut down for 3~4 sec, then auto-recovery.
0
3 ~ 4 sec
T- n ormal (Sec.)
T- peak
24
22
20
18
16
14
12
10
8
6
4
2
0
22
20
18
16
14
12
10
8
6
4
2
0
10 % 20 % 30 % 40 % 50 % 60 % 70 % 80 % 90 %
Load (%)
CURVE A
40
T
I- normal
(Sec.)
110% 115% 120% 125% 130% 135% 140% 145% 150% I- peak
Load (%)
CURVE B
For the latest on Altech Power Supplies please visit www.altechcorp.com/power.
PowerSupplies_2013.QXD_PowerSupplies(v5).QXD 9/18/13 3:43 PM Page 41
PSC-481 Series
Type
Approved
E205412
ENERGY
SAVER
Remote ON/OFF
SW
External Power Source
I = 6 ~ 20mA
123456
T he P S U c a n be turne d O N /O F F by us ing the
"R e mote C ontrol" func tion.
TB2
SW2
INH+(3 PIN)/ INH-(4 PIN)
Output Status
OFF
SW ON (>2.5V)
ENABLE
OFF
SW OFF (<0.8V)
DISABLE
ON
SW ON (>2.5V)
DISABLE
DISABLE
ON
SW OFF (<0.8V)
ENABLE
DC OK
+
+V
ADJ.
DC ON
(De fault S etting)
ON
SW1
SW2
OFF
Derating Curve
150
Load (%)
112.5
For typ. 3sec
100
60
Continuous
40
-10
0
10
20
30
40
50
60
70
(V ertical)
Ambient Temperature (°C) AC=230 / 1 15V AC
Output derating VS input coltage
100
Load (%)
90
80
70
60
50
40
ak
88
100
110
135
230 264VAC
Input Voltage(V)60Hz Ta=25 °C
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
41