File E31519 Project 97ME13811 Issued: *Revised: April 25, 1997 November 19, 1999 REPORT on MOTOR CONTROLLERS, MAGNETIC Siemens AG Amberg, Fed. Rep. Germany Copyright © 1997, 1999 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the above-named company to reproduce this Report provided it is reproduced in its entirety. File E31519 Vol. 8 Sec. 1 and Report Page 1 Issued: 1997-04-25 Revised: 2005-11-11 DESCRIPTION PRODUCT COVERED USL, CNL - Type No 3RT10, 3RT11, 3RT13, 3RT15 or 3RT16 followed by 33, 34, 35 or 36 followed by -1 or -3 followed by A, B, C, D, E, F, H, J, K, M, P, Q, R, S or X followed by a character and a number followed by 0, 1, 2, 3, 4, 5, 6, 8 or 9, may be followed by -0LA2, -0GA0 or any Suffix Letters and/or numbers. USL, CNL - Accessory – terminal housing type 3RT1936-4EA2 GENERAL These devices are open types 3 or 4 pole contactors for use in industrial applications. Type 3RT1133 and 3RT1135 have additionally been evaluated to IEC 60947-6, weld-free. ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE USE) CNL - Indicates Investigated to Canadian National Standard(s) C22.2 No.14-M95 Note: CNL = Canadian National Standards - Listed. USL = United States Standards - Listed. RATINGS Housepower 3RT1033 Voltage 115 V 200/208 230/240 460/480 575/600 V V V V 1-ph 3-ph FLA LRA 2 3 5 --- -7.5 10 20 25 24 A 25.3 A 28 A 27 A 27 A -210.5 A 225 A 225 A 225 A 1-ph 3-ph FLA LRA 2 hp 5 hp 5 hp --- -10 10 25 30 24 A 32.2 A 28 A 34 A 32 A -259 225 281 270 Horsepower 3RT1034 Voltage 115 V 200/208 230/240 460/480 575/600 V V V V hp hp hp hp A A A A File E31519 Vol. 8 Sec. 1 and Report *Page 2 Issued: 4-25-97 Revised: 12-1-00 Horsepower 3RT1035 Voltage 115 V 200/208 230/240 460/480 575/600 V V V V 1-ph 3-ph FLA LRA 3 hp 5 hp 7 1/2 hp --- -10 hp 15 hp 30 hp 40 hp 34 A 32.2 A 42 A 40 A 41 A -259 337 337 330 1-ph 3-ph FLA LRA 3 hp 7 1/2 hp 10 hp --- -15 hp 15 hp 40 hp 50 hp 32 A 48.3 A 42 A 52 A 52 A -388 337 412 412 A A A A FLA 22 22 A 21 A 22 A LRA 183 183 169 180 A A A A A A A A Horsepower 3RT1036 Voltage 115 V 200/208 230/240 460/480 575/600 V V V V Horsepower 3RT1033 or 3RT1034 (Elevator Control) Voltage 120 V 230/240 V 460/480 V 575/600 V 1ph,1 pole 1 1/2 hp 3 hp - 2ph, 2pole 1 1/2 hp 3 hp - 3-ph 7 1/2hp 15 hp 20 hp Horsepower 3RT1035 (Elevator Control) Voltage 120 V 230/240 V 460/480 V 575/600 V 1 ph, 1 pole 2 hp 3 hp - 1 ph, 2 pole 2 hp 5 hp - 3-ph 10 hp 20 hp 25 hp FLA 28 28 A 27 A 27 A LRA 225 225 A 225 A 225 A 3-ph 12 hp 25 hp 30 hp FLA 336 33.6 A 34 A 32 A LRA 270 270 A 281 A 270 A Horsepower 3RT1036 (Elevator Control) Voltage 120 V 230/240 V 460/480 V 575/600 V 1 ph, 1 pole 3 hp 5 hp - 2 ph, 2 pole 3 hp 5 hp - Horsepower 3RT1133 (Weld-Free according to IEC 60947-6 Standard) Voltage 3-ph FLA LRA 200/208 V 230/240 V 460/480 V 7.5 hp 7.5 hp 15 hp 25.3 A 22 A 21 A 210.5 A 183 A 169 A File E31519 Vol. 8 Sec. 1 and Report *Page 2A Issued: 4-25-97 Revised: 9-29-00 Horsepower 3RT1135 (Weld-Free according to IEC 60947-6 Standard) Voltage 3-ph FLA LRA 200/208 V 230/240 V 460/480 V 10 hp 10 hp 25 h 32.2 A 28 A 34 A 259 A 225 A 281 A Horsepower 3RT1336 (4 NO Main Contacts) Voltage 3-ph FLA LRA 200/208 V 230/240 V 460/480 V 5 hp 7.5 hp 15 hp 17.5 A 22 A 21 A 140 A 183 A 169 A Horsepower 3RT1535 (2 NO + 2 NC Main Contacts) Voltage 3-ph FLA LRA 200/208 V 230/240 V 460/480 V 10 hp 15 hp 25 hp 32.2 A 42 A 34 A 259 A 337 A 281 A 3-ph 13 kVar 15 kVar 30 kVar 37 kVar Current 36 A 36 A 36 A 36 A Capacitive Switching 3RT1636 Voltage 200/208 230/240 460/480 575/600 V V V V 1-ph 7.5 kVar 8.5 kVar 17 kVar 21 kVar Main contacts: General Purpose - type - type - type - type Rating 3RT1033, 3RT1034, 3RT1035, 3RT1036, 600 600 600 600 V V V V AC, AC, AC, AC, 45 45 55 50 A A A A Auxiliary contacts: 1-, 2- or 4-pole auxiliary contact blocks Type 3RH1921 are top or side mounted, for ratings refer to File E44653 Vol. 11, Sec. 2 or Vol. 12 Sec. 3. The auxiliary contact blocks are available as factory assembled (removable or not removable design) or available as separate devices for individual arrangements. Coil Ratings: 24 through 600 V ac 12 through 250 V dc Definite Purpose: AC Resistance: Electric Heating, - type 3RT1033 45 - type 3RT1034 45 - type 3RT1035 55 - type 3RT1036 50 600 V ac, 250,000 c. A A A A - type 3RT1336 600 V, 60 A - type 3RT1535 600 V, 55 A File E31519 Vol. 8 Sec. 1 and Report Short Circuit Ratings: Type No. Fuse 3RT1033 3RT1034 3RT1035/3RT1535 3RT1036/3RT1336 3RT1133/3RT1135 3RT1636 1 2 Note: Note: max max max max max max 125 125 150 200 125 125 A A A A A A Bkr max max max max - Circuit TM1 125 A 125 A 150 A 200 A Page 2B Breaker Bkr I2 max 10 A max 10 A max 50 A max 100 A - Issued: 1997-04-25 Revised: 2005-05-10 Short Circuit 5 kA 5 kA 5 kA 5 kA 5 kA 10 kA Voltage 600 600 600 600 480 600 V V V V V V UL Listed inverse time circuit breakers UL Recognized instantaneous trip circuit breakers manufactured by Siemens, Type ED63A... High Capacity Short Circuit Ratings: Type No. Fuse Rating CB Rating (Bkr TM) Size Volt. Short Size Volt. Short [A] [V] [kA] [A] [V] [kA] 3RT1033 60 600 100 60 480 65 600 60 600 25 3RT1034 60 600 100 60 480 65 600 60 600 25 3RT1035 80 600 100 80 480 65 600 80 600 25 3RT1036 100 600 100 125 480 65 600 125 600 25 3RV103/Size Size Volt. [A] [V] 25 480 25 600 32 480 32 600 40 480 40 600 50 480 50 600 S23 Short [kA] 65 25 65 25 65 25 65 25 3 Note: For Siemens UL Listed Combination Motor Controller Type 3RV103 (Size S2) covered in File E156943. NEMA Ratings: * 3RT1036 meets ratings for NEMA Size 2. File E31519 Vol. 8 Sec. 1 and Report Page 2C Issued: 1997-04-25 Revised: 2005-05-10 Short Circuit Rating for Contactor, Fuse, Overload Relay combination according To UL 60947-4-1, for type “2” co-ordination. Contactor Overload Relay Fuse Class LPJ [A] Voltage for High Fault Current High Fault Current [kA] according to UL60947-4-1 Standard Fault Current [kA] according to UL60947-4-1 at 600V 3RT1033 3RT1034 3RT1035 3RU1136-4E 3RU1136-4F 3RU1136-4G 60 60 70 600 600 600 100 100 100 5 5 5