© Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for level ■ Technical specifications SITRANS P DS III for level HART PROFIBUS PA or FOUNDATION Fieldbus Input Measured variable Level Spans (infinitely adjustable) or nominal measuring Span (min. ... max.) range and max. permissible operating pressure Maximum operating pressure Nominal measuring range Maximum operating pressure 25 ... 250 mbar (10 ... 100 inH2O) See "Mounting flange" 250 mbar (100 inH2O) See "Mounting flange" 25 ... 600 mbar (10 ... 240 inH2O) See "Mounting flange" 600 mbar (240 inH2O) See "Mounting flange" 53 ... 1600 mbar (21 ... 642 inH2O) See "Mounting flange" 1600 mbar (642 inH2O) See "Mounting flange" 160 ... 5000 mbar (64 ... 2000 inH2O) See "Mounting flange" 5 bar (2000 inH2O) See "Mounting flange" Lower measuring limit • Measuring cell with silicone oil filling -100 % of max. span or 500 mbar a (7.25 psia) Also available as vacuum-resistant remote seal: 30 mbar a (0.44 psi a) Upper measuring limit 100 % of max. span 100 % of the max. nominal measuring range Output signal 4 ... 20 mA • Lower limit (infinitely adjustable) • Upper limit (infinitely adjustable) 3.55 mA, factory preset to 3.84 mA 23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA Digital PROFIBUS PA and FOUNDATION Fieldbus signal - Output Load • Without HART RB (UH - 10.5 V)/0.023 A in , UH: Power supply in V RB = 230 ... 500 (SIMATIC PDM) or RB = 230 ... 1100 (HART Communicator) - Physical bus - IEC 61158-2 Protection against polarity reversal Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. • With HART Set to 2 s (0 ... 100 s) Electrical damping (step width 0.1 s) Acc. to IEC 60770-1 Measuring accuracy Reference conditions (All error data refer always refer to the set span) - Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 °C (77 °F) Span ratio r = max. span/set span) Nominal measuring range ratio r = nominal measuring range/set measuring range Error in measurement at limit setting incl. hysteresis and reproducibility • Linear characteristic - r 10 0.15 % 0.15 % - 10 < r 30 0.3 % 0.3 % - 30 < r 100 (0.0075 r + 0.075) % (0.0075 r + 0.075) % (0.25 r)% every 5 years static pressure max. 70 bar (1015 psi) (0.25 r)% every 5 years static pressure max. 70 bar (1015 psi) - 250 mbar- (100 inH2O)-measuring cell (0.5 r + 0.2) %1) 4) (0.5 r + 0.2) %1) 4) - 600 mbar- (240 inH2O)-measuring cell (0.3 r + 0.2) (0.3 r + 0.2) %2) 4) Long-term stability (temperature change ± 30 °C (± 54 °F)) Influence of ambient temperature • at -10 ... +60 °C (14 ... 140 °F) %2) 4) - 1600 and 5000 mbar- (642 and 2000 inH2O)- (0.25 r + 0.2) measuring cell %3) 4) (0.25 r + 0.2) %3) 4) • at -40 ... -10 °C and 60 ... 85 °C (-40 ... +14 °F and 140 ... 185 °F) - 250 mbar- (100 inH2O)-measuring cell (0.25 r + 0.15) %/10 K doubled values at 10 < r 30 (0.25 r + 0.15) %/10 K doubled values at 10 < r 30 - 600 mbar- (240 inH2O)-measuring cell (0.15 r + 0.15) %/10 K doubled values at 10 < r 30 (0.15 r + 0.15) %/10 K doubled values at 10 < r 30 - 1600 and 5000 mbar- (642 and 2000 inH2O)- (0.12 r + 0.15) %/10 K measuring cell double values at 10 < r 30 1/152 Siemens FI 01 · 2015 US Edition (0.12 r + 0.15) %/10 K double values at 10 < r 30 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for level SITRANS P DS III for level HART PROFIBUS PA or FOUNDATION Fieldbus - 250 mbar- (100 inH2O)-measuring cell (0.3 r) % per nominal pressure (0.3 r) % per nominal pressure - 600 mbar- (240 inH2O)-measuring cell (0.15 r) % per nominal pressure (0.15 r) % per nominal pressure Influence of static pressure • on the zero point - 1600 and 5000 mbar- (642 and 2000 inH2O)- (0.1 r) % per nominal pressure measuring cell (0.1 r) % per nominal pressure • on the span (0.1 r) % per nominal pressure (0.1 r) % per nominal pressure Measured Value Resolution - 3 10-5 of nominal measuring range Rated conditions Degree of protection to IEC 60529 IP66 (optional IP66/IP68), NEMA 4X Note: Always take into account assignment of max. permissible operating temperature to max. permissible operating pressure of the respective flange connection! Temperature of medium -40 ... +1005) °C (-40 ... +2125) °F) • Measuring cell with silicone oil filling - High-pressure side pabs 1 bar: -40 ... +175 °C (-40 ... +347 °F) pabs < 1 bar: -40 ... +80 °C (-40 ... +176 °F) - Low-pressure side -40 ... +100 °C (-40 ... +212 °F) -20 ... +60 °C (-4 ... +140 °F) in conjunction with dust explosion protection Ambient conditions • Ambient temperature - Transmitter (with 4-wire connection, observe temperature values of supplementary 4-wire electronics) -40 ... +85 °C (-40 ... +185 °F) - -Display readable -30 ... +85 °C (-22 ... +185 °F) • Storage temperature -50 ... +85 °C (-58 ... +185 °F) • Climatic class - Condensation Relative humidity 0 ... 100 %, condensation permissible, suitable for use in the tropics • Electromagnetic Compatibility - Emitted interference and interference immunity Acc. to IEC 61326 and NAMUR NE 21 Design Weight (without options) • To EN (pressure transmitter with mounting flange, without tube) 11 ... 13 kg ( 24.2 ... 28.7 (lb) • To ASME (pressure transmitter with mounting flange, without tube) 11 ... 18 kg ( 24.2 ... 39.7 lb) Low-copper die-cast aluminum, GD-AlSi12 or stainless steel precision casting, mat. no. 1.4408 Enclosure material Wetted parts materials High-pressure side • Seal diaphragm of mounting flange Stainless steel, mat. no. 1.4404/316L, Monel, mat. no. 2.4360, Hastelloy B2, mat. no. 2.4617, Hastelloy C276, mat. no. 2.4819, Hastelloy C4, mat. no. 2.4610, tantalum, PTFE, ETCFE, stainless steel Duplex, mat. no. 1.4462 Measuring cell filling Silicone oil Process connection • High-pressure side Flange to EN and ASME • Low-pressure side Female thread ¼-18 NPT and flange connection with mounting thread M10 to DIN 19213 or 7/ -20 UNF to EN 61518 16 Supplied through bus Power supply UH Terminal voltage on transmitter 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsically-safe mode - Separate 24 V power supply necessary - No • Not Ex - 9 ... 32 V • With intrinsically-safe operation - 9 ... 24 V Bus voltage Current consumption • Basic current (max.) - 12.5 mA • Start-up current basic current - Yes • Max. current in event of fault - 15.5 mA Fault disconnection electronics (FDE) available - Yes Siemens FI 01 · 2015 US Edition 1/153 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for level SITRANS P DS III for level HART PROFIBUS PA or FOUNDATION Fieldbus Certificates and approvals Classification according to PED 97/23/EC For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) Explosion protection • Intrinsic safety "i" PTB 13 ATEX 2007 X Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb - Marking - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +70 °C (-40 ... +158 °F) temperature class T5; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 - Connection To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF L i = 7 H, Ci = 1.1 nF • Explosion-proof "d" PTB 99 ATEX 1160 - Marking Ex II 1/2 G Ex d IIC T4/T6 Gb - Permissible ambient temperature - Connection -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 To circuits with values: UH = 10.5 ... 45 V DC • Dust explosion protection for zone 20 To circuits with values: UH = 9 ... 32 V DC PTB 01 ATEX 2055 - Marking Ex II 1 D IP65 T 120 °C Ex II 1/2 D IP65 T 120 °C - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) - Max. surface temperature 120 °C (248 °F) - Connection To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF L i = 7 H, Ci = 1.1 nF PTB 01 ATEX 2055 • Dust explosion protection for zone 21/22 - Marking Ex II 2 D IP65 T 120 °C - Connection To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W • Type of protection "n" (zone 2) To circuits with values: UH = 9 ... 32 V DC; Pmax = 1 W PTB 13 ATEX 2007 X Ex II 2/3 G Ex nA II T4/T5/T6 Gc Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc - Marking - Connection (Ex nA) Um = 45 V Um = 32 V - Connection (Ex ic) To circuits with values: Ui = 45 V FISCO supply unit ic: Uo = 17.5 V, Io = 570 mA Linear barrier: Uo = 32 V, Io = 132 mA, Po = 1 W - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF • Explosion protection acc. to FM - Identification (XP/DIP) or (IS); (NI) CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III • Explosion protection to CSA - Identification (XP/DIP) or (IS) L i = 7 H, Ci = 1.1 nF Certificate of Compliance 3008490 Certificate of Compliance 1153651 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III 1) Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.4 · r + 0.16) % / 28 °C (50 °F). 2) Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.24 · r + 0.16) % / 28 °C (50 °F). 3) Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.2 · r + 0.16) % / 28 °C (50 °F). 4) 0.32 instead of 0.16 at 10 < r < 30 5) This value may be increased if the process connection is sufficiently insulated. 1/154 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for level HART communication HART 230 ... 1100 Protocol HART Version 5.x Software for computer SIMATIC PDM PROFIBUS PA communication Simultaneous communication with master class 2 (max.) 4 The address can be set using Configuration tool or local operation (standard setting address 126) Cyclic data usage • Output byte 5 (one measured value) or 10 (two measured values) • Input byte 0, 1, or 2 (register operating mode and reset function for metering) Internal preprocessing FOUNDATION Fieldbus communication Function blocks 3 function blocks analog input, 1 function block PID • Analog input - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic - Electrical damping, adjustable 0 ... 100 s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic for flow measurement Yes Device profile PROFIBUS PA Profile for Process Control Devices Version 3.0, class B • PID Standard FOUNDATION Fieldbus function block • Physical block 1 resource block Function blocks 2 Transducer blocks - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic 1 transducer block Pressure with calibration, 1 transducer block LCD • Pressure transducer block - Electrical damping, adjustable 0 ... 100 s - Simulation function Input/Output - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively • Analog input • Register (totalizer) - Failure mode - Limit monitoring Can be reset, preset, optional direction of counting, simulation function of register output parameterizable (summation with last good value, continuous summation, summation with incorrect value) One upper and lower warning limit and one alarm limit respectively • Physical block 1 Transducer blocks 2 - Can be calibrated by applying two pressures Yes - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Constant value or over parameterizable ramp function Mounting flange Nominal diameter Nominal pressure • Acc. to EN 1092-1 - DN 80 PN 40 - DN100 PN16, PN40 • To ASME B16.5 - 3 inch class 150, class 300 - 4 inch class 150, class 300 • Pressure transducer block - Can be calibrated by applying two pressures Yes - Monitoring of sensor limits Yes - Specification of a container characteristic with Max. 30 nodes - Square-rooted characteristic for flow measurement Yes - Gradual volume suppression and implementation point of square-root extraction Parameterizable - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function Siemens FI 01 · 2015 US Edition 1/155 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for level Selection and Ordering data Article No. Pressure transmitter for level, SITRANS P DS III with HART 7MF 4 6 3 3 77 Y 77 - 7777 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Silicone oil Measuring cell cleaning normal Measuring span (min. ... max.) 25 ... 250 mbar (10 ... 100 inH2O) 25 ... 600 mbar (10 ... 240 inH2O) 53 ... 1600 mbar (21 ... 642 inH2O) 0.16 ... 5 bar (64.3 ... 2000 inH2O) Process connection of low-pressure side Female thread ¼-18 NPT with flange connection • Mounting thread 7/16-20 UNF to IEC 61518 • Mounting thread M10 to DIN 19213 (only for replacement requirement) 1 Die-cast aluminum Stainless steel precision casting1) Version • Standard versions • International version, English label inscriptions, documentation in 5 languages on CD (no Order code selectable) Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" - "Explosion-proof (Ex d)"2) - "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"3) - "Ex nA/ic (Zone 2)" 4) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (Ex ia+ Ex d + Zone 1D/2D)"3)5) • FM + CSA intrinsic safe (is) • FM + CSA (is + ep) + Ex ia + Ex d (ATEX)5) • With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)"1) Electrical connection/cable entry • Screwed gland Pg 13.56) • Screwed gland M20x1.5 • Screwed gland ½-14 NPT • Han 7D plug (plastic housing) incl. mating connector6) • M12 connectors (stainless steel) 7) 8) Display • Without display • Without visible display (display concealed, setting: mA) • With visible display (setting mA) • With customer-specific display (setting as specified, Order code "Y21" or "Y22" required) 1/156 Siemens FI 01 · 2015 US Edition Ordering example Item line 1: 7MF4633-1EY20-1AA1-Z B line: Y01 C line: Y01: 80 to 143 mbar (1.16 to 2.1 psi) Item line 2: 7MF4912-3GE01 Power supply units see Chap. 7 "Supplementary Components". Included in delivery of the device: • Brief instructions (Leporello) • CD-ROM with detailed documentation • Sealing plug(s) or sealing screw(s) for the process flanges(s) D E F G 2 0 Non-wetted parts materials process flange screws Electronics housing Stainless steel Stainless steel Ordering information 1st order item: Pressure transmitter 7MF4633-... 2nd order item: Mounting flange 7MF4912-3... 2 3 1 2 A B D P E R F S NC A B C D F 0 1 6 7 1) Not in conjunction with electrical connection "Screwed gland Pg 13.5" and "Han7D plug". 2) Without cable gland, with blanking plug. 3) With enclosed cable gland Ex ia and blanking plug. 4) Configurations with HAN and M12 connectors are only available in Ex ic. 5) Only in connection with IP65. 6) Only in connection with Ex approval A, B or E. 7) M12 delivered without cable socket 8) Only in connection with Ex approval A, B, E or F. © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for level Selection and Ordering data Article No. Ordering information 1st order item: Pressure transmitter 7MF4634-... 2nd order item: Mounting flange 7MF4912-... Pressure transmitters for level SITRANS P DS III with PROFIBUS PA (PA) 7MF 4 6 3 4 - SITRANS P DS III with FOUNDATION Fieldbus (FF) 7MF 4 6 3 5 - Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Nominal measuring range 250 mbar (100 inH2O) 600 mbar (240 inH2O) 1600 mbar (642 inH2O) 5 bar (2000 inH2O) Process connection of low-pressure side Female thread ¼-18 NPT with flange connection • Mounting thread 7/16-20 UNF to IEC 61518 • Mounting thread M10 to DIN 19213 (only for replacement requirement) 1 7 Y 77 - 7777 Ordering example Item line 1: 7MF4634-1EY20-1AA1 Item line 2: 7MF4912-3GE01 Included in delivery of the device: • Brief instructions (Leporello) • CD-ROM with detailed documentation • Sealing plug(s) or sealing screw(s) for the process flanges(s) D E F G 2 0 1) Without cable gland, with blanking plug. 2) With enclosed cable gland Ex ia and blanking plug. 3) Configurations with HAN and M12 connectors are only available in Ex ic. 4) Only in connection with IP65. 5) M12 delivered without cable socket 6) Only in connection with Ex approval A, B, E or F. Non-wetted parts materials process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminum Stainless steel precision casting Version • Standard versions • International version, English label inscriptions, documentation in 5 languages on CD (no Order code selectable) Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" - "Explosion-proof (Ex d)"1) - "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"2) - "Ex nA/ic (Zone 2)" 3) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (Ex ia + Ex d + Zone 1D/2D)"2)4) (not for DS III FF) • FM + CSA intrinsic safe (is) • FM + CSA (is + ep) + Ex ia + Ex d (ATEX)4) • With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)"1) Electrical connection/cable entry • Screwed gland M20 x 1.5 • Screwed gland ½-14 NPT • M12 connectors (stainless steel)5) 6) Display • Without display • Without visible display (display concealed, setting: bar) • With visible display (setting: bar) • With customer-specific display (setting as specified, Order code "Y21" required) 2 3 1 2 A B D P E R F S NC B C F 0 1 6 7 Siemens FI 01 · 2015 US Edition 1/157 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for level Selection and Ordering data Order code Further designs Selection and Ordering data HART PA FF Add "-Z" to Article No. and specify Order code. Add "-Z" to Article No. and specify Order code. O-rings for process flanges on low-pressure side (instead of FPM (Viton)) • PTFE (Teflon) • FEP (with silicone core, approved for food) • FFPM (Kalrez, compound 4079), for measured medium temperatures -15 ... 100 °C (5 ... 212 °F) • NBR (Buna N) Use on zone 1D / 2D (only together with type of protection "Intrinsic safety" (transmitter 7MF4...-.....-.B.. Ex ia)“and IP65) Plug • Han 7D (metal) • Han 8D (instead of Han 7D) • Angled • Han 8D (metal) A20 A21 A22 A23 A30 A31 A32 A33 Sealing screw ¼-18 NPT, with valve in mat. of process flanges A40 A50 Cable sockets for M12 connectors (metal (CuZn)) Rating plate inscription (instead of German) • English • French • Spanish • Italian • Cyrillic (russian) Order code Further designs HART PA E01 Overfilling safety device for flammable and E08 non-flammable liquids (max. PN 32 (MAWP 464 psi), basic device with type of protection "Intrinsic safety (Ex ia)", to WHG and VbF, not together with measuring cell filling "inert liquid") Export approval Korea E11 CRN approval Canada (Canadian Registration Number) E22 Dual seal E24 FF Explosion-proof "Intrinsic safety" (Ex ia) to E252) INMETRO (Brazil) (only for transmitter 7MF4...-.....-.B..) "Flameproof" explosion protection accord- E262) ing to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.D..) B11 B12 B13 B14 B16 Explosion-proof "Intrinsic safety" (Ex ia + Ex d) to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.P..) E282) Ex Approval IEC Ex (Ex ia) (only for transmitter 7MF4...-.....-.B..) E452) English rating plate Pressure units in inH20 and/or psi B21 Ex Approval IEC Ex (Ex d) (only for transmitter 7MF4...-.....-.D..) E462) Quality inspection certificate (Five-step factory calibration) to IEC 60770-2 C11 E552) Inspection certificate Acc. to EN 10204-3.1 C12 Explosion-proof "Intrinsic safety" to NEPSI (China) (only for transmitter 7MF4...-.....-.B..) C14 Explosion protection "Explosion-proof" to E562) NEPSI (China) (only for transmitter 7MF4...-.....-.D..) Factory certificate Acc. to EN 10204-2.2 Functional safety (SIL2) Devices suitable for use according to IEC 61508 and IEC 61511. Includes SIL conformity declaration C20 E572) Functional safety (PROFIsafe) Certificate and PROFIsafe protocol C211) Ex protection „Ex ia“, „Ex d“ and „Zone 2“ E582) to NEPSI (China) (only for transmitter 7MF4...-.....-.R..) Functional safety (SIL2/3) Devices suitable for use according to IEC 61508 and IEC 61511. Includes SIL conformity declaration C23 "Intrinsic safety" and "Explosion-proof" explosion protection acc. to Kosha (Korea) (only for transmitter 7MF4...-.....-.[B, D]..-Z + E11) E702) Device passport Russia C99 Two coats of lacquer on casing and cover (PU on epoxy) G10 Replacement of process connection side Ex protection "Zone 2" to NEPSI (China) (only for transmitter 7MF4...-.....-.E..) (For price request please contact the technical support www.siemens.com/automation/support-request) Setting of upper limit of output signal to 22.0 mA D05 Degree of protection IP66/IP68 (only for M20x1.5 and ½-14 NPT) D12 Supplied with oval flange (1 item), PTFE packing and screws in thread of process flange D37 Capri cable gland 4F CrNi and clamping device (848699 + 810634) included D59 H01 Transient protector 6 kV (lightning protec- J01 tion) Vent valve or blanking plug of process flange welded-in (orientation: on right when viewing the display)3) J08 J09 Vent valve or blanking plug of process flange welded-in (orientation: on left when 3) viewing the display) 1) Profisafe transmitters can only be operated with the S7 F Systems V6.1 configuration software in combination with S7-400H Option beinhaltet keine ATEX-Zulassung, sondern nur die landesspezifische Zulassung. 3) Blanking plug is standard configuration. Order option A40 if a vent valve is required instead of a blanking plug. 2) 1/158 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for level Selection and Ordering data Order code Additional data HART PA FF Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Specify in plain text (max. 5 characters): Y01: ... up to ... mbar, bar, kPa, MPa, psi Y01 1) Stainless steel tag plate and entry in device variable (measuring point description) Max. 16 characters, specify in plain text: Y15: ........................................... Y15 Measuring point text (entry in device variable) Max. 27 characters, specify in plain text: Y16: ........................................... Y16 Entry of HART address (TAG) Max. 8 characters, specify in plain text: Y17: ........................................... Y17 Setting of pressure indicator in pressure Y21 units Specify in plain text (standard setting: bar): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, Torr, ATM or % *) ref. temperature 20 °C Setting of pressure indicator in Y223) non-pressure units2) + Y01 Specify in plain text: 3/h, m, USgpm, ... Y22: ..... up to ..... l/min, m (specification of measuring range in pressure units "Y01" is essential, unit with max. 5 characters) Preset bus address possible between 1 and 126 Specify in plain text: Y25: ........................................... Y25 Damping adjustment in seconds (0 ... 100 s) Y30 Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 and D05 can be factory preset = available 1) Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are calculated in the same way as for HART devices. Preset values can only be changed over SIMATIC PDM. 3) Not in conjunction with over-filling safety device for flammable and nonflammable liquids (Order code "E08") 2) Siemens FI 01 · 2015 US Edition 1/159 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for level Selection and Ordering data Article No. Ord. code Selection and Ordering data Mounting flange 7MF 4 9 1 2 - Further designs Directly mounted on the SITRANS P pressure transmitter (converter part) for level, for DS III series 3 7777 777 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Connection to EN 1092-1 Nominal diameter Nominal pressure DN 50 PN 10/16/25/40 PN 100 A B DN 80 PN 10/16/25/40 D DN 100 PN 10/16 PN 25/40 G H Connection to ASME B16.5 Nominal diameter Nominal pressure 2 inch class 150 class 300 class 400/600 class 900/1500 3 inch class 150 class 300 4 inch class 150 class 300 Other version, add Order code and plain text: Nominal diameter: ...; Nominal press.: ... Wetted parts materials • Stainless steel 316L - Coated with PFA - Coated with PTFE • Coated with ECTFE1) • Monel 400, mat. no. 2.4360 • Hastelloy C276, mat. no. 2.4819 • Hastelloy C4, mat. no. 2.4610 • Tantalum • Duplex 2205, mat. no. 1.4462 • Duplex 2205, mat. no. 1.4462, incl. main body • Stainless steel 316L, gold plated, thickness approx. 25 m Tube length • None • 50 mm (1.97 inch) • 100 mm (3.94 inch) • 150 mm (5.90 inch) • 200 mm (7.87 inch) Other version: add Order code and plain text: material of parts in contact with medium: ........, tubus length: ........ Filling liquid • Silicone oil M5 • Silicone oil M50 • High-temperature oil • Halocarbon oil (for O2-measurement) • Food oil (FDA-listed) Other version, add Order code and plain text: filling liquid: ... 1) For vacuum on request 1/160 Siemens FI 01 · 2015 US Edition L M N P Q R T U Z J1Y A D E0 F G J U K Q R S0 0 1 2 3 4 Z8 K1Y 1 2 3 4 7 9 M1 Y Order code HART PA FF Add "-Z" to Article No. and specify Order code. Spark arrester A01 For mounting on zone 0 (incl. documentation) Remote seal nameplate attached out of stainless steel, contains Article No. and order number of the remote seal supplier B20 Oil- and grease-free cleaned version C10 Oil- and grease-free cleaned and packed version, not for oxygen application, only in conjunction with halocarbon oil fill fluid, certified by certificate acc. to EN 10204-2.2 Quality inspection certificate (Five-step factory calibration) to IEC 60770-2 C11 Inspection certificate Acc. to EN 10204-3.1 C12 2.2 Certificate of FDA approval of fill oil C17 Only in conjunction with filling liquid "Food oil" (FDA listed)" "Functional safety (SIL2)" certificate C20 to IEC 61508 "Functional safety (SIL2/3)" certificate C23 to IEC 61508 (only for conjunction with the Order code "C23" in the case of SITRANS P DS III transmitter) Certification acc. to NACE MR-0175 D07 Includes acceptance test certificate 3.1 acc. to EN 10204 (only for wetted parts made of stainless steel 1.4404/316L and Hastelloy C276) Certification acc. to NACE MR-0103 D08 Includes acceptance test certificate 3.1 acc. to EN 10204 (only for wetted parts made of stainless steel 1.4404/316L and Hastelloy C276) Oil- and grease-free cleaned version E10 Oil- and grease-free cleaned and packed version, only for oxygen application, only inert fill fluid may be used. Max. temperature: 60 °C (140 °F), max. pressure 50 bar (725 psi), only in connection with halocarbon oil, certified by certificate acc. to EN 10204-2.2 Epoxy painting E15 Not possible with vacuum-proof design Color: transparent, coverage: front and rear of the remote seal, capillary(ies) or connecting tube, process connection of the transmitter. With transmitters 7MF40.. and 7MF42.., only possible with process connection G½B according to EN837-1. Sealing surface B1 or J12 ASME B16.5 RF 125 ... 250 AA instead of sealing surface B2 or RFSF (only for wetted parts made of Hastelloy C276 (2.4819), tantalum and Duplex 2205 (1.4462) and for nominal sizes 2", 3", DN 50 and DN 80) Sealing surface groove, EN 1092-1, form D J14 instead of sealing surface B1 (only for wetted parts made of stainless steel 316L) Sealing surface RJF (groove) ASME B16.5 J24 instead of sealing surface ASME B16.5 RF 125 ... 250 AA (only for wetted parts made of stainless steel 316L) (only for conjunction with the Order code "C20" in the case of SITRANS P DS III transmitter) © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for level Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Elongated pipe, 150 mm instead of 100 mm, R15 max. medium temperature 250 °C, observe the maximum permissible media temperature of the filling liquid. Elongated pipe, 200 mm instead of 100 mm, R20 max. medium temperature 300 °C, observe the maximum permissible media temperature of the filling liquid. Vacuum-proof design (for use in low-pressure range) Note: suffix "Y01" required with press. transm. = available V04 Siemens FI 01 · 2015 US Edition 1/161 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for level ■ Dimensional drawings 29 (1.14) 5) 177 (6.97) 84 (3.31) 53 (2.1) 2 3 1 143 (5.6) 74 (2.9) 5 15 (0.6) 6 166 (6.54) 4 Øk ØD Ød4 min. 90 (3.54) 4) Ød 5 1 9 54 (2.1) approx. 96 (3.78) 108 (4.25) 17 (0.67) 7 n x d2 b f L 1 8 1 Electrical connection: Screwed gland Pg 13,5 (adapter)(Adapter)2) 3), Screwed gland M20 x 1,5 or Screwed gland ½-14 NPT or Han 7D/Han 8D2) 3) plug 2 Protective cover over keys 3 Blanking plug 4 Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 5 Terminal side1) 6 Electronic side, digital display (longer overall length for cover with window)1) 7 Sealing screw with valve (option) 8 Harting adapter 9 Process connection of low pressure side ¼-18 NPT (IEC 61518) 1) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing Not with type of protection "Explosion-proof enclosure" Not with type of protection "FM + CSA" [IS + XP]" 92 mm (3.62 inch) for minimum distance to permit rotation with indicator For Pg 13,5 with adapter approx. 45 mm (1.77 inch) 2) 3) 4) 5) SITRANS P DS III with HART pressure transmitters for level, including mounting flange, dimensions in mm (inch) 1/162 Siemens FI 01 · 2015 US Edition Space for rotation of housing © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for level Connection to EN 1092-1 Nominal diameter Nominal pressure DN 50 PN 10/16/ 25/40 DN 80 DN 100 b D d d2 d4 d5 dM f k n L mm mm mm mm mm mm mm mm mm mm mm 20 165 90 18 102 48.3 451) 2 125 8 0, 50, 100, 150 or 200 PN 100 28 195 90 26 102 48.3 451) 2 145 8 PN 10/16/ 25/40 24 200 90 18 138 76 722) 2 160 8 PN 100 32 230 90 26 138 76 722) 2 180 8 PN 10/16 20 220 115 18 158 94 89 2 180 8 PN 25/40 24 235 115 22 162 94 89 2 190 8 Connection to ASME B16.5 Nominal diameter Nominal pressure b lb./sq.in inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) 2 inch 150 0.77 (19.5) 5.91 (150) 0.79 (20) 3.62 (92) 1.9 (48.3) 1.771) (45) 0.08 (2) 4.74 (120.5) 4 300 0.89 (22.7) 6.5 (165) 0.79 (20) 3.62 (92) 1.9 (48.3) 1.771) (45) 0.08 (2) 5 (127) 8 400/600 1.28 (32.4) 6.5 (165) 0.79 (20) 3.62 (92) 1.9 (48.3) 1.771) (45) 0.28 (7) 5 (127) 8 900/1500 1.78 (45.1) 8.46 (215) 1.02 (26) 5 (127) 1.9 (48.3) 1.771) (45) 0.28 (7) 6.5 (165) 8 4 3 inch 4 inch D d2 d4 d5 dM f k n inch (mm) 150 0.96 (24.3) 7.48 (190) 0.79 (20) 5 (127) 3 (76) 2.832) (72) 0.08 (2) 6 (152.5) 300 1.14 (29) 8.27 (210) 0.87 (22) 5 (127) 3 (76) 2.832) (72) 0.08 (2) 6.63 (168.5) 8 600 1.53 (38.8) 8.27 (210) 0.87 (22) 5 (127) 3 (76) 2.832) (72) 0.28 (7) 6.63 (168.5) 8 150 0.96 (24.3) 9.06 (230) 0.79 (20) 6.22 (158) 3.69 (94) 3.5 (89) 0.08 (2) 7.5 (190.5) 8 300 1.27 (32.2) 10.04 (255) 0.87 (22) 6.22 (158) 3.69 (94) 3.5 (89) 0.08 (2) 7.87 (200) 8 400 1.65 (42) 6.22 (158) 3.69 (94) 3.5 (89) 0.28 (7) 7.87 (200) 8 10.04 (255) 1.02 (26) L 0, 2, 3.94, 5.94 or 7.87 (0, 50, 100, 150 or 200) d: Internal diameter of gasket to DIN 2690 dM: Effective diaphragm diameter 1) 59 mm = 2.32 inch with tube length L=0. 2) 89 mm = 3½ inch with tube length L=0. Siemens FI 01 · 2015 US Edition 1/163 1