DS III - 7MF4633,7MF4634,7MF4635,7MF4812 pressure transmitter for level catalog specifications

© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for level
■ Technical specifications
SITRANS P DS III for level
HART
PROFIBUS PA or FOUNDATION Fieldbus
Input
Measured variable
Level
Spans (infinitely adjustable) or nominal measuring Span (min. ... max.)
range and max. permissible operating pressure
Maximum operating
pressure
Nominal measuring
range
Maximum operating
pressure
25 ... 250 mbar
(10 ... 100 inH2O)
See "Mounting flange"
250 mbar
(100 inH2O)
See "Mounting flange"
25 ... 600 mbar
(10 ... 240 inH2O)
See "Mounting flange"
600 mbar
(240 inH2O)
See "Mounting flange"
53 ... 1600 mbar
(21 ... 642 inH2O)
See "Mounting flange"
1600 mbar
(642 inH2O)
See "Mounting flange"
160 ... 5000 mbar
(64 ... 2000 inH2O)
See "Mounting flange"
5 bar
(2000 inH2O)
See "Mounting flange"
Lower measuring limit
• Measuring cell with silicone oil filling
-100 % of max. span or 500 mbar a (7.25 psia)
Also available as vacuum-resistant remote seal: 30 mbar a (0.44 psi a)
Upper measuring limit
100 % of max. span
100 % of the max. nominal measuring range
Output signal
4 ... 20 mA
• Lower limit (infinitely adjustable)
• Upper limit (infinitely adjustable)
3.55 mA, factory preset to 3.84 mA
23 mA, factory preset to 20.5 mA or optionally
set to 22.0 mA
Digital PROFIBUS PA and
FOUNDATION Fieldbus signal
-
Output
Load
• Without HART
RB  (UH - 10.5 V)/0.023 A in ,
UH: Power supply in V
RB = 230 ... 500  (SIMATIC PDM) or
RB = 230 ... 1100  (HART Communicator)
-
Physical bus
-
IEC 61158-2
Protection against polarity reversal
Protected against short-circuit and polarity reversal. Each connection against the other with max.
supply voltage.
• With HART
Set to 2 s (0 ... 100 s)
Electrical damping (step width 0.1 s)
Acc. to IEC 60770-1
Measuring accuracy
Reference conditions
(All error data refer always refer to the set span)
-
Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm,
silicone oil filling, room temperature 25 °C (77 °F)
Span ratio r = max. span/set span)
Nominal measuring range ratio r = nominal
measuring range/set measuring range
Error in measurement at limit setting incl.
hysteresis and reproducibility
• Linear characteristic
- r  10
 0.15 %
 0.15 %
- 10 < r  30
 0.3 %
 0.3 %
- 30 < r  100
 (0.0075  r + 0.075) %
 (0.0075  r + 0.075) %
 (0.25  r)% every 5 years
static pressure max. 70 bar (1015 psi)
 (0.25  r)% every 5 years
static pressure max. 70 bar (1015 psi)
- 250 mbar- (100 inH2O)-measuring cell
 (0.5  r + 0.2) %1) 4)
 (0.5  r + 0.2) %1) 4)
- 600 mbar- (240 inH2O)-measuring cell
 (0.3  r + 0.2)
 (0.3  r + 0.2) %2) 4)
Long-term stability
(temperature change ± 30 °C (± 54 °F))
Influence of ambient temperature
• at -10 ... +60 °C (14 ... 140 °F)
%2) 4)
- 1600 and 5000 mbar- (642 and 2000 inH2O)-  (0.25  r + 0.2)
measuring cell
%3) 4)
 (0.25  r + 0.2) %3) 4)
• at -40 ... -10 °C and 60 ... 85 °C
(-40 ... +14 °F and 140 ... 185 °F)
- 250 mbar- (100 inH2O)-measuring cell
 (0.25  r + 0.15) %/10 K
doubled values at 10 < r  30
 (0.25  r + 0.15) %/10 K
doubled values at 10 < r  30
- 600 mbar- (240 inH2O)-measuring cell
 (0.15  r + 0.15) %/10 K
doubled values at 10 < r  30
 (0.15  r + 0.15) %/10 K
doubled values at 10 < r  30
- 1600 and 5000 mbar- (642 and 2000 inH2O)-  (0.12  r + 0.15) %/10 K
measuring cell
double values at 10 < r  30
1/152
Siemens FI 01 · 2015 US Edition
 (0.12  r + 0.15) %/10 K
double values at 10 < r  30
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for level
SITRANS P DS III for level
HART
PROFIBUS PA or FOUNDATION Fieldbus
- 250 mbar- (100 inH2O)-measuring cell
 (0.3  r) % per nominal pressure
 (0.3  r) % per nominal pressure
- 600 mbar- (240 inH2O)-measuring cell
 (0.15  r) % per nominal pressure
 (0.15  r) % per nominal pressure
Influence of static pressure
• on the zero point
- 1600 and 5000 mbar- (642 and 2000 inH2O)-  (0.1  r) % per nominal pressure
measuring cell
 (0.1  r) % per nominal pressure
• on the span
 (0.1  r) % per nominal pressure
 (0.1  r) % per nominal pressure
Measured Value Resolution
-
3  10-5 of nominal measuring range
Rated conditions
Degree of protection to IEC 60529
IP66 (optional IP66/IP68), NEMA 4X
Note: Always take into account assignment of max. permissible operating temperature to max.
permissible operating pressure of the respective flange connection!
Temperature of medium
-40 ... +1005) °C (-40 ... +2125) °F)
• Measuring cell with silicone oil filling
- High-pressure side
pabs  1 bar: -40 ... +175 °C (-40 ... +347 °F)
pabs < 1 bar: -40 ... +80 °C (-40 ... +176 °F)
- Low-pressure side
-40 ... +100 °C (-40 ... +212 °F)
-20 ... +60 °C (-4 ... +140 °F) in conjunction with dust explosion protection
Ambient conditions
• Ambient temperature
- Transmitter
(with 4-wire connection, observe temperature
values of supplementary 4-wire electronics)
-40 ... +85 °C (-40 ... +185 °F)
- -Display readable
-30 ... +85 °C (-22 ... +185 °F)
• Storage temperature
-50 ... +85 °C (-58 ... +185 °F)
• Climatic class
- Condensation
Relative humidity 0 ... 100 %, condensation permissible, suitable for use in the tropics
• Electromagnetic Compatibility
- Emitted interference and interference immunity
Acc. to IEC 61326 and NAMUR NE 21
Design
Weight (without options)
• To EN (pressure transmitter with mounting
flange, without tube)
 11 ... 13 kg ( 24.2 ... 28.7 (lb)
• To ASME (pressure transmitter with mounting
flange, without tube)
 11 ... 18 kg ( 24.2 ... 39.7 lb)
Low-copper die-cast aluminum, GD-AlSi12 or stainless steel precision casting, mat. no. 1.4408
Enclosure material
Wetted parts materials
High-pressure side
• Seal diaphragm of mounting flange
Stainless steel, mat. no. 1.4404/316L, Monel, mat. no. 2.4360, Hastelloy B2, mat. no. 2.4617,
Hastelloy C276, mat. no. 2.4819, Hastelloy C4, mat. no. 2.4610, tantalum, PTFE, ETCFE,
stainless steel Duplex, mat. no. 1.4462
Measuring cell filling
Silicone oil
Process connection
• High-pressure side
Flange to EN and ASME
• Low-pressure side
Female thread ¼-18 NPT and flange connection with mounting thread M10 to DIN 19213 or
7/ -20 UNF to EN 61518
16
Supplied through bus
Power supply UH
Terminal voltage on transmitter
10.5 ... 45 V DC
10.5 ... 30 V DC in intrinsically-safe mode
-
Separate 24 V power supply necessary
-
No
• Not Ex
-
9 ... 32 V
• With intrinsically-safe operation
-
9 ... 24 V
Bus voltage
Current consumption
• Basic current (max.)
-
12.5 mA
• Start-up current  basic current
-
Yes
• Max. current in event of fault
-
15.5 mA
Fault disconnection electronics (FDE) available
-
Yes
Siemens FI 01 · 2015 US Edition
1/153
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for level
SITRANS P DS III for level
HART
PROFIBUS PA or FOUNDATION Fieldbus
Certificates and approvals
Classification according to PED 97/23/EC
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3,
paragraph 3 (sound engineering practice)
Explosion protection
• Intrinsic safety "i"
PTB 13 ATEX 2007 X
Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb
- Marking
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +70 °C (-40 ... +158 °F) temperature class T5;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
- Connection
To certified intrinsically-safe circuits with peak
values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW; Ri = 300 
FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier:
Uo = 24 V, Io = 250 mA, Po = 1.2 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
• Explosion-proof "d"
PTB 99 ATEX 1160
- Marking
Ex II 1/2 G Ex d IIC T4/T6 Gb
- Permissible ambient temperature
- Connection
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
To circuits with values: UH = 10.5 ... 45 V DC
• Dust explosion protection for zone 20
To circuits with values: UH = 9 ... 32 V DC
PTB 01 ATEX 2055
- Marking
Ex II 1 D IP65 T 120 °C
Ex II 1/2 D IP65 T 120 °C
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
- Max. surface temperature
120 °C (248 °F)
- Connection
To certified intrinsically-safe circuits with peak
values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW, Ri = 300 
FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier:
Uo = 24 V, Io = 250 mA, Po = 1.2 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
L i = 7 H, Ci = 1.1 nF
PTB 01 ATEX 2055
• Dust explosion protection for zone 21/22
- Marking
Ex II 2 D IP65 T 120 °C
- Connection
To circuits with values: UH = 10.5 ... 45 V DC;
Pmax = 1.2 W
• Type of protection "n" (zone 2)
To circuits with values: UH = 9 ... 32 V DC;
Pmax = 1 W
PTB 13 ATEX 2007 X
Ex II 2/3 G Ex nA II T4/T5/T6 Gc
Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc
- Marking
- Connection (Ex nA)
Um = 45 V
Um = 32 V
- Connection (Ex ic)
To circuits with values:
Ui = 45 V
FISCO supply unit ic:
Uo = 17.5 V, Io = 570 mA
Linear barrier:
Uo = 32 V, Io = 132 mA, Po = 1 W
- Effective internal inductance/capacitance
L i = 0.4 mH, Ci = 6 nF
• Explosion protection acc. to FM
- Identification (XP/DIP) or (IS); (NI)
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6;
CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III
• Explosion protection to CSA
- Identification (XP/DIP) or (IS)
L i = 7 H, Ci = 1.1 nF
Certificate of Compliance 3008490
Certificate of Compliance 1153651
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD
T4...T6; CL II, DIV 2, GP FG; CL III
1)
Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.4 · r + 0.16) % / 28 °C (50 °F).
2)
Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.24 · r + 0.16) % / 28 °C (50 °F).
3)
Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.2 · r + 0.16) % / 28 °C (50 °F).
4)
0.32 instead of 0.16 at 10 < r < 30
5)
This value may be increased if the process connection is sufficiently insulated.
1/154
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for level
HART communication
HART
230 ... 1100 
Protocol
HART Version 5.x
Software for computer
SIMATIC PDM
PROFIBUS PA communication
Simultaneous communication with
master class 2 (max.)
4
The address can be set using
Configuration tool or local
operation (standard setting
address 126)
Cyclic data usage
• Output byte
5 (one measured value) or
10 (two measured values)
• Input byte
0, 1, or 2 (register operating
mode and reset function for
metering)
Internal preprocessing
FOUNDATION Fieldbus
communication
Function blocks
3 function blocks analog input,
1 function block PID
• Analog input
- Adaptation to customer-specific process variables
Yes, linearly rising or falling
characteristic
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Output/input (can be locked
within the device with a bridge)
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
- Square-rooted characteristic
for flow measurement
Yes
Device profile
PROFIBUS PA Profile for Process Control Devices Version
3.0, class B
• PID
Standard FOUNDATION Fieldbus function block
• Physical block
1 resource block
Function blocks
2
Transducer blocks
- Adaptation to customer-specific process variables
Yes, linearly rising or falling
characteristic
1 transducer block Pressure with
calibration, 1 transducer block
LCD
• Pressure transducer block
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Input/Output
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
• Analog input
• Register (totalizer)
- Failure mode
- Limit monitoring
Can be reset, preset, optional
direction of counting, simulation
function of register output
parameterizable (summation
with last good value, continuous
summation, summation with
incorrect value)
One upper and lower warning
limit and one alarm limit respectively
• Physical block
1
Transducer blocks
2
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Simulation function: Measured
pressure value, sensor temperature and electronics temperature
Constant value or over parameterizable ramp function
Mounting flange
Nominal diameter
Nominal pressure
• Acc. to EN 1092-1
- DN 80
PN 40
- DN100
PN16, PN40
• To ASME B16.5
- 3 inch
class 150, class 300
- 4 inch
class 150, class 300
• Pressure transducer block
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Specification of a container
characteristic with
Max. 30 nodes
- Square-rooted characteristic
for flow measurement
Yes
- Gradual volume suppression
and implementation point of
square-root extraction
Parameterizable
- Simulation function for measured pressure value and sensor temperature
Constant value or over parameterizable ramp function
Siemens FI 01 · 2015 US Edition
1/155
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for level
Selection and Ordering data
Article No.
Pressure transmitter for level,
SITRANS P DS III with HART
7MF 4 6 3 3 77 Y 77 - 7777
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Measuring cell
cleaning
normal
Measuring span (min. ... max.)
25 ... 250 mbar
(10 ... 100 inH2O)
25 ... 600 mbar
(10 ... 240 inH2O)
53 ... 1600 mbar
(21 ... 642 inH2O)
0.16 ... 5 bar
(64.3 ... 2000 inH2O)
Process connection of low-pressure side
Female thread ¼-18 NPT with flange connection
• Mounting thread 7/16-20 UNF to IEC 61518
• Mounting thread M10 to DIN 19213
(only for replacement requirement)
1
Die-cast aluminum
Stainless steel precision
casting1)
Version
• Standard versions
• International version, English label inscriptions,
documentation in 5 languages on CD
(no Order code selectable)
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"2)
- "Intrinsic safety and flameproof enclosure"
(Ex ia + Ex d)"3)
- "Ex nA/ic (Zone 2)" 4)
- "Intrinsic safety, explosion-proof enclosure and
dust explosion protection (Ex ia+ Ex d +
Zone 1D/2D)"3)5)
• FM + CSA intrinsic safe (is)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX)5)
• With FM + CSA, Type of protection:
- "Intrinsic Safe und Explosion Proof (is + xp)"1)
Electrical connection/cable entry
• Screwed gland Pg 13.56)
• Screwed gland M20x1.5
• Screwed gland ½-14 NPT
• Han 7D plug (plastic housing) incl. mating
connector6)
• M12 connectors (stainless steel) 7) 8)
Display
• Without display
• Without visible display
(display concealed, setting: mA)
• With visible display (setting mA)
• With customer-specific display (setting as
specified, Order code "Y21" or "Y22" required)
1/156
Siemens FI 01 · 2015 US Edition
Ordering example
Item line 1:
7MF4633-1EY20-1AA1-Z
B line:
Y01
C line:
Y01: 80 to 143 mbar (1.16 to 2.1 psi)
Item line 2:
7MF4912-3GE01
Power supply units see Chap. 7 "Supplementary Components".
Included in delivery of the device:
• Brief instructions (Leporello)
• CD-ROM with detailed documentation
• Sealing plug(s) or sealing screw(s) for the process flanges(s)
D
E
F
G
2
0
Non-wetted parts materials
process flange screws Electronics housing
Stainless steel
Stainless steel
Ordering information
1st order item: Pressure transmitter 7MF4633-...
2nd order item: Mounting flange 7MF4912-3...
2
3
1
2
A
B
D
P
E
R
F
S
NC
A
B
C
D
F
0
1
6
7
1)
Not in conjunction with electrical connection "Screwed gland Pg 13.5" and
"Han7D plug".
2)
Without cable gland, with blanking plug.
3)
With enclosed cable gland Ex ia and blanking plug.
4)
Configurations with HAN and M12 connectors are only available in Ex ic.
5)
Only in connection with IP65.
6)
Only in connection with Ex approval A, B or E.
7)
M12 delivered without cable socket
8)
Only in connection with Ex approval A, B, E or F.
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for level
Selection and Ordering data
Article No.
Ordering information
1st order item: Pressure transmitter 7MF4634-...
2nd order item: Mounting flange 7MF4912-...
Pressure transmitters for level
SITRANS P DS III with PROFIBUS PA (PA)
7MF 4 6 3 4 -
SITRANS P DS III with FOUNDATION Fieldbus (FF)
7MF 4 6 3 5 -
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Nominal measuring range
250 mbar
(100 inH2O)
600 mbar
(240 inH2O)
1600 mbar
(642 inH2O)
5 bar
(2000 inH2O)
Process connection of low-pressure side
Female thread ¼-18 NPT with flange connection
• Mounting thread 7/16-20 UNF to IEC 61518
• Mounting thread M10 to DIN 19213
(only for replacement requirement)
1 7 Y 77 - 7777
Ordering example
Item line 1:
7MF4634-1EY20-1AA1
Item line 2:
7MF4912-3GE01
Included in delivery of the device:
• Brief instructions (Leporello)
• CD-ROM with detailed documentation
• Sealing plug(s) or sealing screw(s) for the process flanges(s)
D
E
F
G
2
0
1)
Without cable gland, with blanking plug.
2)
With enclosed cable gland Ex ia and blanking plug.
3)
Configurations with HAN and M12 connectors are only available in Ex ic.
4)
Only in connection with IP65.
5)
M12 delivered without cable socket
6)
Only in connection with Ex approval A, B, E or F.
Non-wetted parts materials
process flange screws Electronics housing
Stainless steel
Stainless steel
Die-cast aluminum
Stainless steel precision
casting
Version
• Standard versions
• International version, English label inscriptions,
documentation in 5 languages on CD
(no Order code selectable)
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"1)
- "Intrinsic safety and flameproof enclosure"
(Ex ia + Ex d)"2)
- "Ex nA/ic (Zone 2)" 3)
- "Intrinsic safety, explosion-proof enclosure and
dust explosion protection (Ex ia + Ex d +
Zone 1D/2D)"2)4) (not for DS III FF)
• FM + CSA intrinsic safe (is)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX)4)
• With FM + CSA, Type of protection:
- "Intrinsic Safe und Explosion Proof (is + xp)"1)
Electrical connection/cable entry
• Screwed gland M20 x 1.5
• Screwed gland ½-14 NPT
• M12 connectors (stainless steel)5) 6)
Display
• Without display
• Without visible display
(display concealed, setting: bar)
• With visible display (setting: bar)
• With customer-specific display (setting as
specified, Order code "Y21" required)
2
3
1
2
A
B
D
P
E
R
F
S
NC
B
C
F
0
1
6
7
Siemens FI 01 · 2015 US Edition
1/157
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for level
Selection and Ordering data
Order code
Further designs
Selection and Ordering data
HART PA
FF
Add "-Z" to Article No. and specify Order code.
Add "-Z" to Article No. and specify Order code.
O-rings for process flanges on
low-pressure side
(instead of FPM (Viton))
• PTFE (Teflon)
• FEP (with silicone core, approved for food)
• FFPM (Kalrez, compound 4079),
for measured medium temperatures
-15 ... 100 °C (5 ... 212 °F)
• NBR (Buna N)
Use on zone 1D / 2D
(only together with type of protection
"Intrinsic safety" (transmitter
7MF4...-.....-.B.. Ex ia)“and IP65)
Plug
• Han 7D (metal)
• Han 8D (instead of Han 7D)
• Angled
• Han 8D (metal)
A20
A21
A22









A23



A30
A31
A32
A33




Sealing screw
¼-18 NPT, with valve in mat. of process flanges A40



A50



Cable sockets for M12 connectors
(metal (CuZn))
Rating plate inscription
(instead of German)
• English
• French
• Spanish
• Italian
• Cyrillic (russian)
Order code
Further designs
HART PA
E01

Overfilling safety device for flammable and E08
non-flammable liquids
(max. PN 32 (MAWP 464 psi), basic device
with type of protection "Intrinsic safety (Ex ia)",
to WHG and VbF, not together with measuring
cell filling "inert liquid")

Export approval Korea
E11
CRN approval Canada
(Canadian Registration Number)
E22
Dual seal
E24
FF











Explosion-proof "Intrinsic safety" (Ex ia) to E252)
INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.B..)



"Flameproof" explosion protection accord- E262)
ing to INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.D..)



B11
B12
B13
B14
B16















Explosion-proof "Intrinsic safety" (Ex ia +
Ex d) to INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.P..)
E282)


Ex Approval IEC Ex (Ex ia)
(only for transmitter 7MF4...-.....-.B..)
E452)



English rating plate
Pressure units in inH20 and/or psi
B21



Ex Approval IEC Ex (Ex d)
(only for transmitter 7MF4...-.....-.D..)
E462)



Quality inspection certificate (Five-step
factory calibration) to IEC 60770-2
C11



E552)



Inspection certificate
Acc. to EN 10204-3.1
C12



Explosion-proof "Intrinsic safety"
to NEPSI (China)
(only for transmitter 7MF4...-.....-.B..)


C14



Explosion protection "Explosion-proof" to E562)
NEPSI (China)
(only for transmitter 7MF4...-.....-.D..)

Factory certificate
Acc. to EN 10204-2.2
Functional safety (SIL2)
Devices suitable for use according to IEC
61508 and IEC 61511. Includes SIL conformity declaration
C20

E572)






Functional safety (PROFIsafe)
Certificate and PROFIsafe protocol
C211)
Ex protection „Ex ia“, „Ex d“ and „Zone 2“ E582)
to NEPSI (China)
(only for transmitter 7MF4...-.....-.R..)
Functional safety (SIL2/3)
Devices suitable for use according to IEC
61508 and IEC 61511. Includes SIL conformity declaration
C23

"Intrinsic safety" and "Explosion-proof"
explosion protection acc. to Kosha (Korea)
(only for transmitter
7MF4...-.....-.[B, D]..-Z + E11)
E702)



Device passport Russia
C99

Two coats of lacquer on casing and cover
(PU on epoxy)
G10



Replacement of process connection side
Ex protection "Zone 2" to NEPSI (China)
(only for transmitter 7MF4...-.....-.E..)



(For price request please contact the technical
support
www.siemens.com/automation/support-request)
Setting of upper limit of
output signal to 22.0 mA
D05

Degree of protection IP66/IP68
(only for M20x1.5 and ½-14 NPT)
D12



Supplied with oval flange
(1 item), PTFE packing and screws in thread
of process flange
D37



Capri cable gland 4F CrNi and clamping
device (848699 + 810634) included
D59



H01



Transient protector 6 kV (lightning protec- J01
tion)



Vent valve or blanking plug of process
flange welded-in (orientation: on right
when viewing the display)3)
J08



J09
Vent valve or blanking plug of process
flange welded-in (orientation: on left when
3)
viewing the display)



1)
Profisafe transmitters can only be operated with the S7 F Systems V6.1 configuration software in combination with S7-400H
Option beinhaltet keine ATEX-Zulassung, sondern nur die landesspezifische Zulassung.
3)
Blanking plug is standard configuration. Order option A40 if a vent valve is
required instead of a blanking plug.
2)
1/158
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for level
Selection and Ordering data
Order code
Additional data
HART PA
FF
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
Measuring range to be set
Specify in plain text (max. 5 characters):
Y01: ... up to ... mbar, bar, kPa, MPa, psi
Y01

1)
Stainless steel tag plate and entry in
device variable (measuring point description)
Max. 16 characters, specify in plain text:
Y15: ...........................................
Y15



Measuring point text (entry in device variable)
Max. 27 characters, specify in plain text:
Y16: ...........................................
Y16



Entry of HART address (TAG)
Max. 8 characters, specify in plain text:
Y17: ...........................................
Y17

Setting of pressure indicator in pressure
Y21
units
Specify in plain text (standard setting: bar):
Y21: mbar, bar, kPa, MPa, psi, ...
Note:
The following pressure units can be selected:
bar, mbar, mm H2O*), inH2O*), ftH2O*),
mmHG, inHG, psi, Pa, kPa, MPa, g/cm2,
kg/cm2, Torr, ATM or %
*) ref. temperature 20 °C



Setting of pressure indicator in
Y223)
non-pressure units2)
+ Y01
Specify in plain text:
3/h, m, USgpm, ...
Y22: ..... up to ..... l/min, m
(specification of measuring range in pressure
units "Y01" is essential, unit with
max. 5 characters)





Preset bus address
possible between 1 and 126
Specify in plain text:
Y25: ...........................................
Y25
Damping adjustment in seconds
(0 ... 100 s)
Y30

Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 and D05 can be factory preset
 = available
1)
Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are
calculated in the same way as for HART devices.
Preset values can only be changed over SIMATIC PDM.
3)
Not in conjunction with over-filling safety device for flammable and nonflammable liquids (Order code "E08")
2)
Siemens FI 01 · 2015 US Edition
1/159
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for level
Selection and Ordering data
Article No. Ord. code
Selection and Ordering data
Mounting flange
7MF 4 9 1 2 -
Further designs
Directly mounted on the SITRANS P pressure
transmitter (converter part) for level, for DS III
series
3 7777
777
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Connection to EN 1092-1
Nominal diameter
Nominal pressure
DN 50
PN 10/16/25/40
PN 100
A
B
DN 80
PN 10/16/25/40
D
DN 100
PN 10/16
PN 25/40
G
H
Connection to ASME B16.5
Nominal diameter
Nominal pressure
2 inch
class 150
class 300
class 400/600
class 900/1500
3 inch
class 150
class 300
4 inch
class 150
class 300
Other version, add Order code and plain text:
Nominal diameter: ...; Nominal press.: ...
Wetted parts materials
• Stainless steel 316L
- Coated with PFA
- Coated with PTFE
• Coated with ECTFE1)
• Monel 400, mat. no. 2.4360
• Hastelloy C276, mat. no. 2.4819
• Hastelloy C4, mat. no. 2.4610
• Tantalum
• Duplex 2205, mat. no. 1.4462
• Duplex 2205, mat. no. 1.4462, incl. main body
• Stainless steel 316L, gold plated,
thickness approx. 25 m
Tube length
• None
• 50 mm
(1.97 inch)
• 100 mm
(3.94 inch)
• 150 mm
(5.90 inch)
• 200 mm
(7.87 inch)
Other version: add Order code and plain text:
material of parts in contact with medium: ........,
tubus length: ........
Filling liquid
• Silicone oil M5
• Silicone oil M50
• High-temperature oil
• Halocarbon oil (for O2-measurement)
• Food oil (FDA-listed)
Other version, add
Order code and plain text:
filling liquid: ...
1)
For vacuum on request
1/160
Siemens FI 01 · 2015 US Edition
L
M
N
P
Q
R
T
U
Z
J1Y
A
D
E0
F
G
J
U
K
Q
R
S0
0
1
2
3
4
Z8
K1Y
1
2
3
4
7
9
M1 Y
Order code
HART PA
FF
Add "-Z" to Article No. and specify Order code.
Spark arrester
A01
For mounting on zone 0 (incl. documentation)



Remote seal nameplate
attached out of stainless steel, contains Article No. and order number of the remote seal
supplier
B20



Oil- and grease-free cleaned version
C10
Oil- and grease-free cleaned and packed version, not for oxygen application, only in conjunction with halocarbon oil fill fluid, certified by
certificate acc. to EN 10204-2.2



Quality inspection certificate (Five-step
factory calibration) to IEC 60770-2
C11



Inspection certificate
Acc. to EN 10204-3.1
C12



2.2 Certificate of FDA approval of fill oil
C17
Only in conjunction with filling liquid "Food oil"
(FDA listed)"
"Functional safety (SIL2)" certificate
C20
to IEC 61508





"Functional safety (SIL2/3)" certificate
C23
to IEC 61508
(only for conjunction with the Order code "C23"
in the case of SITRANS P DS III transmitter)


Certification acc. to NACE MR-0175
D07
Includes acceptance test certificate 3.1 acc. to
EN 10204 (only for wetted parts made of stainless steel 1.4404/316L and Hastelloy C276)



Certification acc. to NACE MR-0103
D08
Includes acceptance test certificate 3.1 acc. to
EN 10204 (only for wetted parts made of stainless steel 1.4404/316L and Hastelloy C276)



Oil- and grease-free cleaned version
E10
Oil- and grease-free cleaned and packed version, only for oxygen application, only inert fill
fluid may be used. Max. temperature: 60 °C
(140 °F), max. pressure 50 bar (725 psi), only
in connection with halocarbon oil, certified by
certificate acc. to EN 10204-2.2



Epoxy painting
E15
Not possible with vacuum-proof design
Color: transparent, coverage: front and rear of
the remote seal, capillary(ies) or connecting
tube, process connection of the transmitter.
With transmitters 7MF40.. and 7MF42.., only
possible with process connection G½B
according to EN837-1.



Sealing surface B1 or
J12
ASME B16.5 RF 125 ... 250 AA
instead of sealing surface B2 or RFSF
(only for wetted parts made of Hastelloy C276
(2.4819), tantalum and Duplex 2205 (1.4462)
and for nominal sizes 2", 3", DN 50 and DN 80)



Sealing surface groove, EN 1092-1, form D J14
instead of sealing surface B1 (only for wetted
parts made of stainless steel 316L)



Sealing surface RJF (groove) ASME B16.5 J24
instead of sealing surface ASME B16.5 RF
125 ... 250 AA (only for wetted parts made of
stainless steel 316L)



(only for conjunction with the Order code "C20"
in the case of SITRANS P DS III transmitter)
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for level
Selection and Ordering data
Order code
Further designs
HART PA
FF
Add "-Z" to Article No. and specify Order code.
Elongated pipe, 150 mm instead of 100 mm, R15
max. medium temperature 250 °C, observe
the maximum permissible media temperature
of the filling liquid.



Elongated pipe, 200 mm instead of 100 mm, R20
max. medium temperature 300 °C, observe
the maximum permissible media temperature
of the filling liquid.



Vacuum-proof design
(for use in low-pressure range)
Note: suffix "Y01" required with press. transm.
 = available



V04
Siemens FI 01 · 2015 US Edition
1/161
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for level
■ Dimensional drawings
29 (1.14) 5)
177 (6.97)
84 (3.31)
53 (2.1)
2
3
1
143 (5.6)
74 (2.9)
5
15
(0.6)
6
166 (6.54)
4
Øk
ØD
Ød4
min. 90
(3.54) 4)
Ød 5
1
9
54 (2.1)
approx. 96 (3.78)
108 (4.25)
17 (0.67)
7
n x d2
b
f
L
1
8
1
Electrical connection:
Screwed gland Pg 13,5 (adapter)(Adapter)2) 3),
Screwed gland M20 x 1,5 or Screwed gland ½-14 NPT or
Han 7D/Han 8D2) 3) plug
2
Protective cover over keys
3
Blanking plug
4
Screw cover - safety bracket (only for type of protection
"Explosion-proof enclosure", not shown in the drawing)
5
Terminal side1)
6
Electronic side, digital display
(longer overall length for cover with window)1)
7
Sealing screw with valve (option)
8
Harting adapter
9
Process connection of low pressure side ¼-18 NPT (IEC 61518)
1)
Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing
Not with type of protection "Explosion-proof enclosure"
Not with type of protection "FM + CSA" [IS + XP]"
92 mm (3.62 inch) for minimum distance to permit rotation with indicator
For Pg 13,5 with adapter approx. 45 mm (1.77 inch)
2)
3)
4)
5)
SITRANS P DS III with HART pressure transmitters for level, including mounting flange, dimensions in mm (inch)
1/162
Siemens FI 01 · 2015 US Edition
Space for rotation
of housing
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for level
Connection to EN 1092-1
Nominal
diameter
Nominal
pressure
DN 50
PN 10/16/
25/40
DN 80
DN 100
b
D
d
d2
d4
d5
dM
f
k
n
L
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
20
165
90
18
102
48.3
451)
2
125
8
0, 50, 100,
150 or 200
PN 100
28
195
90
26
102
48.3
451)
2
145
8
PN 10/16/
25/40
24
200
90
18
138
76
722)
2
160
8
PN 100
32
230
90
26
138
76
722)
2
180
8
PN 10/16
20
220
115
18
158
94
89
2
180
8
PN 25/40
24
235
115
22
162
94
89
2
190
8
Connection to ASME B16.5
Nominal
diameter
Nominal
pressure
b
lb./sq.in
inch (mm) inch (mm) inch (mm) inch (mm)
inch (mm) inch (mm) inch (mm) inch (mm)
2 inch
150
0.77 (19.5) 5.91 (150)
0.79 (20)
3.62 (92)
1.9 (48.3)
1.771) (45)
0.08 (2)
4.74 (120.5) 4
300
0.89 (22.7) 6.5 (165)
0.79 (20)
3.62 (92)
1.9 (48.3)
1.771) (45)
0.08 (2)
5 (127)
8
400/600
1.28 (32.4) 6.5 (165)
0.79 (20)
3.62 (92)
1.9 (48.3)
1.771) (45)
0.28 (7)
5 (127)
8
900/1500
1.78 (45.1) 8.46 (215)
1.02 (26)
5 (127)
1.9 (48.3)
1.771) (45)
0.28 (7)
6.5 (165)
8
4
3 inch
4 inch
D
d2
d4
d5
dM
f
k
n
inch (mm)
150
0.96 (24.3) 7.48 (190)
0.79 (20)
5 (127)
3 (76)
2.832) (72)
0.08 (2)
6 (152.5)
300
1.14 (29)
8.27 (210)
0.87 (22)
5 (127)
3 (76)
2.832) (72)
0.08 (2)
6.63 (168.5) 8
600
1.53 (38.8) 8.27 (210)
0.87 (22)
5 (127)
3 (76)
2.832) (72)
0.28 (7)
6.63 (168.5) 8
150
0.96 (24.3) 9.06 (230)
0.79 (20)
6.22 (158)
3.69 (94)
3.5 (89)
0.08 (2)
7.5 (190.5)
8
300
1.27 (32.2) 10.04 (255) 0.87 (22)
6.22 (158)
3.69 (94)
3.5 (89)
0.08 (2)
7.87 (200)
8
400
1.65 (42)
6.22 (158)
3.69 (94)
3.5 (89)
0.28 (7)
7.87 (200)
8
10.04 (255) 1.02 (26)
L
0, 2, 3.94,
5.94 or 7.87
(0, 50, 100,
150 or 200)
d: Internal diameter of gasket to DIN 2690
dM: Effective diaphragm diameter
1)
59 mm = 2.32 inch with tube length L=0.
2)
89 mm = 3½ inch with tube length L=0.
Siemens FI 01 · 2015 US Edition
1/163
1