AIMTEC AME15

Series AME15-MAZ
15 Watt | AC-DC Converter
FEATURES:
•
•
•
•
4000VAC I/O Isolation
Operating temperature: -40 to +80°C
Over load, Over Voltage, Short Circuit Protection
Universal input: 90-264VAC, 47-440Hz
•
•
•
•
RoHS compliant
Soft start
Energy Star compliant
CE, cULus, CB approvals
CB
Models
Single output
Model
Input Voltage
(VAC/Hz)
Input voltage
(VDC)
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
120-370
120-370
120-370
120-370
120-370
AME15-3.3SMAZ
AME15-5SMAZ
AME15-12SMAZ
AME15-15SMAZ
AME15-24SMAZ
Output
Voltage (V)
Output Current
max (A)
3.3
5
12
15
24
3
3
1.25
1
0.63
Maximum
capacitive Load (µF)
Efficiency
(%)
4700
2200
1000
680
470
74
78
81
81
83
Models
Dual output
Model
Input Voltage
(VAC/Hz)
Input voltage
(VDC)
Output
Voltage (V)
AME15-5DMAZ
AME15-12DMAZ
AME15-15DMAZ
90-264/47-440
90-264/47-440
90-264/47-440
120-370
120-370
120-370
±5
±12
±15
Output Current
Maximum
Capacitive Load (µF)
max (A)
±1.5
±0.63
±0.5
±1000
±470
±330
Efficiency
(%)
78
80
81
Input Specifications
Parameters
Conditions
Typical
115 VAC
230 VAC
115 VAC
230 VAC
115 VAC
264 VAC
slow blow type
No Load
Current
Inrush current <2ms (Cold Start)
Leakage current
External Fuse (recommend)
Input Dissipation
Under Voltage Protection
Maximum
Units
350
180
10
20
0.1
0.2
mA
mA
A
A
mA
mA
A
W
VAC
Maximum
Units
2
<0.5
88
Output Specifications
Parameters
Voltage accuracy
Line regulation
Load regulation (single)
Cross regulation (dual)
Transient Recovery Time
Transient Response Deviation
Ripple & Noise*
Hold-up time
Conditions
Typical
±2
±0.5
±0.5
±5
200
±2
100
20
LL-HL
0-100%
25% load - 1st out, 100% load – 2nd out
25% load step
20MHz bandwidth
min
%
%
%
%
µs
% of Vout
mVp-p
ms
*Ripple & Noise measured with 1μF M/C and 47μF E/C
Isolation Specifications
Parameters
Tested I/O voltage
Isolation resistance
www.aimtec.com
F 052e R8.H
Conditions
Typical
3sec
>1000
Tel: +1 514 620 2722
1 of 4
Rated
Units
4000
VAC
MΩ
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AME15-MAZ
15 Watt | AC-DC Converter
General Specifications
Parameters
Switching frequency
Start up time
Over load protection
Over voltage protection
Short Circuit protection
Short Circuit restart
Operating temperature
Storage temperature
Max Case temperature
Temperature coefficient
Cooling
Humidity
Weight
Dimensions (L x W x H)
MTBF
Case material
Conditions
Typical
Maximum
132
900
>131
Zener diode clamp
Continous
Auto recovery
-40 to +80
-40 to +100
Auto recovery, hiccup mode
With derating over 55 oC
Units
KHz
mS
%
o
C
C
o
C
% / oC
o
100
±0.02
Free air convection
95
100
2.56 x 1.83 x 0.79 inches
65.0 x 46. 5 x 20.1 mm , ±0.5mm
> 400 000hrs (MIL-HDBK -217F, t=+25oC)
Plastic resin + Fiberglass (flammability to UL 94V-0)
% RH
g
NOTE: All specifications in this datasheet are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at
rated output load unless otherwise specified.
Environment Approval
Parameters
Shock
Vibrations
Conditions
Wave form: Half sine wave
Acceleration amplitude: 5gn
Bump duration: 30 ms
Number of bumps: 18 (3 in each direction for every axis)
Converter operation before and after test, body mounted (on chassis)
Test mode: Sweep sine
10-100Hz, speed 0.05Hz/s
Displacement: 1mm
Acceleration: 3g
3 loops 30min one cycle, 3h total, every axis tested
Converter operation before and after test, body mounted (on chassis)
Safety & EMC Specifications
Parameters
Agency approvals
Standards
www.aimtec.com
F 052e R8.H
cULus, CE, CB
Medical Electrical Equipment
Information technology Equipment
EMI - Conducted and radiated emission
Harmonic Current Emissions
Voltage fluctuations and flicker
Electrostatic Discharge Immunity
RF, Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
RF, Conducted Disturbance Immunity
Power frequency Magnetic Field Immunity
Voltage dips, Short Interruptions Immunity
Tel: +1 514 620 2722
2 of 4
IEC\EN\UL 60601-1, CSA-C22.2 No. 601.1-M90
EN 60950-1:2006+A11:2009
EN55011, class B
IEC/EN 61000-3-2, (EN60555-2)
IEC/EN 61000-3-3, (EN60555-3)
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AME15-MAZ
15 Watt | AC-DC Converter
Pin Out Specifications
Pin
Single
Dual
1
2
3
4
5
6
No pin
AC Input (N)
AC Input (L)
-V Output
No pin
+V Output
No pin
AC Input (N)
AC Input (L)
-V Output
Common
+V Output
Dimensions (Top View)
www.aimtec.com
F 052e R8.H
Tel: +1 514 620 2722
3 of 4
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only
Series AME15-MAZ
15 Watt | AC-DC Converter
Derating
Free Air Convection
55 º C
100
80
Safe Operating Area
60
40
20
0
-40
-20
0
20
40
60
85
80
100
Ambient Temperature º C
NOTE: 1. Datasheets are updated as needed and as such, specifications are subject to change without notice. Once printed or downloaded, datasheets are no longer
controlled by Aimtec; refer to www.aimtec.com for the most current product specifications. 2. Product labels shown, including safety agency certifications on labels, may vary
based on the date manufactured. 3. Mechanical drawings and specifications are for reference only. 4. All specifications are measured at an ambient temperature of 25°C,
humidity<75%, nominal input voltage and at rated output load unless otherwise specified. 5. Aimtec may not have conducted destructive testing or chemical analysis on all
internal components and chemicals at the time of publishing this document. CAS numbers and other limited information are considered proprietary and may not be available for
release. 6. This product is not designed for use in critical life support systems, equipment used in hazardous environments, nuclear control systems or other such applications
which necessitate specific safety and regulatory standards other the ones listed in this datasheet. 7. Warranty is in accordance with Aimtec’s standard Terms of Sale available at
www.aimtec.com.
www.aimtec.com
F 052e R8.H
Tel: +1 514 620 2722
4 of 4
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only