Download

Datasheet
connectPower PROmax
Single- and three-phase switched-mode power supply units
NEW
The new PROmax power supplies offer a wide range of robust
solutions for demanding application requirements.
Designed for high performance and durability, PROmax switchmode power supply units reliably provide continuous overload
currents of up to 120%, or supply short-term peak loads up to
300% of nominal power.
Features include high output power boost capability and maximum
power within a wide operating temperature range. PROmax switchmode power supply units are suited for use in most global
applications, and their compact size offers valuable space saving.
The PROmax power supplies, together with Weidmuller’s
uninterruptible DC UPSs, diode modules, and/or CAP modules,
offer users the ability to tailor solutions for their unique and
demanding power requirements.
C
US
SEMI F47
Weidmuller, Canada
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (877) 300-5635
Email: [email protected]
Website: www.weidmuller.ca
Weidmuller, Mexico
Blvd. Hermanos Serdán 698,
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: [email protected]
Website: www.weidmuller.com.mx
Features:
• Small housing: 32 mm – 140 mm widths
• MTBF: >500,000 hours
•Wide temperature range: -25°C …+70°C (Derating >60°C);
startup at -40°C and above
• 16 variants offer application flexibility:
− single-phase input: 24 V: 3…40 A, 5 V: 14 A,
12 V: 6…10 A, 48 V: 5…20 A
− three-phase input : 24 V: 5…40 A
•Wide input ranges: 85…277 V AC/320 ...575 V AC,
80…370 V DC/450…800 V DC
• External monitoring with relay (Change over contact)
• Capable of parallel and series output connections
• Bi-color LED status indicator
• International approvals:
− cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
• Shock and vibration resistant
•Powerful output surge capability: 120% min.1 min (permanent
< +45°C), 150% min 4s, 300% min 2ms
• Installation manual available via QR code
Weidmuller, United States
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: [email protected]
Website: www.weidmuller.com
connectPower PROmax switched-mode power supply unit
connectPower
PROmax
Derating curve
Technical data
/RDG
7HPSƒ&
Max. limiting average on state
current [A]
Typ\Temp.
45°C
1ph 24 V / 3 A 3.6
1ph 24 V / 5 A
6
1ph 24 V / 7.5 A 9
1ph 24 V / 10 A 12
1ph 24 V / 20 A 24
1ph 24 V / 40 A 48
1ph 5 V / 14 A 16.8
1ph 12 V / 6 A 7.2
1ph 12 V / 10 A 12
1ph 48 V / 5 A
6
1ph 48 V / 10 A 12
1ph 48 V / 20 A 24
3ph 24 V / 5 A
6
3ph 24 V / 10 A 12
3ph 24 V / 20 A 24
3ph 24 V / 40 A 48
2
50°C
3.3
5.7
8.5
11.3
22.6
45.2
15.8
6.8
11.3
5.7
11.3
22.6
5.7
11.3
22.6
45.2
55°C
3.2
5.4
8
10.7
21.4
42.8
15
6.4
10.7
5.4
10.7
21.4
5.4
10.7
21.4
42.8
60°C
3
5
7.5
10
20
40
14
6
10
5
10
20
5
10
20
40
65°C
2.6
4.4
6.6
8.8
17.6
35.2
12.3
5.3
8.8
4.4
8.8
17.6
4.4
8.8
17.6
35.2
70°C
2.2
3.8
5.6
7.5
15
30
10.5
4.5
7.5
3.8
7.5
15
3.8
7.5
15
30
General technical data
Current limiting
Insulation voltage input ground
Insulation voltage output ground
Insulation voltage input/output
Earth leakage current
Series switching capability
Ambient temp. operating /
storage temperature / Start up
Humidity at operating temperature
Class of protection / Pollution degree
MTBF
Housing version
Status indication
Mounting position, installation notice
EMC / shock / vibration
Noise immunity tests acc. to
Resistance against vibration and shock
Electrical safety (applied standards)
Electrical equipment of machines
Safety transformers for switched-mode power units
Machinery with electronic equipment
Safety extra-low voltage
Protective separation /
protection against electrical shock
Protection against dangerous shock currents
Additional Information on
Major North American Approvals
cULus Listed file E258476 according to UL508 and
CSA C22.2 No. 107.1; cURus file E255651 according to
UL60950-1 and CSA C22.2 No. 60950-1; cULus C1D2
file E470829 according to ISA12.12.01 and
CSA C22.2 No. 213
> 120% IN
3.5 kV
0.5 kV
4 kV
3.5 mA
Yes
-25°C...+70°C / -40°C...+85°C / ≥ -40°C
5...95%, no condensation
I/2
>500,000h (25°C, IEC 61709)
Metal, corrosion resistant
LED red/green and relay (≥21.6 V DC LED green, relay
on/ ≤20.6 LED red, relay off)
Horizontal on TS35 mounting rail, with 50 mm of
clearance at top and bottom for air circulation. Can be
mounted side by side with no space in between.
EN55024; EN55022; IEC61000-3-2,-3; IEC61000-42,-3,-4,-5,-6,-8,-11
2.3 g / 30 g in all directions
Acc. to EN60204
Acc. to EN61558-2-16
Acc. to EN50178 / VDE0160
SELV acc. to EN60950, PELV acc. to EN60204,
IEC61204
VDE0100-410 / acc. to DIN57100-410
Acc. to VDE0106-101
connectPower PROmax switched-mode power supply unit
PRO MAX 72W 24V 3A
connectPower
PROmax
PRO MAX 120W 24V 5A
Similar
to illustration
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Similar
to illustration
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continuous output current @ URated
Power boost @ URated
Pulsed current capacity @ URated
General data
Degree of efficiency
Power factor (approx.)
AC failure bridging time @ INom
Protection against reverse voltages from the load
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Screwdriver blade
mm²
mm²
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
1 A @ 230 V AC / 1.5 A @ 115 V AC
1 A @ 370 V DC / 1.5 A @ 120 V DC
T3.15 A/250 V AC / max. 15 A
6 A, Char. B, circuit breaker, 3 - 5 A Char. C,
circuit breaker
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
1 A @ 230 V AC / 2.5 A @ 115 V AC
1.5A @ 370 V DC / 2.5 A @ 120 V DC
T3.15 A/250 V AC / max. 15 A
6 A, Char. B, circuit breaker, 6 A, char. C
circuit breaker
24 V DC ± 1%
22.5...29.5 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
3 A @ 60°C
3.6 A @ 45°C, 2.25 A @ 70°C
3.6 A (1 min), 4.5 A (4s)
9 A (2ms)
24 V DC ± 1%
22.5...29.5 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
5 A @ 60°C
6.0 A @ 45°C, 3.75 A @ 70°C
6 A (1 min), 7.5 A (4s)
15 A (2ms)
90%
> 0.90 @ 230 V AC
min. 20 ms
30…35 V DC
yes, max. 5
125 / 32 / 130 mm
0.6 kg
90%
> 0.90 @ 230 V AC
min. 20 ms
30…35 V DC
yes, max. 5
125 / 40 / 130 mm
0.8 kg
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.5 / 6
0.22 / 4
0.5 / 4
26 / 10
26 / 12
0.8 x 4.0, PZ 1
0.6 x 3.5
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.5 / 6
0.22 / 4
0.5 / 4
26 / 10
26 / 12
0.8 x 4.0, PZ 1
0.6 x 3.5
Type
PRO MAX 72W 24V 3A
Type
PRO MAX 120W 24V 5A
Ordering data
Note:
Qty.
1
Part No.
1478100000
Qty.
1
Part No.
1478110000
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
Metal Din-Rail Mounting Foot
Metal Din-Rail Mounting Foot
Accessories
3
connectPower PROmax switched-mode power supply unit
PRO MAX 180W 24V 7.5A
connectPower
PROmax
PRO MAX 240W 24V 10A
Similar
Similar
to illustration
to illustration
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continuous output current @ URated
Power boost @ URated
Pulsed current capacity @ URated
General data
Degree of efficiency
Power factor (approx.)
AC failure bridging time @ INom
Protection against reverse voltages from the load
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Screwdriver blade
mm²
mm²
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
1 A @ 230 V AC / 2 A @ 115 V AC
1 A @ 370 V DC / 2 A @ 120 V DC
T3.15 A/250 V AC / max. 15 A
10 A, char. B circuit breaker, 6…8 A, char.
C circuit breaker
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
1.5 A @ 230 V AC / 3 A @ 115 V AC
1.5 A @ 370 V DC / 3 A @ 120 V DC
T3.15 A/250 V AC / max. 15 A
10 A, char. B circuit breaker, 6…8 A, char.
C circuit breaker
24 V DC ± 1%
22.5...29.5 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
7.5 A @ 60°C
9 A @ 45°C, 5.6 A @ 70°C
9 A (1 min), 11.25 A (4s)
22.5 A (2ms)
24 V DC ± 1%
22.5...29.5 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
10 A @ 60°C
12 A @ 45°C, 7.5 A @ 70°C
12 A (1 min), 15 A (4s)
30 A (2ms)
91%
> 0.95 @ 230 V AC
min. 20 ms
30…35 V DC
yes, max. 5
125 / 50 / 130 mm
0.9 kg
91%
> 0.95 @ 230 V AC
min. 20 ms
30…35 V DC
yes, max. 5
125 / 60 / 130 mm
1 kg
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.5 / 6
0.22 / 4
0.5 / 4
26 / 10
26 / 12
0.8 x 4.0, PZ 1
0.6 x 3.5
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.18 / 6
0.22 / 4
0.22 / 4
26 / 10
26 / 10
0.8 x 4.0, PZ 1
0.8 x 4.0, PZ 1
Type
PRO MAX 180W 24V 7.5A
Type
PRO MAX 240W 24V 10A
Ordering data
Note:
Accessories
4
Qty.
1
Part No.
1478120000
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
Qty.
1
Part No.
1478130000
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
connectPower PROmax switched-mode power supply unit
PRO MAX 480W 24V 20A
connectPower
PROmax
PRO MAX 960W 24V 40A
Similar
to illustration
Similar
to illustration
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continuous output current @ URated
Power boost @ URated
Pulsed current capacity @ URated
General data
Degree of efficiency
Power factor (approx.)
AC failure bridging time @ INom
Protection against reverse voltages from the load
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Screwdriver blade
mm²
mm²
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
2.3 A @ 230 V AC / 4.8 A @ 115 V AC
1.5 A @ 370 V DC / 4.8 A @ 120 V DC
T3.15 A/250 V AC / max. 15 A
16 A, Char. B circuit breaker, 10 A, char.
C circuit breaker
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
4.52 A @ 230 V AC / 10 A @ 115 V AC
2.8 A @ 370 V DC / 10 A @ 120 V DC
T3.15 A / 250 V AC / max. 15 A
20 A, char. B circuit breaker, 16 A, Char.
C circuit breaker
24 V DC ± 1%
22.5...29.5 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
20 A @ 60°C
24 A @ 45°C, 15 A @ 70°C
24 A (1 min), 30 A (4s)
60 A (2ms)
24 V DC ± 1%
22.5...29.5 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
40 A @ 60°C
48 A @ 45°C, 30 A @ 70°C
48 A (1 min), 60 A (4s)
120 A (2ms)
91.5%
> 0.95 @ 230 V AC
min. 20 ms
30…35 V DC
yes, max. 3
150 / 90 / 130 mm
1.95 kg
92.5%
> 0.95 @ 230 V AC
min. 20 ms
30…35 V DC
yes, max. 3
150 / 140 / 130 mm
3.4 kg
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.18 / 6
0.22 / 4
0.22 / 4
26 / 10
26 / 10
0.8 x 4.0, PZ 1
0.8 x 4.0, PZ 1
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.5 / 16
0.22 / 4
0.5 / 16
26 / 10
22 / 8
0.8 x 4.0, PZ 1
1.0 x 5.5
Type
PRO MAX 480W 24V 20A
Type
PRO MAX 960W 24V 40A
Ordering data
Note:
Qty.
1
Part No.
1478140000
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
Qty.
1
Part No.
1478150000
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
Accessories
5
connectPower PROmax switched-mode power supply unit
PRO MAX 70W 5V 14A
connectPower
PROmax
PRO MAX 72W 12V 6A
Similar
to illustration
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Similar
to illustration
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continuous output current @ URated
Power boost @ URated
Pulsed current capacity @ URated
General data
Degree of efficiency
Power factor (approx.)
AC failure bridging time @ INom
Protection against reverse voltages from the load
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Screwdriver blade
mm²
mm²
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
1 A @ 230 V AC / 1.5 A @ 115 V AC
1 A @ 370 V DC / 1.5 A @ 120 V DC
T3.15 A / 250 V AC / max. 15 A
6 A, Char. B, circuit breaker, 3 - 5 A Char. C, circuit
breaker
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
1 A @ 230 V AC / 1.5 A @ 115 V AC
1 A @ 370 V DC / 1.5 A @ 120 V DC
T3.15 A / 250 V AC / max. 15 A
6 A, Char. B, circuit breaker, 3 - 5 A Char. C, circuit
breaker
5 V DC
4.5...7 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
14 A @ 60°C
16.8 A @ 45°C, 10.5 A @ 70°C
16.8 A (1 min), 21 A (4s)
42 A (2ms)
12 V DC ± 1%
10...15 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
6 A @ 60°C
7.2 A @ 45°C, 4.5 A @ 70°C
7.2 A (1 min), 9 A (4s)
18 A (2ms)
86%
> 0.90 @ 230 V AC
min. 20 ms
> 7.5 V DC
yes, max. 5
125 / 32 / 130 mm
0.6 kg
89%
> 0.90 @ 230 V AC
min. 20 ms
> 18 V DC
yes, max. 5
125 / 32 / 130 mm
0.6 kg
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.5 / 6
0.22 / 4
0.5 / 4
26 / 10
26 / 12
0.8 x 4.0, PZ 1
0.6 x 3.5
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.5 / 6
0.22 / 4
0.5 / 4
26 / 10
26 / 12
0.8 x 4.0, PZ 1
0.6 x 3.5
Type
PRO MAX 70W 5V 14A
Type
PRO MAX 72W 12V 6A
Ordering data
Note:
Qty.
1
Part No.
1478210000
Part No.
1478220000
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
Metal Din-Rail Mounting Foot
Metal Din-Rail Mounting Foot
Accessories
6
Qty.
1
connectPower PROmax switched-mode power supply unit
PRO MAX 120W 12V 10A
connectPower
PROmax
PRO MAX 240W 48V 5A
Similar
to illustration
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Similar
to illustration
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continuous output current @ URated
Power boost @ URated
Pulsed current capacity @ URated
General data
Degree of efficiency
Power factor (approx.)
AC failure bridging time @ INom
Protection against reverse voltages from the load
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Screwdriver blade
mm²
mm²
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
1 A @ 230 V AC / 2.5 A @ 115 V AC
1.5 A @ 370 V DC / 2.5 A @ 120 V DC
T3.15 A / 250 V AC / max. 15 A
6 A, Char. B, circuit breaker, 6 A, char.
C circuit breaker
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
1.5 A @ 230 V AC / 3 A @ 115 V AC
1.5 A @ 370 V DC / 3 A @ 120 V DC
T3.15 A / 250 V AC / max. 15 A
10 A, char. B circuit breaker, 6…8 A, char.
C circuit breaker
12 V DC ± 1%
10...15 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
10 A @ 60°C
12 A @ 45°C, 7.5 A @ 70°C
12 A (1 min), 15 A (4s)
30 A (2ms)
48 V DC ± 1%
30...56 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
5 A @ 60°C
6.0 A @ 45°C, 3.75 A @ 70°C
5 A (1 min), 7.5 A (4s)
15 A (2ms)
89%
> 0.90 @ 230 V AC
min. 20 ms
> 18 V DC
yes, max. 5
125 / 40 / 130 mm
0.8 kg
91%
> 0.95 @ 230 V AC
min. 20 ms
58 … 65 V DC
yes, max. 5
125 / 60 / 130 mm
1 kg
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.5 / 6
0.22 / 4
0.5 / 4
26 / 10
26 / 12
0.8 x 4.0, PZ 1
0.6 x 3.5
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.18 / 6
0.22 / 4
0.22 / 4
26 / 10
26 / 10
0.8 x 4.0, PZ 1
0.8 x 4.0, PZ 1
Type
PRO MAX 120W 12V 10A
Type
PRO MAX 240W 48V 5A
Ordering data
Note:
Qty.
1
Part No.
1478230000
Qty.
1
Part No.
1478240000
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
Metal Din-Rail Mounting Foot
Metal Din-Rail Mounting Foot
Accessories
7
connectPower PROmax switched-mode power supply unit
PRO MAX 480W 48V 10A
connectPower
PROmax
PRO MAX 960W 48V 20A
Similar
to illustration
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Similar
to illustration
/
1²
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continuous output current @ URated
Power boost @ URated
Pulsed current capacity @ URated
General data
Degree of efficiency
Power factor (approx.)
AC failure bridging time @ INom
Protection against reverse voltages from the load
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Screwdriver blade
mm²
mm²
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
2.3 A @ 230 V AC / 4.8 A @ 115 V AC
1.5 A @ 370 V DC / 4.8 A @ 120 V DC
T3.15 A / 250 V AC / max. 15 A
16 A, Char. B circuit breaker, 10 A, char.
C circuit breaker
100...240 V AC (wide-range input)
85…277 V AC
45…65 Hz
80...370 V DC
4.52 A @ 230 V AC / 10 A @ 115 V AC
2.8 A @ 370 V DC / 10 A @ 120 V DC
T3.15 A / 250 V AC / max. 15 A
20 A, char. B circuit breaker, 16 A, Char.
C circuit breaker
48 V DC ± 1%
30...56 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
10 A @ 60°C
12 A @ 45°C, 7.5 A @ 70°C
12 A (1 min), 15 A (4s)
60 A (2ms)
48 V DC ± 1%
30...56 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
20 A @ 60°C
24 A @ 45°C, 15 A @ 70°C
24 A (1 min), 30 A (4s)
60 A (2ms)
91.5%
> 0.95 @ 230 V AC
min. 20 ms
58 … 65 V DC
yes, max. 5
150 / 90 / 130 mm
1.95 kg
92.5%
> 0.95 @ 230 V AC
min. 20 ms
58 … 65 V DC
yes, max. 5
150 / 140 / 130 mm
3.4 kg
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.18 / 6
0.22 / 4
0.22 / 4
26 / 10
26 / 10
0.8 x 4.0, PZ 1
0.8 x 4.0, PZ 1
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
3 for L/N/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.5 / 16
0.22 / 4
0.5 / 16
26 / 10
22 / 8
0.8 x 4.0, PZ 1
1.0 x 5.5
Type
PRO MAX 480W 48V 10A
Type
PRO MAX 960W 48V 20A
Ordering data
Note:
Qty.
1
Part No.
1478250000
Part No.
1478270000
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
Metal Din-Rail Mounting Foot
Metal Din-Rail Mounting Foot
Accessories
8
Qty.
1
connectPower PROmax switched-mode power supply unit
PRO MAX3 120W 24V 5A
connectPower
PROmax
PRO MAX3 240W 24V 10A
Similar
to illustration
/
/²
/
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Similar
to illustration
/
/²
/
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continuous output current @ URated
Power boost @ URated
Pulsed current capacity @ URated
General data
Degree of efficiency
Power factor (approx.)
AC failure bridging time @ INom
Protection against reverse voltages from the load
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Screwdriver blade
mm²
mm²
3 x 400...3 x 500 V AC (wide-range input)
3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC
45…65 Hz
450...800 V DC (max. 500 V DC acc. to UL508)
0.28 A @ 3*500 V AC / 0.3 A @ 3*400 V AC
0.18 A @ 800 V DC / 0.3 A @ 450 V DC
T3.15 A / 250 V AC / max. 15 A
2…3 A, char. C circuit breaker
3 x 400...3 x 500 V AC (wide-range input)
3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC
45…65 Hz
450...800 V DC (max. 500 V DC acc. to UL508)
0.35 A @ 3*500 V AC / 0.4 A @ 3*400 V AC
0.35 A @ 800 V DC / 0.6 A @ 450 V DC
T3.15 A / 250 V AC / max. 15 A
3 - 5 A Char. C, circuit breaker
24 V DC ± 1%
22.5...29.5 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
5 A @ 60°C
6.0 A @ 45°C, 3.75 A @ 70°C
6 A (1 min), 7.5 A (4s)
15 A (2ms)
24 V DC ± 1%
22.5...29.5 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
10 A @ 60°C
12 A @ 45°C, 7.5 A @ 70°C
12 A (1 min), 15 A (4s)
30 A (2ms)
90%
> 0.50 @ 3*400 V AC
min. 20 ms
30…35 V DC
yes, max. 5
125 / 40 / 130 mm
0.65 kg
91%
> 0.75 @ 3*400 V AC
min. 20 ms
30…35 V DC
yes, max. 5
125 / 60 / 130 mm
1.3 kg
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.5 / 6
0.22 / 4
0.5 / 4
26 / 10
26 / 12
0.8 x 4.0, PZ 1
0.6 x 3.5
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.18 / 6
0.22 / 4
0.22 / 4
26 / 10
26 / 10
0.8 x 4.0, PZ 1
0.8 x 4.0, PZ 1
Type
PRO MAX3 120W 24V 5A
Type
PRO MAX3 240W 24V 10A
Ordering data
Note:
Qty.
1
Part No.
1478170000
Qty.
1
Part No.
1478180000
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
Metal Din-Rail Mounting Foot
Metal Din-Rail Mounting Foot
Accessories
9
connectPower PROmax switched-mode power supply unit
PRO MAX3 480W 24V 20A
connectPower
PROmax
PRO MAX3 960W 24V 40A
Similar
to illustration
/
/²
/
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Similar
to illustration
/
/²
/
$&
3(
²
²
²
'&
3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ
Technical data
Input
Rated input voltage
Input voltage range AC
Frequency range AC
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / Inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Residual ripple, breaking spikes
Rated (nominal) output current @ UNom
Continuous output current @ URated
Power boost @ URated
Pulsed current capacity @ URated
General data
Degree of efficiency
Power factor (approx.)
AC failure bridging time @ INom
Protection against reverse voltages from the load
Parallel connection option
Depth x width x height
Weight
Approvals
Approvals
Connection data
Connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
Screwdriver blade
mm²
mm²
3 x 400...3 x 500 V AC (wide-range input)
3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC
45…65 Hz
450...800 V DC (max. 500 V DC acc. to UL508)
0.7 A @ 3*500 V AC / 0.85 A @ 3*400 V AC
0.7 A @ 800 V DC / 1.2 A @ 450 V DC
T3.15 A / 250 V AC / max. 15 A
3 - 5 A Char. C, circuit breaker
3 x 400...3 x 500 V AC (wide-range input)
3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC
45…65 Hz
450...800 V DC (max. 500 V DC acc. to UL508)
1.3 A @ 3*500 V AC / 1.6 A @ 3*400 V AC
1.4 A @ 800 V DC / 2.4 A @ 450 V DC
T3.15 A / 250 V AC / max. 15 A
6…8 A, char. C circuit breaker
24 V DC ± 1%
22.5...29.5 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
20 A @ 60°C
24 A @ 45°C, 15 A @ 70°C
24 A (1 min), 30 A (4s)
60 A (2ms)
24 V DC ± 1%
22.5...29.5 V (adjustable via potentiometer)
< 50 mVss @ UNenn, Full Load
40 A @ 60°C
48 A @ 45°C, 30 A @ 70°C
48 A (1 min), 60 A (4s)
120 A (2ms)
91.5%
> 0.75 @ 3*400 V AC
min. 20 ms
30…35 V DC
yes, max. 3
150 / 70 / 130 mm
1.3 kg
92.5%
> 0.75 @ 3*400 V AC
min. 20 ms
30…35 V DC
yes, max. 3
150 / 140 / 130 mm
3.1 kg
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.18 / 6
0.22 / 4
0.22 / 4
26 / 10
26 / 10
0.8 x 4.0, PZ 1
0.8 x 4.0, PZ 1
cULus, cURus, TÜV, CE, CCC, SEMI F47, GL (EMC1),
Class1 Div2, RCM, Gost
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
8 (++,- - - ,11,13,14)
0.18 / 6
0.5 / 16
0.22 / 4
0.5 / 16
26 / 10
22 / 8
0.8 x 4.0, PZ 1
1.0 x 5.5
Type
PRO MAX3 480W 24V 20A
Type
PRO MAX3 960W 24V 40A
Ordering data
Note:
Qty.
1
Part No.
1478190000
Part No.
1478200000
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
The internal varistor found in a switch-mode power supply does not replace the need
for surge protection within a system.
Metal Din-Rail Mounting Foot
Metal Din-Rail Mounting Foot
Accessories
10
Qty.
1
connectPower PRO-M power supply unit
CP M DM20
PRO-M: diode, capacity
and relay modules
CP M DM40
Similar
to illustration
1+
Similar
to illustration
3+
4+
1+
11
3+
4+
11
12
14
12
14
12-
34-
12-
34-
21
21
22
24
22
24
2+
2+
Technical data
Input
Rated input voltage / DC input voltage range
Input current
Output
Rated output voltage / Output voltage
Rated (nominal) output current @ UNom
Continuous output current @ 24 V DC
Voltage monitoring / Floating contact
Switching thresholds
General data
Degree of efficiency
Depth x width x height / Weight
Ambient temperature (operational) /
Storage temperature
Humidity
Protection degree / Class of protection /
Pollution severity
Insulation voltage
MTBF
Mounting position, installation notice
EMC / shock / vibration
Noise emission acc. to EN55022
Interference immunity test acc. to
Resistance to vibration / Shock
Electrical safety (applied standards)
Electrical machine equipment
For use with electronic equipment
Safety extra-low voltage
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
mm²
mm²
24 V DC / 18…30 V DC
2 x 10 A or 1 x 20 A
24 V DC / 18…30 V DC
2 x 20 A or 1 x 40 A
24 V DC ± 1% / Input voltage - 0.7 V
20 A @ 60°C
24 A @ 45°C, 22.5 A @ 55°C, 15 A @ 70°C
Yes, In both inputs / Yes
21.6 V DC, relay is on for Power Good, 20.4 V DC,
relay is off for Power Fail
24 V DC ± 1% / Input voltage - 0.7 V
40 A @ 60°C
48 A @ 45°C, 45 A @ 55°C, 30 A @ 70°C
Yes, In both inputs / Yes
21.6 V DC, relay is on for Power Good, 20.4 V DC,
relay is off for Power Fail
> 97% @ 24 V input voltage
150 / 34 / 130 mm / 0.3 kg
-25°C...+70°C / -40°C...+85°C
> 97% @ 24 V input voltage
150 / 60 / 130 mm / 0.6 kg
-25°C...+70°C / -40°C...+85°C
5...95%, no condensation
IP 20 / III, with no ground connection, for SELV / 2
5...95%, no condensation
IP 20 / III, with no ground connection, for SELV / 2
0.5 kV Input/output housing
> 500,000 h acc. to IEC 1709 (SN29500)
Horizontal on TS35 DIN-rail. 50 mm clearance top &
bottom for air circ. Can mount side by side with no
space in between.
0.5 kV Input/output housing
> 500,000 h acc. to IEC 1709 (SN29500)
Horizontal on TS35 DIN-rail. 50 mm clearance top &
bottom for air circ. Can mount side by side with no
space in between.
Class B
EN 61000-4-2 (ESD) | EN 61000-4-3 and EN 610004-8 (fields) | EN 61000-4-4 (burst) | EN 61000-4-5
(surge) | EN 61000-4-6 (conducted)
Class B
EN 61000-4-2 (ESD) | EN 61000-4-3 and EN 610004-8 (fields) | EN 61000-4-4 (burst) | EN 61000-4-5
(surge) | EN 61000-4-6 (conducted)
1 g according to EN50178 / 15 g In all directions
1 g according to EN50178 / 15 g In all directions
Acc. to EN60204
Acc. to EN50178 / VDE0160
SELV acc. to EN60950, PELV acc. to EN60204
Acc. to EN60204
Acc. to EN50178 / VDE0160
SELV acc. to EN60950, PELV acc. to EN60204
cCSAus; CE; cULus; GL; GOSTME25
cCSAus; CE; cULus; GL; GOSTME25
Input
Screw connection
Output
Screw connection
Input
Screw connection
Output
Screw connection
4 (1+, 2+, 1-, 2-)
4 (3+, 4+, 3-, 4-)
4 (1+, 2+, 1-, 2-)
4 (3+, 4+, 3-, 4-)
0.5 / 6
0.5 / 6
0.5 / 16
0.5 / 16
0.5 / 2.5
0.5 / 2.5
2.5 / 10
2.5 / 10
26 / 12
26 / 12
22 / 6
22 / 6
Note:
Ordering data
Plastic clip-on foot
Type
CP M DM20
Qty.
1
Part No.
1222210000
Type
CP M DM40
Qty.
1
Part No.
1222220000
11
connectPower PRO-M power supply unit
CP M CAP
PRO-M: diode, capacity
and relay modules
Pulse triggering for circuit breakers:
with the Weidmuller capacitance module.
The following conditions apply to the table entries:
• Ambient temperature of 20°C
•Inner resistance of the circuit breakers is
taken into account
•Half of the rated current flows to a neighbouring
circuit before the short circuit is formed
•DC-compatible circuit breakers: Siemens 5SY series
+
11
12
14
Load
1+
2+
Power supply
+
CAP module
Similar
to illustration
12-
Distance in m
Fuse tripping
Technical data
Input
Rated input voltage / DC input voltage range
Output
Peak current output / Recovery time for the capacitor
Switching thresholds
Floating contact
General data
Depth x width x height / Weight
Ambient temperature (operational) /
Storage temperature
Humidity
Protection degree
Class of protection
Pollution severity
Insulation voltage
24 V DC / 18…30 V DC
Depending on the load (typically 40 A for 1 ms) /
Approx. 1 sec.
21.6 V DC, relay is on for Power Good, 20.4 V DC,
relay is off for Power Fail
Yes
5...95%, no condensation
IP 20
III, with no ground connection, for SELV
2
0.5 kV Input/output housing
> 500,000 h acc. to IEC 1709 (SN29500)
Horizontal on TS35 DIN-rail. 50 mm clearance top &
bottom for air circ. Can mount side by side with no
space in between.
Mounting position, installation notice
EMC / shock / vibration
Noise emission acc. to EN55022
Interference immunity test acc. to
Class B
EN 61000-4-2 (ESD) | EN 61000-4-3 and
EN 61000-4-8 (fields) | EN 61000-4-4 (burst)
EN 61000-4-5 (surge) | EN 61000-4-6 (conducted)
EN 61000-4-11 (dips)
Resistance to vibration / Shock
Electrical safety (applied standards)
Electrical machine equipment
For use with electronic equipment
Safety extra-low voltage
Approvals
Approvals
Connection data
Wire connection method
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil min/max
B6
10 m
14 m
20 m
30 m
50 m
B10
6m
9m
15 m
24 m
B16
150 / 34 / 130 mm / 0.4 kg
-25°C...+70°C / -40°C...+85°C
MTBF
Conductor
cross section
0.75 mm2
1.0 mm2
1.5 mm2
2.5 mm2
4 mm2
6 mm2
1 g according to EN50178 / 15 g In all directions
Acc. to EN60204
Acc. to EN50178 / VDE0160
SELV acc. to EN60950, PELV acc. to EN60204
0.75 mm2
1.0 mm2
1.5 mm2
2.5 mm2
4 mm2
6 mm2
0.75 mm2
1.0 mm2
1.5 mm2
2.5 mm2
4 mm2
6 mm2
0.75 mm2
1.0 mm2
1.5 mm2
2.5 mm2
4 mm2
6 mm2
4m
6m
10 m
16 m
C2
11 m
14 m
21 m
34 m
C6
3m
3.5 m
5.5 m
9m
14 m
C4
6m
8m
12 m
19 m
32 m
C10
2m
3m
5m
8m
12 m
CE; cULus; GL
mm²
mm²
Input
Screw connection
Output
Screw connection
4 (++-)
3 (CO contacts)
0.5 / 6
0.5 / 6
0.5 / 4
0.5 / 2.5
26 / 12
26 / 12
For low-impedance connections, we recommend 2.5 mm2.
Note:
Ordering data
Plastic clip-on foot
Type
CP M CAP
Qty.
1
Part No.
1222240000
Note:
12
Subject to technical changes • 02/15 • LIT1426E