© Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for absolute pressure (from gauge pressure series) ■ Technical specifications SITRANS P DS III series for absolute pressure (from the gauge pressure series) HART PROFIBUS PA and FOUNDATION Fieldbus Input Measured variable Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure Absolute pressure Span (min. ... max.) Max. perm. test pressure Nominal measuring range Max. perm. test pressure 8.3 ... 250 mbar a (0.12 ... 3.62 psia) 6 bar a (87 psia) 250 mbar a (3.6 psia) 6 bar a (87 psia) 43 ... 1300 mbar a (0.62 ... 18.85 psi a) 10 bar a (145 psia) 1300 mbar a (18.9 psi a) 10 bar a (145 psia) 160 ... 5000 mbar a (2.32 ... 72.5 psia) 30 bar a (435 psia) 5 bar a (72.5 psia) 30 bar a (435 psia) 1 ... 30 bar a (14.5 ... 435 psia) 100 bar a (1450 psia) 30 bar a (435 psia) 100 bar a (1450 psia) Lower measuring limit • Measuring cell with silicone oil filling 0 mbar a (0 psia) Upper measuring limit 100 % of max. span Output Output signal 4 ... 20 mA Digital PROFIBUS PA and FOUNDATION Fieldbus signal • Lower limit (infinitely adjustable) 3.55 mA, factory preset to 3.84 mA - • Upper limit (infinitely adjustable) 23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA - • Without HART RB (UH - 10.5 V)/0.023 A in , UH: Power supply in V - • With HART RB = 230 ... 500 (SIMATIC PDM) or RB = 230 ... 1100 (HART Communicator) - Physical bus - IEC 61158-2 Load Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. Protection against polarity reversal Electrical damping (step width 0.1 s) Set to 2 s (0 ... 100 s) Measuring accuracy Acc. to IEC 60770-1 Reference conditions (All error data refer always refer to the set span) Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 °C (77 °F) Span ratio r = max. span/set span Nominal measuring range ratio r = nominal measuring range/set measuring range Error in measurement at limit setting incl. hysteresis and reproducibility • Linear characteristic - r 10 0.1 % 0.1 % - 10 < r 30 0.2 % 0.2 % (0.1 r) %/year (0.1 r) %/year • at -10 ... +60 °C (14 ... 140 °F) (0.1 r + 0.2) %1) (0.1 r + 0.2) %1) • at -40 ... -10 °C and 60 ... 85 °C (-40 ... +14 °F and 140 ... 185 °F) (0.1 r + 0.15) %/10 K (0.1 r + 0.15) %/10 K Measured Value Resolution - 3 10-5 of nominal measuring range Long-term stability (temperature change ± 30 °C (± 54 °F)) Influence of ambient temperature Siemens FI 01 · 2015 US Edition 1/119 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for absolute pressure (from gauge pressure series) SITRANS P DS III series for absolute pressure (from the gauge pressure series) HART PROFIBUS PA and FOUNDATION Fieldbus Rated conditions Degree of protection (to IEC 60529) IP66 (optional IP66/IP68), NEMA 4X Temperature of medium • Measuring cell with silicone oil filling -40 ... +100 °C (-40 ... +212 °F) -20 ... +100 °C (-4 ... +212 °F) with 30 bar a measuring cell • Measuring cell with inert filling liquid -20 ... +100 °C (-4 ... +212 °F) • In conjunction with dust explosion protection -20 ... +60 °C (-4 ... +140 °F) Ambient conditions • Ambient temperature - Transmitter (with 4-wire connection, observe temperature values of supplementary 4-wire electronics) -40 ... +85 °C (-40 ... +185 °F) - Display readable -30 ... +85 °C (-22 ... +185 °F) • Storage temperature -50 ... +85 °C (-58 ... +185 °F) • Climatic class - Condensation Relative humidity 0 ... 100 % Condensation permissible, suitable for use in the tropics • Electromagnetic Compatibility - Emitted interference and interference immunity Acc. to IEC 61326 and NAMUR NE 21 Design 1.5 kg ( 3.3 lb) Weight (without options) Enclosure material Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408 Wetted parts materials • Connection shank Stainless steel, mat. no. 1.4404/316L or Hastelloy C4, mat. no. 2.4610 Stainless steel, mat. no. 1.4404/316L • Oval flange • Seal diaphragm Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819 Measuring cell filling Silicone oil or inert filling liquid (maximum value with oxygen measurement pressure 100 bar (1450 psi) at 60 °C (140 °F)) Process connection Connection shank G½B to EN 837-1, female thread ½ -14 NPT or oval flange (PN 160 (MAWP 2320 psia)) to DIN 19213 with mounting thread M10 or 7/16-20 UNF to IEC 61518 Material of mounting bracket • Steel Sheet-steel, Mat. No. 1.0330, chrome-plated Sheet stainless steel, mat. no. 1.4301 (SS 304) • Stainless steel Supplied through bus Power supply UH Terminal voltage on transmitter 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsically-safe mode - Separate 24 V power supply necessary - No • Not Ex - 9 ... 32 V • With intrinsically-safe operation - 9 ... 24 V • Basic current (max.) - 12.5 mA • Start-up current basic current - Yes • Max. current in event of fault - 15.5 mA Fault disconnection electronics (FDE) available - Yes Bus voltage Current consumption 1/120 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for absolute pressure (from gauge pressure series) SITRANS P DS III series for absolute pressure (from the gauge pressure series) HART PROFIBUS PA and FOUNDATION Fieldbus Certificates and approvals Classification according to PED 97/23/EC For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) Explosion protection • Intrinsic safety "i" PTB 13 ATEX 2007 X Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb - Marking - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +70 °C (-40 ... +158 °F) temperature class T5; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 - Connection To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF L i = 7 H, Ci = 1.1 nF • Explosion-proof "d" PTB 99 ATEX 1160 - Marking Ex II 1/2 G Ex d IIC T4/T6 Gb - Permissible ambient temperature - Connection -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 To circuits with values: UH = 10.5 ... 45 V DC • Dust explosion protection for zone 20 PTB 01 ATEX 2055 - Marking Ex II 1 D IP65 T 120 °C Ex II 1/2 D IP65 T 120 °C - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) - Max. surface temperature 120 °C (248 °F) - Connection To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF L i = 7 H, Ci = 1.1 nF PTB 01 ATEX 2055 • Dust explosion protection for zone 21/22 - Marking - Connection Ex II 2 D IP65 T 120 °C To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W • Type of protection "n" (zone 2) To circuits with values: UH = 9 ... 32 V DC; Pmax = 1 W PTB 13 ATEX 2007 X Ex II 2/3 G Ex nA II T4/T5/T6 Gc Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc - Marking - Connection (Ex nA) Um = 45 V Um = 32 V - Connection (Ex ic) To circuits with values: Ui = 45 V FISCO supply unit ic: Uo = 17.5 V, Io = 570 mA Linear barrier: Uo = 32 V, Io = 132 mA, Po = 1 W - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF • Explosion protection acc. to FM - Identification (XP/DIP) or (IS); (NI) • Explosion protection to CSA - Identification (XP/DIP) or (IS) 1) To circuits with values: UH = 9 ... 32 V DC L i = 7 H, Ci = 1.1 nF Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 1153651 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.08. r + 0.16) % / 28 °C (50 °F). Siemens FI 01 · 2015 US Edition 1/121 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for absolute pressure (from gauge pressure series) HART communication HART 230 ... 1100 Protocol HART Version 5.x Software for computer SIMATIC PDM PROFIBUS PA communication Simultaneous communication with master class 2 (max.) 4 The address can be set using Configuration tool or local operation (standard setting address 126) Cyclic data usage • Output byte 5 (one measured value) or 10 (two measured values) • Input byte 0, 1, or 2 (register operating mode and reset function for metering) Internal preprocessing FOUNDATION Fieldbus communication Function blocks 3 function blocks analog input, 1 function block PID • Analog input - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic - Electrical damping, adjustable 0 ... 100 s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic for flow measurement Yes Device profile PROFIBUS PA Profile for Process Control Devices Version 3.0, class B • PID Standard FOUNDATION Fieldbus function block • Physical block 1 resource block Function blocks 2 Transducer blocks - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic 1 transducer block Pressure with calibration, 1 transducer block LCD • Pressure transducer block - Electrical damping, adjustable 0 to 100 s - Simulation function Input /Output - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively • Register (totalizer) Can be reset, preset, optional direction of counting, simulation function of register output • Analog input - Failure mode parameterizable (summation with last good value, continuous summation, summation with incorrect value) - Limit monitoring One upper and lower warning limit and one alarm limit respectively • Physical block 1 Transducer blocks 2 • Pressure transducer block - Can be calibrated by applying two pressures Yes - Monitoring of sensor limits Yes - Specification of a container characteristic with Max. 30 nodes - Square-rooted characteristic for flow measurement Yes - Gradual volume suppression and implementation point of square-root extraction Parameterizable - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function 1/122 Siemens FI 01 · 2015 US Edition - Can be calibrated by applying two pressures Yes - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Constant value or over parameterizable ramp function © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for absolute pressure (from gauge pressure series) Selection and Ordering data Article No. Selection and Ordering data Article No. Pressure transmitters for absolute pressure from gauge pressure series SITRANS P DS III with HART 7MF 4 2 3 3 - Pressure transmitters for absolute pressure from gauge pressure series SITRANS P DS III with HART 7MF 4 2 3 3 - 77777 - 7777 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Silicone oil Inert liquid1) Measuring cell cleaning normal grease-free to cleanliness level 2 Measuring span (min. ... max.) 8.3 ... 250 mbar a (0.12 ... 3.62 psia) 43 ... 1300 mbar a (0.62 ... 18.85 psia) 0.16 ... 5 bar a (2.32 ... 72.5 psia) 1 ... 30 bar a (14.5 ... 435 psia) Display • Without display • Without visible display (display concealed, setting: mA) • With visible display (setting: mA) • with customer-specific display (setting as specified, Order code "Y21" or "Y22" required) 1 3 Process connection • Connection shank G½B to EN 837-1 • Female thread ½-14 NPT • Stainless steel oval flange with process connection (Oval flange has no female thread) - Mounting thread 7/16-20 UNF to EN 61518 - Mounting thread M10 to DIN 19213 - Mounting thread M12 to DIN 19213 • Male thread M20 x 1.5 • Male thread ½ -14 NPT Non-wetted parts materials • Housing made of die-cast aluminium • Housing stainless steel precision casting7) Version • Standard versions • International version, English label inscriptions, documentation in 5 languages on CD (no Order code selectable) Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" - "Explosion-proof (Ex d)"8) - "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"9) - "Ex nA/ic (Zone 2)"10) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (Ex ia+ Ex d + Zone 1D/2D)"9)11) • FM + CSA intrinsic safe (is) • FM + CSA (is + ep) + Ex ia + Ex d (ATEX)11) • With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)"8) Electrical connection/cable entry • Screwed gland Pg 13.512) • Screwed gland M20x1.5 • Screwed gland ½-14 NPT • Han 7D plug (plastic housing) incl. mating connector12) • M12 connectors (stainless steel) 13) 14) 0 1 6 7 Power supply units see Chap. 7 "Supplementary Components". D F G H Included in delivery of the device: • Brief instructions (Leporello) • CD-ROM with detailed documentation Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Version for diaphragm seal2) 3) 4) 5) 6) 77777 - 7777 1) For oxygen application, add Order code E10. 2) Version 7MF4233-1DY... only up to max. span 200 mbar a (80 inH2O a). 3) When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here.If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 4) If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 5) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF423.-..Y..-.... and 7MF4900-1...-.B 6) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 7) Not in conjunction with Electrical connection "Screwed gland Pg 13.5" and "Han7D plug". 8) Without cable gland, with blanking plug. 9) With enclosed cable gland Ex ia and blanking plug. A B C Y 0 1 2 3 4 5 6 0 3 10) Configurations 1 2 with HAN and M12 connectors are only available in Ex ic. 11) Only in connection with IP65. 12) Only in connection with Ex apporval A, B or E. 13) Only in connection with Ex apporval A, B, E or F. 14) M12 delivered without cable socket A B D P E R F S NC A B C D F Siemens FI 01 · 2015 US Edition 1/123 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for absolute pressure (from gauge pressure series) Selection and Ordering data Article No. Selection and Ordering data Pressure transmitters for absolute pressure from gauge pressure series SITRANS P DS III with PROFIBUS PA (PA) 7MF 4 2 3 4 - SITRANS P DS III with PROFIBUS PA (PA) SITRANS P DS III with FOUNDATION Fieldbus (FF) 7MF 4 2 3 5 - SITRANS P DS III with FOUNDATION Fieldbus (FF) Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Silicone oil Inert liquid1) Measuring cell cleaning normal grease-free to cleanliness level 2 Nominal measuring range 250 mbar a (3.62 psia) 1300 mbar a (18.85 psia) 5 bar a (72.5 psia) 30 bar a (435 psia) 77777 - 7777 Process connection • Connection shank G½B to EN 837-1 • Female thread ½-14 NPT • Stainless steel oval flange with process connection (Oval flange has no female thread) - Mounting thread 7/16-20 UNF to IEC 61518 - Mounting thread M10 to DIN 19213 - Mounting thread M12 to DIN 19213 • Male thread M20 x 1.5 • Male thread ½ -14 NPT Non-wetted parts materials • Housing made of die-cast aluminium • Housing stainless steel precision casting Version • Standard versions • International version, English label inscriptions, documentation in 5 languages on CD (no Order code selectable) Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" - "Explosion-proof (Ex d)"7) - "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"8) - "Ex nA/ic (Zone 2)" 9) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (Ex ia + Ex d + Zone 1D/2D)"8) 10) (not for DS III FF) • FM + CSA intrinsic safe (is) • FM + CSA (is + ep) + Ex ia + Ex d (ATEX)10) • With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)"7) Electrical connection/cable entry • Screwed gland M20 x 1.5 • Screwed gland ½-14 NPT • M12 connectors (stainless steel) 11) 12) 1/124 Siemens FI 01 · 2015 US Edition 7MF 4 2 3 4 7MF 4 2 3 5 77777 - 7777 Display • Without display • Without visible display (display concealed, setting: bar) • With visible display (setting: bar) • with customer-specific display (setting as specified, Order code "Y21" or "Y22" required) 1 3 D F G H 0 1 6 7 Included in delivery of the device: • Brief instructions (Leporello) • CD-ROM with detailed documentation Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Version as diaphragm seal 2) 3) 4) 5) 6) Article No. Pressure transmitters for absolute pressure from gauge pressure series A B C Y 0 1 2 3 4 5 6 0 3 1 2 A B D P E R F S NC B C F 1) For oxygen application, add Order code E10. 2) Version 7MF4233-1DY... only up to max. span 200 mbar a (2.9 psia). 3) When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 4) If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 5) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF423.-..Y..-.... and 7MF4900-1...-.B 6) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 7) Without cable gland, with blanking plug. 8) With enclosed cable gland Ex ia and blanking plug. 9) Configurations with HAN and M12 connectors are only available in Ex ic. 10) Only in connection with IP65. 11) Only in connection with Ex approval A, B, E or F. 12) M12 delivered without cable socket. © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for absolute pressure (from gauge pressure series) Selection and Ordering data Order code Further designs Selection and Ordering data HART PA FF Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Add "-Z" to Article No. and specify Order code. Pressure transmitter with mounting bracket (1x fixing angle, 2 x nut, 2 x Uwasher or 1 x bracket, 2 x nut, 2 x Uwasher) made of: • Steel • Stainless steel E01 A01 A02 Use in or on zone 1D/2D (only together with type of protection "Intrinsic safety" (transmitter 7MF4...-.....-.B.. Ex ia)“ and IP65) E10 Plug • Han 7D (metal) • Han 8D (instead of Han 7D) • Angled • Han 8D (metal) A30 A31 A32 A33 Oxygen application (In the case of oxygen measurement and inert liquid max. 100 bar (1450 psi) at 60°C (140 °F)) Export approval Korea E11 CRN approval Canada (Canadian Registration Number) E22 A50 Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.B..) E254) "Flameproof" explosion protection according to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.D..) E264) Cable sockets for M12 connectors (metal (CuZn)) Rating plate inscription (instead of German) • English • French • Spanish • Italian • Cyrillic (russian) B11 B12 B13 B14 B16 B21 Explosion-proof "Intrinsic safety" (Ex ia + Ex d) to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.P..) E284) English rating plate Pressure units in inH20 and/or psi Quality inspection certificate (Five-step factory calibration) to IEC 60770-21) C11 Ex Approval IEC Ex (Ex ia) (only for transmitter 7MF4...-.....-.B..) E454) Inspection certificate2) Acc. to EN 10204-3.1 C12 Ex Approval IEC Ex (Ex d) (only for transmitter 7MF4...-.....-.D..) E464) Factory certificate Acc. to EN 10204-2.2 C14 E554) Functional safety (SIL2) Devices suitable for use according to IEC 61508 and IEC 61511. Includes SIL conformity declaration C20 Explosion-proof "Intrinsic safety" to NEPSI (China) (only for transmitter 7MF4...-.....-.B..) Explosion protection "Explosion-proof" to NEPSI (China) (only for transmitter 7MF4...-.....-.D..) E564) Functional safety (PROFIsafe) Certificate and PROFIsafe protocol C213) E574) Functional safety (SIL2/3) Devices suitable for use according to IEC 61508 and IEC 61511. Includes SIL conformity declaration C23 Explosion-proof "Zone 2" to NEPSI (China) (only for transmitter 7MF4...-.....-.E..) E584) Device passport Russia C99 Ex protection „Ex ia“, „Ex d“ and „Zone 2“ to NEPSI (China) (only for transmitter 7MF4...-.....-.R..) "Intrinsic safety" and "Explosion-proof" explosion protection acc. to Kosha (Korea) E704) Two coats of lacquer on casing and cover (PU on epoxy) G10 Transient protector 6 kV (lightning protection) J01 Oval flange NAM (ASTAVA) J06 (For price request please contact the technical support www.siemens.com/automation/supportrequest) (only for transmitter 7MF4...-.....-.[B, D]..-Z + E11) Setting of upper limit of output signal to 22.0 mA D05 Manufacturer's declaration acc. to NACE (MR 0103-2012 and MR 0175-2009) D07 Degree of protection IP66/IP68 (only for M20 x 1.5 and ½-14 NPT) D12 Supplied with oval flange (1 item), PTFE packing and screws in thread of oval flange D37 Capri cable gland 4F CrNi and clamping device (848699 + 810634) included D59 1) When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 2) If the acceptance test certificate 3.1 is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 3) Profisafe transmitters can only be operated with the S7 F Systems V6.1 configuration software in combination with S7-400H 4) Option does not include ATEX approval, but instead includes only the country-specific approval. Siemens FI 01 · 2015 US Edition 1/125 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for absolute pressure (from gauge pressure series) Selection and Ordering data Order code Additional data HART PA FF Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Specify in plain text (max. 5 characters): Y01: ... up to ... mbar a, bar a, kPaabs, MPaabs, psia2) Y01 1) Stainless steel tag plate and entry in device variable (measuring point description) Max. 16 characters, specify in plain text: Y15: ........................................... Y15 Measuring point text (entry in device variable) Max. 27 characters, specify in plain text: Y16: ........................................... Y16 Entry of HART address (TAG) Max. 8 characters, specify in plain text: Y17: ........................................... Y17 Setting of pressure indication in pressure units Specify in plain text (standard setting: bar): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, Torr, ATM or % *) ref. temperature 20 °C Y21 Setting of pressure indication in non-pressure units3) Specify in plain text: Y22: ..... up to ..... l/min, m3/h, m, USgpm, ... (specification of measuring range in pressure units "Y01" is essential, unit with max. 5 characters) Y22 + Y01 Preset bus address possible between 1 and 126 Specify in plain text: Y25: ..................... Y25 Damping adjustment in seconds (0 ... 100 s) Y30 Factory mounting of valve manifolds, see accessories. Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 and D05 can be factory preset = available 1) Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are calculated in the same way as for HART devices. 2) Only absolute pressure units selectable. Negative pressure values not permitted. 3) Preset values can only be changed over SIMATIC PDM. 1/126 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for absolute pressure (from gauge pressure series) 53 (2.1) 54 (2.13) 27 (1.1) Ø80 (3.15) 2 17 (0.67) 29 (1.14) 4) 5 84 (3.31) 6 3 4 3 7 9 72 (2.8) 8 120 (4.72) 68 (2.68) SW 36 approx. 40 (1.6) 171 (6.7) approx. 96 (3.78) 176 (6.93) 237 (9.33) 143 (5.6) 74 (2.9) 50 (1.97) 117 (4.61) 15 (0.6) 1 24 (0.94) ■ Dimensional drawings Space for rotation of housing min. 90 (3.54) 5) 123 (4.84) Ø50 ... 60 (1.97 ... 2.36) 105 (4.13) Electronic side, digital display (longer overall length for cover with window)1) 5 Protective cover over keys 6 Blanking plug 2 Terminal side1) 7 3 Electrical connection: Screwed gland Pg 13,5 (adapter)(Adapter)2) 3), Screwed gland M20 x 1,5 or Screwed gland ½-14 NPT or Han 7D/Han 8D2) 3) plug Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 8 Process connection: Connection shank G½B or Oval flange 9 Mounting bracket (option) 1 4 Harting adapter 1) 2) 3) 4) 5) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing Not with type of protection "Explosion-proof enclosure" Not with type of protection "FM + CSA" [IS + XP]" For Pg 13,5 with adapter approx. 45 mm (1.77 inch) Minimum distance for rotating SITRANS P DS III pressure transmitters for absolute pressure, from the pressure series, dimensions in mm (inch) Siemens FI 01 · 2015 US Edition 1/127 1