pdf


POWERTRONIC PT-FIT 50/220-240 S Technical
Information
Edition: June 2011
For metal halide lamps 50 W
Subject to change
Technical data
Reference:
Lamp:
System wattage:
Lamp wattage:
Ballast efficiency:
Line voltage:
Voltage range:
Line frequency:
Line current:
Power factor :
Inrush current:
Max. no. of ECG @ circuit brakers 10 A (B Type):
Max. no. of ECG @ circuit brakers 16 A (B Type):
Max. no. of ECG @ circuit brakers 16 A (B Type) in
combination with EBN-OS:
Protective conductor current:
Operating frequency (50/60 Hz line frequency):
U-OUT:
Max. working voltage between LH and LL:
Max. working voltage between LL/LH and PE:
Ambient temperature ta:
Max. temperature at tc test point:
ECG life time:
Overheating protection:
Min. ECG reset time (by mains interrupt):
Wire cross section input / output line:
Wire stripping:
Max. wire length ECG/lamp:
Max. capacitance of wire ECG/lamp:
Max. ignition voltage:
Limited ignition time:
Dimensions (l x w x h):
Distance mounting holes (l1 x w1):
Weight:
Safety:
Radio interference suppression:
Harmonics of line current:
Immunity:
VDE-sign (safety):
VDE-EMC-sign:
PT-FIT 50/220-240 S
HCI 50 W and other similar commercially
available lamps
54.5 W  1.5 W
50 W  1.5 W
~ 92 %
220 – 240 VAC
198 – 264 VAC
50/60 Hz
0.24 Aeff @ 230 VAC
> 0.95
max. 45 A / 250 µs @ 50%
7
13
32
0.3 mArms
200/240 Hz
250 V
250 V
250 V
-15 °C to +60 °C
+85 °C
30000 h (@ tc max.) 1)
Power reduction and shutdown at T at the tc point
> 85 °C
0.5 sec
0.5 – 1.5 mm² without ferrule
0.5 – 1.0 mm2 with ferrule
8.5 – 9.5 mm
1.50 m
120 pF
4.5 kV
20 min
110 mm x 75 mm x 30 mm
99 mm x 64 mm
≈ 257 g
EN 61347-2-12 / IEC 61347-2-12
EN 55015 / CISPR 15
EN 61000-3-2 / IEC 61000-3-2
EN 61547 / IEC 61547
40020649
40027499
Approval marks:
1)
with max. 10% failure rate at max. tc
2011-11-25
page 1 of 3

POWERTRONIC PT-FIT 50/220-240 S Technical
Information
For metal halide lamps 50 W
Edition: June 2011
Subject to change
Geometry
Product number:
Reference
PT-FIT 50/220-240 S
2011-11-25
EAN 10
4008321 648693
page 2 of 3
EAN 40
4008321 648709

POWERTRONIC PT-FIT 50/220-240 S Technical
Information
Edition: June 2011
For metal halide lamps 50 W
Subject to change
Thermal characteristics
Ballast losses and lamp heat radiation can lead to heat accumulation in a complete closed case. Therefore
it is necessary to ensure, that the temperature at the measuring point tc does not exceed the maximum
value.
Attention!
For safety reasons disconnect the device before replacing the lamp!
Any conductive material must have a minimum distance of 4mm to the front of the terminal block.
Wiring diagram
Installation by qualified electricians only.
Terminals for protective earth not suitable for any through connection.
PE
Setup for built-in or integral ECG
Mains
ECG
PT-FIT 50/220-240 S
2011-11-25
page 3 of 3