© Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for differential pressure and flow ■ Technical specifications SITRANS P, DS III for differential pressure and flow HART PROFIBUS PA and FOUNDATION Fieldbus Input Measured variable Spans (infinitely adjustable) or nominal measuring range and max. permissible operating pressure Differential pressure and flow Span (min. ... max.) Maximum operating pressure Nominal measuring range Maximum operating pressure 1 ... 20 mbar (0.4 ... 8 inH2O) 32 bar (464 psi) 20 mbar (8 inH2O) 32 bar (464 psi) 1 ... 60 mbar (0.4 ... 24 inH2O) 160 bar (2320 psi) 60 mbar (24 inH2O) 160 bar (2320 psi) 2.5 ... 250 mbar (1 ... 100 inH2O) 250 mbar (100 inH2O) 6 ... 600 mbar (2.4 ... 240 inH2O) 600 mbar (240 inH2O) 16 ... 1600 mbar (6.4 ... 642 inH2O) 1600 mbar (642 inH2O) 50 ... 5000 mbar (20 ... 2000 inH2O) 5 bar (2000 inH2O) 0.3 ... 30 bar (4.35 ... 435 psi) 2.5 ... 250 mbar (1 ... 100 inH2O) 6 ... 600 mbar (2.4 ... 240 inH2O) 30 bar (435 psi) 420 bar (6091 psi) 250 mbar (100 inH2O) 600 mbar (240 inH2O) 16 ... 1600 mbar (6.4 ... 642 inH2O) 1600 mbar (642 inH2O) 50 ... 5000 mbar (20 ... 2000 inH2O) 5 bar (2000 inH2O) 0.3 ... 30 bar (4.35 ... 435 psi) 30 bar (435 psi) 420 bar (6091 psi) Lower measuring limit • Measuring cell with silicone oil filling -100 % of max. span or 30 mbar a (0.44 psia) (-33 % with 30 bar (435 psi) measuring cell) Upper measuring limit 100 % of max. span (for oxygen version and inert filling liquid; max. 120 bar (1740 psi)) Output Output signal 4 ... 20 mA Digital PROFIBUS PA and FOUNDATION Fieldbus signal • Lower limit (infinitely adjustable) 3.55 mA, factory preset to 3.84 mA - • Upper limit (infinitely adjustable) 23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA Load • Without HART RB (UH - 10.5 V)/0.023 A in , UH: Power supply in V - • With HART RB = 230 ... 500 (SIMATIC PDM) or RB = 230 ... 1100 (HART Communicator) - Physical bus - IEC 61158-2 Protection against polarity reversal Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. Set to 2 s (0 ... 100 s) Electrical damping (step width 0.1 s) Acc. to IEC 60770-1 Measuring accuracy Reference conditions (All error data refer always refer to the set span) Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 °C (77 °F) Span ratio r = max. span/set span Nominal measuring range ratio r = nominal measuring range/set measuring range Error in measurement at limit setting incl. hysteresis and reproducibility • Linear characteristic - r 10 (0.0029 r + 0.071) % (0.0029 r + 0.071) % - 10 < r 30 (0.0045 r + 0.071) % (0.0045 r + 0.071) % - 30 < r 100 (0.005 r + 0.05) % (0.005 r + 0.05) % - r 10 0.1 % 0.1 % - 10 < r 30 0.2 % 0.2 % - r 10 0.2 % 0.2 % - 10 < r 30 0.4 % 0.4 % • Square-rooted characteristic (flow > 50 %) • Square-rooted characteristic (flow > 25 ... 50 %) Siemens FI 01 · 2015 US Edition 1/137 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for differential pressure and flow SITRANS P, DS III for differential pressure and flow HART PROFIBUS PA and FOUNDATION Fieldbus Long-term stability (temperature change ± 30 °C (± 54 °F)) • 250, 600, 1600 and 5000 mbar (0.29, 0.87, (0.125 r) per 5 years 2.32 and 7.25 psi)-measuring cell (0.125 r) per 5 years • 20 mbar (8 inH2O)-measuring cell (0.2 r) per year (0.2 r) per year • 60 mbar (24 inH2O)-measuring cell (0.25 r) % per 5 years (0.25 r) % per 5 years • 30 bar (435 psi)-measuring cell (0.25 r) % per 5 years (0.25 r) % per 5 years • at -10 ... +60 °C (14 ... 140 °F) (0.08 r + 0.1) %1) (0.08 r + 0.1) %1) • at -40 ... -10 °C and 60 ... 85 °C (-40 ... +14 °F and 140 ... 185 °F) (0.1 r + 0.15) %/10 K (0.1 r + 0.15) %/10 K (0.15 r) % per 70 bar (1015 psi) (0.15 r) % per 70 bar (1015 psi) (0.15 r) % per 32 bar (464 psi) (0.15 r) % per 32 bar (464 psi) 0.14 % per 70 bar (1015 psi) 0.14 % per 70 bar (1015 psi) 0.2 % per 32 bar (464 psi) 0.2 % per 32 bar (464 psi) - 3 10-5 of nominal measuring range Influence of ambient temperature (Twice the value with 20 mbar (8 inH2O)measuring cell Influence of static pressure • on the zero point (PKN) - 20 mbar (0.29 psi)-measuring cell • on the span (PKS) - 20 mbar (0.29 psi)-measuring cell Measured Value Resolution Rated conditions Degree of protection (to EN 60529) IP66 (optional IP66/IP68), NEMA 4X Temperature of medium • Measuring cell with silicone oil filling -40 ... +100 °C (-40 ... +212 °F) -20 ... +100 °C (-4 ... +212 °F) with 30 bar measuring cell • Measuring cell with inert filling liquid -20 ... +100 °C (-4 ... +212 °F) • In conjunction with dust explosion protection -20 ... +60 °C (-4 ... +140 °F) Ambient conditions • Ambient temperature - Transmitter (with 4-wire connection, observe temperature values of supplementary 4-wire electronics) -40 ... +85 °C (-40 ... +185 °F) - Display readable -30 ... +85 °C (-22 ... +185 °F) • Storage temperature -50 ... +85 °C (-58 ... +185 °F) • Climatic class - Condensation Relative humidity 0 ... 100 % Condensation permissible, suitable for use in the tropics • Electromagnetic Compatibility - Emitted interference and interference immunity Acc. to IEC 61326 and NAMUR NE 21 Design Weight (without options) Enclosure material Die-cast aluminum: 4.5 kg ( 9.9 lb) Stainless steel precision casting: 7.1 kg ( 15.6 lb) Low-copper die-cast aluminum, GD-AlSi12 or stainless steel precision casting, mat. no. 1.4408 Wetted parts materials • Seal diaphragm Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819, Monel, mat. no. 2.4360, tantalum or gold Measuring cell filling Silicone oil or inert filling liquid (maximum value with oxygen measurement pressure 100 bar (1450 psi) at 60 °C (140 °F)) Process connection Female thread ¼-18 NPT and flange connection with mounting thread M10 to DIN 19213 or 7/ -20 UNF to IEC 61518 16 Material of mounting bracket • Steel Sheet-steel, Mat. No. 1.0330, chrome-plated • Stainless steel 1/138 Siemens FI 01 · 2015 US Edition Sheet stainless steel, mat. no. 1.4301 (SS 304) © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for differential pressure and flow SITRANS P, DS III for differential pressure and flow HART PROFIBUS PA and FOUNDATION Fieldbus Supplied through bus Power supply UH Terminal voltage on transmitter 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsically-safe mode - Separate 24 V power supply necessary - No • Not Ex - 9 ... 32 V • With intrinsically-safe operation - 9 ... 24 V Bus voltage Current consumption • Basic current (max.) - 12.5 mA • Start-up current basic current - Yes • Max. current in event of fault - 15.5 mA Fault disconnection electronics (FDE) available - Yes Certificates and approvals Classification according to PED 97/23/EC PN 32/160 (MAWP 464/2320 psi) PN 420 (MAWP 6092 psi) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) For gases of fluid group 1 and liquids of fluid group 1; complies with basic safety requirements of Article 3, paragraph 1 (appendix 1); assigned to category III, conformity evaluation module H by the TÜV Nord. Explosion protection • Intrinsic safety "i" PTB 13 ATEX 2007 X - Marking Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb - Permissible ambient temperature - Connection -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +70 °C (-40 ... +158 °F) temperature class T5; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 To certified intrinsically-safe circuits with peak val- FISCO supply unit: ues: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W L i = 7 H, Ci = 1.1 nF - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF • Explosion-proof "d" PTB 99 ATEX 1160 - Marking Ex II 1/2 G Ex d IIC T4/T6 Gb -40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6 - Permissible ambient temperature - Connection To circuits with values: UH = 10.5 ... 45 V DC - Marking Ex II 1 D IP65 T 120 °C Ex II 1/2 D IP65 T 120 °C - Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) - Max. surface temperature - Connection 120 °C (248 °F) To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 - Marking - Connection FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1 W L i = 7 H, Ci = 1.1 nF - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF • Dust explosion protection for zone 21/22 To circuits with values: UH = 9 ... 32 V DC PTB 01 ATEX 2055 • Dust explosion protection for zone 20 PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 °C To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W To circuits with values: UH = 9 ... 32 V DC; Pmax = 1 W Siemens FI 01 · 2015 US Edition 1/139 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for differential pressure and flow SITRANS P, DS III for differential pressure and flow HART • Type of protection "n" (zone 2) Ex II 2/3 G Ex nA IIC T4/T5/T6 Gc Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc - Marking - Connection (Ex nA) Um = 45 V Um = 32 V - Connection (Ex ic) To circuits with values: Ui = 45 V FISCO supply unit ic: Uo = 17.5 V, Io = 570 mA Linear barrier: Uo = 32 V, Io = 132 mA, Po = 1 W - Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF • Explosion protection acc. to FM - Identification (XP/DIP) or (IS); (NI) • Explosion protection to CSA - Identification (XP/DIP) or (IS) 1) PROFIBUS PA and FOUNDATION Fieldbus PTB 13 ATEX 2007 X L i = 7 H, Ci = 1.1 nF Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 1153651 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.064 . r + 0.08) % / 28 °C (50 °F). 1/140 Siemens FI 01 · 2015 US Edition © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for differential pressure and flow HART communication HART 230 ... 1100 Protocol HART Version 5.x Software for PC SIMATIC PDM PROFIBUS PA communication Simultaneous communication with master class 2 (max.) 4 The address can be set using Configuration tool or local operation (standard setting address 126) Cyclic data usage • Output byte 5 (one measured value) or 10 (two measured values) • Input byte 0, 1, or 2 (register operating mode and reset function for metering) Internal preprocessing FOUNDATION Fieldbus communication Function blocks 3 function blocks analog input, 1 function block PID • Analog input - Adaptation to customerspecific process variables Yes, linearly rising or falling characteristic - Electrical damping, adjustable 0 ... 100 s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic for flow measurement Yes Device profile PROFIBUS PA Profile for Process Control Devices Version 3.0, class B • PID Standard FOUNDATION Fieldbus function block • Physical block 1 resource block Function blocks 2 Transducer blocks - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic 1 transducer block Pressure with calibration, 1 transducer block LCD • Pressure transducer block - Electrical damping, adjustable 0 ... 100 s - Simulation function Input /Output - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively • Register (totalizer) Can be reset, preset, optional direction of counting, simulation function of register output • Analog input - Failure mode parameterizable (summation with last good value, continuous summation, summation with incorrect value) - Limit monitoring One upper and lower warning limit and one alarm limit respectively • Physical block 1 Transducer blocks 2 - Can be calibrated by applying two pressures Yes - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Constant value or over parameterizable ramp function • Pressure transducer block - Can be calibrated by applying two pressures Yes - Monitoring of sensor limits Yes - Specification of a container characteristic with Max. 30 nodes - Square-rooted characteristic for flow measurement Yes - Gradual volume suppression and implementation point of square-root extraction Parameterizable - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function Siemens FI 01 · 2015 US Edition 1/141 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for differential pressure and flow Selection and Ordering data Article No. Selection and Ordering data Article No. SITRANS P DS III with HART pressure transmitters for differential pressure and flow, PN 32/160 (MAWP 464/2320 psi) 7MF 4 4 3 3 - SITRANS P DS III with HART pressure transmitters for differential pressure and flow, PN 32/160 (MAWP 464/2320 psi) 7MF 4 4 3 3 - 77777 - 7777 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal Inert liquid1) grease-free to cleanliness level 2 Electrical connection/cable entry • Screwed gland Pg 13.513) • Screwed gland M20 x 1.5 • Screwed gland ½-14 NPT • Han 7D plug (plastic housing) incl. mating connector13)14) • M12 connectors (stainless steel)15)16) 1 3 Measuring span (min. ... max.) PN 32 (MAWP 464 psi) 1 ... 20 mbar2) (0.4015 ... 8.03 inH2O) B PN 160 (MAWP 2320 psi) 1 ... 60 mbar (0.4015 ... 24.09 inH2O) 2.5 ... 250 mbar (1.004 ... 100.4 inH2O) 6 ... 600 mbar (2.409 ... 240.9 inH2O) 16 ... 1600 mbar (6.424 ... 642.4 inH2O) 50 ... 5000 mbar (20.08 ... 2008 inH2O) 0.3 ... 30 bar (4.35 ... 435 psi) C D E F G H Process connection Female thread ¼-18 NPT with flange connection • Sealing screw opposite process connection - Mounting thread 7/16-20 UNF to IEC 61518 - Mounting thread M10 to DIN 19213 (only for replacement requirement) • Vent on side of process flange 2) - Mounting thread 7/16-20 UNF to IEC 61518 - Mounting thread M10 to DIN 19213 (only for replacement requirement) Die-cast aluminum Stainless steel precision casting8) Version • Standard versions • International version, English label inscriptions, documentation in 5 languages on CD (no Order code selectable) Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" - "Explosion-proof (Ex d)"9) - "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"10) - "Ex nA/ic (Zone 2)"11) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (Ex ia+ Ex d + Zone 1D/2D)"10)12) • FM + CSA intrinsic safe (is) • FM + CSA (is + ep) + Ex ia + Ex d (ATEX)12) • With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)"9) 1/142 Siemens FI 01 · 2015 US Edition F 0 1 6 7 Power supply units see Chap. 7 "Supplementary Components". Included in delivery of the device: • Brief instructions (Leporello) • CD-ROM with detailed documentation • Sealing plug(s) or sealing screw(s) for the process flanges(s) A B C E H L Y 2 0 6 4 Non-wetted parts materials process flange screws Electronics housing Stainless steel Stainless steel A B C D Display • Without display • Without visible display (display concealed, setting: mA) • With visible display (setting: mA) • with customer-specific display (setting as specified, Order code "Y21" or "Y22" required) Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Tantalum3) Tantalum Monel3) Monel Gold3) Gold Version for diaphragm seal4) 5) 6) 7) 77777 - 7777 1) For oxygen application, add Order code E10. 2) Not suitable for connection of remote seal. Position of the top vent valve in the process flange (see dimensional drawing). 3) Not in conjunction with max. span 20 and 60 mbar (8.03 und 24.09 inH2O)) 4) When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 5) If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 6) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF443.-..Y..-.... und 7MF4900-1...-.B 7) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 8) Not in conjunction with Electrical connection "Screwed gland Pg 13.5" and "Han7D plug". 9) Without cable gland, with blanking plug 10) With enclosed cable gland Ex ia and blanking plug 11) Configurations 2 3 in connection with IP65. 13) Only in connection with Ex approval A, B or E. 14) Permissible 1 2 A B D P E R F S NC with HAN and M12 connectors are only available in Ex ic. 12) Only only for crimp-contact of conductor cross-section 1 mm2 15) Only in connection with Ex approval A, B, E or F. 16) M12 delivered without cable socket. © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for differential pressure and flow Selection and Ordering data Article No. Selection and Ordering data Pressure transmitters for differential pressure and flow PN 32/160 (MAWP 464/2320 psi) SITRANS P DS III with PROFIBUS PA (PA) SITRANS P DS III with FOUNDATION Fieldbus (FF) Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Silicone oil Inert liquid1) Measuring cell cleaning normal grease-free to cleanliness level 2 Pressure transmitters for differential pressure and flow PN 32/160 (MAWP 464/2320 psi) 7MF 4 4 3 4 - SITRANS P DS III with PROFIBUS PA (PA) 7MF 4 4 3 5 - SITRANS P DS III with FOUNDATION Fieldbus (FF) 77777 - 7777 1 3 B PN 160 (MAWP 2320 psi) 60 mbar (24.09 inH2O) 250 mbar (100.4 inH2O) 600 mbar (240.9 inH2O) 1600 mbar (642.4 inH2O) 5 bar (2008 inH2O) 30 bar (435 psi) C D E F G H - Mounting thread M10 to DIN 19213 (only for replacement requirement) 7MF 4 4 3 5 77777 - 7777 Display • Without display • Without visible display (display concealed, setting: bar) • With visible display (setting: bar) • With customer-specific display (setting as specified, Order code "Y21" required) B C F 0 1 6 7 Included in delivery of the device: • Brief instructions (Leporello) • CD-ROM with detailed documentation • Sealing plug(s) or sealing screw(s) for the process flanges(s) Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Process connection Female thread ¼-18 NPT with flange connection • Sealing screw opposite process connection - Mounting thread 7/16-20 UNF to IEC 61518 - Mounting thread M10 to DIN 19213 (only for replacement requirement) • Venting on side of process flanges2) - Mounting thread 7/16-20 UNF to IEC 61518 7MF 4 4 3 4 - Electrical connection/cable entry • Screwed gland M20 x 1.5 • Screwed gland ½-14 NPT • M12 connectors (stainless steel)12) 13) Nominal measuring range PN 32 (MAWP 464 psi) 20 mbar 2) (8.03 inH2O) Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Tantalum 3) Tantalum Monel3) Monel Gold 3) Gold Version as diaphragm seal 4) 5) 6) 7) Article No. A B C E H L Y 2 0 6 4 1) For oxygen application, add Order code E10. 2) Not suitable for connection of remote seal. Position of the top vent valve in the process flange (see dimensional drawing). 3) Not in conjunction with max. span 20 and 60 mbar (8.03 und 24.09 inH2O)) 4) When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 5) If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 6) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF443.-..Y..-.... und 7MF4900-1...-.B 7) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 8) Without cable gland, with blanking plug. 9) With enclosed cable gland Ex ia and blanking plug. 10) Configurations with HAN and M12 connectors are only available in Ex ic. 11) Only in connection with IP65. 12) Only in connection with Ex approval A, B, E or F. 13) M12 delivered without cable socket Non-wetted parts materials process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminum Stainless steel precision casting Version • Standard versions • International version, English label inscriptions, documentation in 5 languages on CD (no Order code selectable) Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" - "Explosion-proof (Ex d)"8) - "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"9) - "Ex nA/ic (Zone 2)" 10) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (Ex ia + Ex d + Zone 1D/2D)"9) 11)(not for DS III FF) • FM + CSA intrinsic safe (is) • FM + CSA (is + ep) + Ex ia + Ex d (ATEX)11) • With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)"8) 2 3 1 2 A B D P E R F S NC Siemens FI 01 · 2015 US Edition 1/143 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for differential pressure and flow Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. Pressure transmitter with mounting bracket (1x fixing angle, 2 x nut, 2 x Uwasher or 1 x bracket, 2 x nut, 2 x Uwasher) made of: • Steel • Stainless steel O-rings for process flanges (instead of FPM (Viton)) • PTFE (Teflon) • FEP (with silicone core, approved for food) • FFPM (Kalrez, compound 4079), for measured medium temperatures -15 ... 100 °C (5 ... 212 °F) • NBR (Buna N) Selection and Ordering data HART PA A01 A02 FF A20 A21 A22 A23 A30 A31 A32 A33 Sealing screws (2 units) ¼-18 NPT, with valve in mat. of process flanges A40 Cable sockets for M12 connectors (metal (CuZn)) A50 B11 B12 B13 B14 B16 English rating plate Pressure units in inH2O and/or psi B21 Quality inspection certificate (Five-step factory calibration) to IEC 60770-21) C11 Inspection certificate2) to EN 10204-3.1 C12 Factory certificate to EN 10204-2.2 C14 Functional safety (SIL2) Devices suitable for use according to IEC 61508 and IEC 61511. Includes SIL conformity declaration C20 Functional safety (PROFIsafe) Certificate and PROFIsafe protocol C213) Functional safety (SIL2/3) Devices suitable for use according to IEC 61508 and IEC 61511. Includes SIL conformity declaration C23 Device passport Russia (For price request please contact the technical support www.siemens.com/automation/supportrequest) C99 plug • Han 7D (metal) • Han 8D (instead of Han 7D) • Angled • Han 8D (metal) Rating plate inscription (instead of German) • English • French • Spanish • Italian • Cyrillic (russian) 1/144 Siemens FI 01 · 2015 US Edition Order code Further designs Add "-Z" to Article No. and specify Order code. HART PA FF Setting of upper limit of output signal to 22.0 mA D05 Manufacturer's declaration acc. to NACE (MR 0103-2012 and MR 0175-2009) (only together with seal diaphragm made of Hastelloy and stainless steel) D07 Degree of protection IP66/IP68 (only for M20 x 1.5 and ½-14 NPT) D12 Process flange screws made of Monel (max. nominal pressure PN20) D34 Supplied with oval flange set (2 items), PTFE packings and screws in thread of process flanges D37 Capri cable gland 4F CrNi and clamping device (848699 + 810634) included D59 Use in or on zone 1D/2D (only together with type of protection "Intrinsic safety" (transmitter 7MF4...-.....-.B.. Ex ia)“and IP65) E01 Overfilling safety device for flammable and non-flammable liquids (max. PN 32 (MAWP 464 psi), basic device with type of protection "Intrinsic safety (Ex ia)", to WHG and VbF, not together with measuring cell filling "inert liquid") E08 Oxygen application (In the case of oxygen measurement and inert liquid max. 100 bar (1450 psi) at 60°C (140 °F)) E10 Export approval Korea E11 CRN approval Canada (Canadian Registration Number) E22 Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.B..) E254) "Flameproof" explosion protection according to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.D..) E264) Explosion-proof "Intrinsic safety" (Ex ia + Ex d) to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.P..) E284) Ex Approval IEC Ex (Ex ia) (only for transmitter 7MF4...-.....-.B..) E454) Ex Approval IEC Ex (Ex d) (only for transmitter 7MF4...-.....-.D..) E464) Explosion-proof "Intrinsic safety" to NEPSI (China) (only for transmitter 7MF4...-.....-.B..) E554) Explosion protection "Explosion-proof" to NEPSI (China) (only for transmitter 7MF4...-.....-.D..) E564) Explosion-proof "Zone 2" to NEPSI (China) (only for transmitter 7MF4...-.....-.E..) E574) Ex protection „Ex ia“, „Ex d“ and „Zone 2“ to NEPSI (China) (only for transmitter 7MF4...-.....-.R..) E584) "Intrinsic safety" and "Explosion-proof" explosion protection acc. to Kosha (Korea) (only for transmitter 7MF4...-.....-.[B, D]..-Z + E11) E704) © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for differential pressure and flow Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. Selection and Ordering data HART PA FF Additional data Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Specify in plain text: • in the case of linear characteristic curve (max. 5 characters): Y01: ... up to ... mbar, bar, kPa, MPa, psi • in the case of square rooted characteristic (max. 5 characters): Y02: ... up to ... mbar, bar, kPa, MPa, psi Two coats of lacquer on casing and cover (PU on epoxy) G10 Interchanging of process connection side H01 Vent on side for gas measurements H02 Stainless steel process flanges for vertical differential pressure lines (not together with K01, K02 and K04)5) H03 Transient protector 6 kV (lightning protection) J01 Chambered graphite gasket for process flange J02 Chambered PTFE graphite gasket J03 EPDM O-rings for process flange with approval (WRC/WRAS) J05 Vent valve or blanking plug of process flange welded-in (orientation: on right when viewing the display)6) J08 Vent valve or blanking plug of process flange welded-in (orientation: on left when viewing the display)6) J09 K01 K02 K04 Process flange • Hastelloy • Monel • Stainless steel with PVDF insert max. PN 10 (MAWP 145 psi), max. temperature of medium 90 °C (194 °F) For ½-14 NPT inner process connection on the side in the middle of the process flange, vent valve not possible Factory mounting of valve manifolds, see accessories. Supplementary electronics for 4-wire connection, see accessories. = available 1) 2) When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. Order code HART PA FF 1) Y01 Y02 Stainless steel tag plate and entry in device variable (measuring point description) Max. 16 characters, specify in plain text: Y15: ........................................... Y15 Measuring point text (entry in device variable) Max. 27 char., specify in plain text: Y16: ....... Y16 Entry of HART address (TAG) Max. 8 char., specify in plain text: Y17: ....... Y17 Setting of pressure indicator in pressure units Specify in plain text (standard setting: bar): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, Torr, ATM or % *) ref. temperature 20 °C Y21 Setting of pressure indicator in nonpressure units2) Specify in plain text: Y22: ..... up to ..... l/min, m3/h, m, USgpm, ... (specification of measuring range in pressure units "Y01" or "Y02" is essential, unit with max. 5 characters) Y223) + Y01 or Y02 Preset bus address possible between 1 and 126 Specify in plain text: Y25: ..................... Y25 Damping adjustment in seconds (0 ... 100 s) Y30 Factory mounting of valve manifolds, see accessories. Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 und D05 can be factory preset 3) Profisafe transmitters can only be operated with the S7 F Systems V6.1 configuration software in combination with S7-400H = available 4) Option does not include ATEX approval, but instead includes only the countryspecific approval. 1) 5) Not suitable for connection of remote seal. 6) Blanking plug is standard configuration. Order option A40 if a vent valve is required instead of a blanking plug. Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are calculated in the same way as for HART devices. 2) Preset values can only be changed over SIMATIC PDM. 3) Not in conjunction with over-filling safety device for flammable and nonflammable liquids (Order code "E08") Siemens FI 01 · 2015 US Edition 1/145 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for differential pressure and flow Selection and Ordering data Article No. Selection and Ordering data Article No. SITRANS P DS III with HART pressure transmitters for differential pressure and flow, PN 420 (MAWP 6092 psi) 7MF 4 5 3 3 - SITRANS P DS III with HART pressure transmitters for differential pressure and flow, PN 420 (MAWP 6092 psi) 7MF 4 5 3 3 - 77777 - 7777 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Silicone oil Measuring cell cleaning normal Measuring span (min. ... max.) 2.5 ... 250 mbar (1.004 ... 100.4 inH2O) 6 ... 600 mbar (2.409 ... 240.9 inH2O) 16 ... 1600 mbar (6.424 ... 642.4 inH2O) 50 ... 5000 mbar (20.08 ... 2008 inH2O) 0.3 ... 30 bar (4.35 ... 435 psi) Display • Without display • Without visible display (display concealed, setting: mA) • With visible display (setting: mA) • with customer-specific display (setting as specified, Order code "Y21" or "Y22" required) 1 D E F G H Process connection Female thread ¼-18 NPT with flange connection • Sealing screw opposite process connection - Mounting thread 7/16-20 UNF to IEC 61518 - Mounting thread M12 to DIN 19213 (only for replacement requirement) • Venting on side of process flanges, location of vent valve at top of process flanges (see dimensional drawing) - Mounting thread 7/16-20 UNF to IEC 61518 - Mounting thread M12 to DIN 19213 (only for replacement requirement) Die-cast aluminum Stainless steel precision casting6) Version • Standard versions • International version, English label inscriptions, documentation in 5 languages on CD (no Order code selectable) Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" - "Explosion-proof (Ex d)"7) - "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"8) - "Ex nA/ic (Zone 2)"9) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (Ex ia+ Ex d + Zone 1D/2D)"8)10) • FM + CSA intrinsic safe (is) • FM + CSA (is + ep) + Ex ia + Ex d (ATEX)10) • With FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 7), max PN 360 Electrical connection/cable entry • Screwed gland Pg 13.511) • Screwed gland M20x1.5 • Screwed gland ½-14 NPT • Han 7D plug (plastic housing) incl. mating connector11)12) • M12 connectors (stainless steel)13) 14) 1/146 Siemens FI 01 · 2015 US Edition 6 7 Scope of delivery: Pressure transmitter as ordered (Instruction Manual is extra ordering item) A B L Y 3 1 7 5 1) Not in conjunction with max. span 600 mbar (240.9 inH2O) 2) When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 3) If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 4) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF453.-..Y..-.... und 7MF4900-1....-.B 5) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 6) Not in conjunction with Electrical connection "Screwed gland Pg 13.5" and "Han7D plug". 7) Without cable gland, with blanking plug 8) With enclosed cable gland Ex ia and blanking plug 9) Configurations with HAN and M12 connectors are only available in Ex ic. 10) Only in connection with IP65. 11) Only in connection with Ex approval A, B or E. 12) Permissible Non-wetted parts materials process flange screws Electronics housing Stainless steel Stainless steel 0 1 Power supply units see Chap. 7 "Supplementary Components". Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel Hastelloy Stainless steel Gold1) Gold Ausführung als Membrandruckmittler 2) 3) 4) 5) 77777 - 7777 2 3 1 2 A B D P E R F S NC A B C D F only for crimp-contact of conductor cross-section 1 mm2 13) Only in connection with Ex approval A, B, E or F. 14) M12 delivered without cable socket. © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for differential pressure and flow Selection and Ordering data Article No. Selection and Ordering data Pressure transmitters for differential pressure and flow, PN 420 (MAWP 6092 psi) Article No. Pressure transmitters for differential pressure and flow, PN 420 (MAWP 6092 psi) SITRANS P DS III with PROFIBUS PA (PA) 7MF 4 5 3 4 - SITRANS P DS III with PROFIBUS PA (PA) 7MF 4 5 3 4 - SITRANS P DS III with FOUNDATION Fieldbus (FF) 7MF 4 5 3 5 - SITRANS P DS III with FOUNDATION Fieldbus (FF) 7MF 4 5 3 5 - Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Nominal measuring range 250 mbar (100.4 inH2O) 600 mbar (240.9 inH2O) 1600 mbar (642.4 inH2O) 5 bar (2008 inH2O) 30 bar (435 psi) 1 7777 - 7777 D E F G H Process connection Female thread ¼-18 NPT with flange connection • Sealing screw opposite process connection - Mounting thread 7/16-20 UNF to IEC 61518 - Mounting thread M12 to DIN 19213 (only for replacement requirement) • Venting on side of process flanges, location of vent valve at top of process flanges (see dimensional drawing). - Mounting thread 7/16-20 UNF to IEC 61518 - Mounting thread M12 to DIN 19213 (only for replacement requirement) A B L Y 3 1 7 5 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminum Stainless steel precision casting Version • Standard versions • International version, English label inscriptions, documentation in 5 languages on CD (no Order code selectable) Explosion protection • None • With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" - "Explosion-proof (Ex d)"6) - "Intrinsic safety and flameproof enclosure" (Ex ia + Ex d)"7) - "Ex nA/ic (Zone 2)" 8) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (Ex ia + Ex d + Zone 1D/2D)"7) 9) (not for DS III FF) • FM + CSA intrinsic safe (is) • FM + CSA (is + ep) + Ex ia + Ex d (ATEX)9) • With FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)"6), max PN 360 Electrical connection/cable entry • Screwed gland M20 x 1.5 • Screwed gland ½-14 NPT • M12 connectors (stainless steel) 10) 11) 0 1 6 7 Included in delivery of the device: • Brief instructions (Leporello) • CD-ROM with detailed documentation • Sealing plug(s) or sealing screw(s) for the process flanges(s) Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel Hastelloy Stainless steel Gold 1) Gold Ausführung als Membrandruckmittler 2) 3) 4) 5) 1 7777 - 7777 Display • Without (display hidden) • Without visible display (display concealed, setting: bar) • With visible display (setting: bar) • With customer-specific display (setting as specified, Order code "Y21" required) 2 3 1) Not in conjunction with max. span 600 mbar (240.9 inH2O) 2) When the manufacture’s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 3) If the acceptance test certificate 3.1.is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 4) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF453.-..Y..-.... und 7MF4900-1....-.B 5) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 6) Without cable gland, with blanking plug. 7) With enclosed cable gland Ex ia and blanking plug. 8) Configurations with HAN and M12 connectors are only available in Ex ic. 9) Only in connection with IP65. 10) Only in connection with Ex approval A, B, E or F. 11) M12 delivered without cable socket 1 2 A B D P E R F S NC B C F Siemens FI 01 · 2015 US Edition 1/147 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 1 SITRANS P DS III for differential pressure and flow Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. Pressure transmitter with mounting bracket (1x fixing angle, 2 x nut, 2 x Uwasher or 1 x bracket, 2 x nut, 2 x Uwasher) made of: • Steel • Stainless steel O-rings for process flanges (instead of FPM (Viton)) • PTFE (Teflon) • FEP (with silicone core, approved for food) • FFPM (Kalrez, compound 4079), for measured medium temperatures -15 ... 100 °C (5 ... 212 °F) • NBR (Buna N) Selection and Ordering data HART PA A01 A02 FF A20 A21 A22 A23 A30 A31 A32 A33 Sealing screws (2 units) A40 ¼-18 NPT, with valve in mat. of process flanges Cable sockets for M12 connection (metal (CuZn)) Plug • Han 7D (metal) • Han 8D (instead of Han 7D) • Angled • Han 8D (metal) Rating plate inscription (instead of German) • English • French • Spanish • Italian • Cyrillic (russian) A50 B11 B12 B13 B14 B16 English rating plate Pressure units in inH2O and/or psi B21 Quality inspection certificate (Five-step factory calibration) to IEC 60770-2 C11 Inspection certificate Acc. to EN 10204-3.1 C12 Factory certificate Acc. to EN 10204-2.2 C14 Functional safety (SIL2) C20 Devices suitable for use according to IEC 61508 and IEC 61511. Includes SIL conformity declaration Functional safety (PROFIsafe) Certificate and PROFIsafe protocol C211) Functional safety (SIL2/3) C23 Devices suitable for use according to IEC 61508 and IEC 61511. Includes SIL conformity declaration Device passport Russia (For price request please contact the technical support www.siemens.com/automation/supportrequest) C99 Setting of upper limit of output signal to 22.0 mA D05 Manufacturer's declaration acc. to NACE (MR 0103-2012 and MR 0175-2009) (only together with seal diaphragm made of Hastelloy and stainless steel) D07 Degree of protection IP66/IP68 (only for M20 x 1.5 and ½-14 NPT) D12 Nom. press. rating PN 500 (MAWP 7250 psi) D56 (Only for measuring cell 600 mbar ... 30 bar (240 inH2O ... 435 psi), SIL- und Ex-options not possible))2) Capri cable gland 4F CrNi and clamping device (848699 + 810634) included 1/148 Siemens FI 01 · 2015 US Edition HART PA FF Use in or on zone 1D/2D (only together with type of protection "Intrinsic safety" (transmitter 7MF4...-.....-.B.. Ex ia)“and IP65) E01 Export approval Korea E11 Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) to E253) INMETRO (Brazil) (only for transmitter 7MF4...-.....-.B..) "Flameproof" explosion protection accord- E263) ing to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.D..) Explosion-proof "Intrinsic safety" (Ex ia + Ex d) to INMETRO (Brazil) (only for transmitter 7MF4...-.....-.P..) E283) Ex Approval IEC Ex (Ex ia) (only for transmitter 7MF4...-.....-.B..) E453) Ex Approval IEC Ex (Ex d) (only for transmitter 7MF4...-.....-.D..) E463) Explosion-proof "Intrinsic safety" to NEPSI (China) (only for transmitter 7MF4...-.....-.B..) E553) Ex prot. "Explosion-proof" to NEPSI (China) E563) (only for transmitter 7MF4...-.....-.D..) Explosion-proof "Zone 2" to NEPSI (China) E573) (only for transmitter 7MF4...-.....-.E..) Ex protection „Ex ia“, „Ex d“ and „Zone 2“ E583) to NEPSI (China) (only for transmitter 7MF4...-.....-.R..) "Intrinsic safety" and "Explosion-proof" explosion protection acc. to Kosha (Korea) (only for transmitter 7MF4...-.....-.[B, D]..-Z + E11) E703) Two coats of lacquer on casing and cover (PU on epoxy) G10 Interchanging of process connection side H01 Stainless steel process flanges for vertical H03 differential pressure lines Transient protector 6 kV (lightning protec- J01 tion) Chambered graphite gasket for process flange J02 EPDM O-rings for process flange with approval (WRC/WRAS) J05 Vent valve or blanking plug of process flange welded-in (orientation: on right when viewing the display)4) J08 Vent valve or blanking plug of process J09 flange welded-in (orientation: on left when 4) viewing the display) 1) D59 Order code Further designs Add "-Z" to Article No. and specify Order code. Profisafe transmitters can only be operated with the S7 F Systems V6.1 configuration software in combination with S7-400H Tested according to IEC 61010. Only for measuring materials of the group of fluids 2 in accordance with PED permissible. Not for use with dangerous media suitable. 3) Option does not include ATEX approval, but instead includes only the country-specific approval. 4) Blanking plug is standard configuration. Order option A40 if a vent valve is required instead of a blanking plug. 2) © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for differential pressure and flow Selection and Ordering data Order code Additional data HART PA FF Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Specify in plain text: • in the case of linear characteristic curve (max. 5 characters): Y01: ... up to ... mbar, bar, kPa, MPa, psi • in the case of square rooted characteristic (max. 5 characters): Y02: ... up to ... mbar, bar, kPa, MPa, psi 1) Y01 Y02 Y15 Measuring point text (entry in device vari- Y16 able) Max. 27 char., specify in plain text: Y16: ....... Entry of HART address (TAG) Y17 Max. 8 char., specify in plain text: Y17: ......... Setting of pressure indication in pressure Y21 units Specify in plain text (standard setting: bar): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, Torr, ATM or % *) ref. temperature 20 °C Setting of pressure indication in Y22 + non-pressure units2) Y01 or Y02 Specify in plain text: 3 Y22: ..... up to ..... l/min, m /h, m, USgpm, ... (specification of measuring range in pressure units "Y01" or "Y02" is essential, unit with max. 5 characters) Stainless steel tag plate and entry in device variable (measuring point description) Max. 16 characters, specify in plain text: Y15: ........................................... Preset bus address possible between 1 and 126 Specify in plain text: Y25: ..................... Y25 Damping adjustment in seconds (0 ... 100 s) Y30 Factory mounting of valve manifolds, see accessories. Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 and D05 can be factory preset. = available 1) 2) Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are calculated in the same way as for HART devices. Preset values can only be changed over SIMATIC PDM. Siemens FI 01 · 2015 US Edition 1/149 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements SITRANS P DS III for differential pressure and flow ■ Dimensional drawings 143 (5.6) 1 5 2 29 (1.14) 4) 84 (3.31) 6 3 7 8 166 (6.54) 53 (2.1) 24 (0.94) 69 (2.7) 50 (1.97) 128 (5.04) 15 (0.6) Ø80 (3.15) 12 10 11 52 (2.05) 3 17 (0.67) 4 72 (2.83) 68 (2.7) 105 (4.1) Electronic side, digital display (longer overall length for cover with window)1) 2 Terminal side1) 3 Electrical connection: Screwed gland Pg 13,5 (adapter)(Adapter)2) 3), Screwed gland M20 x 1,5 or Screwed gland ½-14 NPT or Han 7D/ Han 8D2) 3) plug 120 (4.7) 6 Blanking plug 7 Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 8 Lateral venting for liquid measurement (Standard) 9 Lateral venting for gas measurement (suffix H02) 10 Mounting bracket (option) Harting adapter 11 Sealing screw with valve (option) 5 Protective cover over keys 12 Process connection: ¼-18 NPT (IEC 61518) 1) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing Not with type of protection "Explosion-proof enclosure" Not with type of protection "FM + CSA" [IS + XP]" For Pg 13,5 with adapter approx. 45 mm (1.77 inch) 92 mm (3.62 inch) for minimum distance to permit rotation with indicator 4 2) 3) 4) 5) SITRANS P DS III pressure transmitters for differential pressure and flow, dimensions in mm (inch) 1/150 Siemens FI 01 · 2015 US Edition 96 (3.8) Space for rotation of housing 9 approx. 96 (3.78) 1 262 (10.3) min. 90 (3.54) 5) 134 (5.28) 1 © Siemens AG 2015 Pressure Measurement Transmitters for general requirements 143 (5.6) 53 (2.1) 17 (0.67) 29 (1.14) 8) 5 84 (3.31) Ø80 (3.15) 50 (1.97) 1 approx. 96 (3.78) 6 3 4 3 7 2 min. 90 (3.54) 4) approx. 85 (3.35) 6) Space for rotation of housing 8 8 128 (5.04) approx. 217 (8.54) 7) 15 (0.6) 24 (0.94) SITRANS P DS III for differential pressure and flow 9 60 (2.36) 5) approx. 87 (3.43) 65 (2.56) Electronic side, digital display (longer overall length for cover with window)1) 5 Protective cover over keys 6 Blanking plug 2 Terminal side1) 7 3 Electrical connection: Screwed gland Pg 13,5 (adapter)(Adapter)2) 3), Screwed gland M20 x 1,5 or Screwed gland ½-14 NPT or Han 7D/ Han 8D2) 3) plug Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 8 Sealing screw with valve (option) 9 Process connection: ¼-18 NPT (IEC 61518) 1 4 Harting adapter 1) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing Not with type of protection "Explosion-proof enclosure" Not with type of protection "FM + CSA" [IS + XP]" 92 mm (3.6 inch) for minimum distance to permit rotation with indicator 74 mm (2.9 inch) for PN ≥ 420 (MAWP ≥ 6092 psi) 91 mm (3.6 inch) for PN ≥ 420 (MAWP ≥ 6092 psi) 219 mm (8.62 inch) for PN ≥ 420 (MAWP ≥ 6092 psi) For Pg 13,5 with adapter approx. 45 mm (1.77 inch) 2) 3) 4) 5) 6) 7) 8) SITRANS P DS III pressure transmitters for differential pressure and flow, with process covers for vertical differential pressure lines, optional "H03" , dimensional drawing, dimensions in mm (inch) SITRANS P DS III pressure transmitters for differential pressure and flow, with process covers for vertical differential pressure lines Siemens FI 01 · 2015 US Edition 1/151 1