FUJI EDS6-120

E SERIESE ELECTROMAGNETIC FLOWMETER
(SEPARATE TYPE)
DATA SHEET
FMF1,2/FMH
The electromagnetic flowmeter is an instrument to measure
the volumetric flow rate of liquid simply by applying a magnetic field from the outside utilizing the fact that an electric
conductor which crosses a magnetic field at a certain velocity
causes voltage to be induced in proportion to the velocity,
which is known as Faraday’s law.
This flowmeter is designed with the latest electronics technology, realizing a compact and light-weight structure and
measurement with high accuracy.
FEATURES
1. High accuracy
When conductivity is above 5 µS/cm, flow rate of liquid
can be measured regardless of density and viscosity. The
measurement accuracy is as high as 0.6% of rate.
2. Free power supply
The flowmeter operates on power supply 100 to 230V AC,
50/60Hz.
3. Grounding electrode
Use of the grounding electrode of Hasteroy C in the flowmeter allows installation without an earth ring.
• Mounting method :
Mounted via flange insertion type on opposite (with Guide rings)
··· 3A to 100A
Note 1) Guide ring : A ring-shaped guide used for
centering the sensor when a wafer type
is mounted on the piping.
Note 2) Flange with meter size 3A or 6A can be
used for 15A.
4. Change of settings.
The setting of various parameters can be changed from
the outside of the case cover. Application of the supplied
magnetic stick to the outside glass surface enables the
setting to change without opening the case cover.
5. Stable measurement of flow rate
A digital filter for pulsating or noisy flow signal, flow rate
output low cut, and damping function allows flow rate
measurement to be stabilized.
6. Self-diagnosis function
Since self-diagnosis function is provided for empty detection, trouble, and maloperation, the flowmeter can be
used with safety.
7. Simultaneous display of instantaneous flow and total
flow 2-stage display with LCD backlight which is visible in
the dark.
SPECIFICATIONS
Detector (Model: FMF)
• Measurement item :
General-use industrial water, waste water,
and other liquids with conductivity of more
than 5µs/cm.
Wafer type or flange type
• Structure :
or flange mounting
··· 15A to 300A
• Fluid pressure :
0 to 2000kPa or flange operating pressure,
whichever is lower.
• Meter size and measurement range
See the following table for the full scale of
measurable flow rate.
Meter size
Min.measurement range
[m3/h]
Max. measurement range
[m3/h]
3A Note 3)
0 to 0.012
0 to 0.24
6A Note 3)
0 to 0.06
0 to 1.2
15A
0 to 0.3
0 to 6.0
25A
0 to 0.6
0 to 12.0
40A
0 to 1.8
0 to 36.0
50A
0 to 3.0
0 to 60.0
80A
0 to 9.0
0 to 180.0
100A
0 to 12.0
0 to 240.0
150A Note 4)
0 to 30.0
0 to 600.0
200A Note 4)
0 to 54.0
0 to 1080
250A Note 4)
0 to 90.0
0 to 1800
300A Note 4)
0 to 120.0
0 to 2400
Note 3) Meter size 3A and 6A : Wafer type only
Note 4) Meter size 150A or more : Flange type only
EDS6-120
Date
Aug.3, 2001
FMF1,2/FMH
• Fluid temperature :
–25 to +130˚C (PFA, TFE lining)
[˚C]
Fluid temperature
130
50
0
-25
-20
10
25
60
[˚C]
Ambient tempertaure
Fluid wetted
parts
Note 1)
Ambient temperature – fluid temperature allowable range
• Material :
Lining
Signal electrode
Earth electrode
Earth ring Note 2)
Housing case
Flange Note 3)
Case of terminal box
Tefron(PFA, TFE)
Hasteroy C-4 equivalent
Aluminum alloy
SUS316 equivalent
Aluminum alloy
Note 1) Materials of fluid wetted parts should be selected in
consideration of erosion due to measuring fluid. Refer to the table of material selection on the attached
sheet.
Note 2) For earth ring attachments, see CODE SYMBOLS.
Note 3) Flange type only
• Wiring connection port :
G1 /2
• Finish color : Silver, Lid ....Beige
• Protection class :
IP67
• Grounding : D-class grounding (100Ω or less)
Conveter (Model: FMH)
• Mounting method :
Mounting on the pipe or wall
• Input/output signal :
Current output; 4 to 20mA DC
Load rasistance 0 to 600Ω
Pulse output; open-collector
Capacity; 16 to 30V DC, 0.22A or less
ON voltage; 2V or less
Max. 5kHz
Status output; open-collector
Capacity: 16 to 30V DC, 0.22A or less
ON voltage; 2V or less
Status input; voltage input
Capacity: 16 to 30V DC
Internal resistance: 2kΩ
• Pulse output : Total pulses are outputted by setting total
constant. Pulse width 0.1 to 2000ms is
settable.
• Span setting : Flow rate full scale(FS) can be set by setting flow rate unit and flow rate value.
Display cubic volume; m3, L, mL
Display time unit ; /d, /h, /min, /s
• Flow direction change :
Flow direction can be reversed in flow direction mode.
• Flow display : Real unit flow display, % display or user
unit display is possible. Max 6 disits.
• Total display : Totaled volume can be displayed by setting the unit of cubic volume.
Displayed cubic volume unit ; m3, L, mL
Totaled value is held when power failure
occurs.
2
• Fault diagnosis function :
Various faults can be diagnosed by hardware check and process check.
• Zero point adjustment :
Zero point is automatically calibrated with
key operation.
0 to 10% FS settable
• Low cut :
Momentary output can be cut to 0% at
flow rate below the set cutoff point.
Note) Output low cut and total low cut are
set at the same value.
• 0% signal lock :
Display and output can be locked to 0%
with status input.
• Filter :
A digital filter is included in the converter
especially for pulsating or noisy flow signals.
• Empty detection :
Absence of liquid is detected and status
signal is outputted only when diameter is
more than 10A and conductivity is more
than 20µS/cm.
• Flow switch : 0 to 130% FS
Status signal is outputted by setting high/
low limit flow.
• Dumping time constant :
1 to 99.999 sec
• Density setting :
Available from 0.01 to 5.00g/cm3, and the
weight of the fluid can also be indicated.
• Converter case :
Aluminum alloy
• Wiring connection port :
G1 /2 (with water-proof gland)
• Finish color : Silver, Lid ....Beige
• Protection class :
IP67
• Grounding : D-class grounding (100Ω or less)
• Mass :
4.5kg
• Length of exclusive signal cable :
50m or less
Other specifications
For different materials of the electrode and earth-ring, contact with Fuji Electric.
Standard performance
• Accuracy rating of display and pulse output :
Flow velocity
Accuracy
±0.5% of rate
0.0035
100 % of rate
±
0.7m/s 0or less
Qv
Qv : Measuring flow velocity
0.7m/s or more
• Accuracy rating of analog output :
Flow velocity
Accuracy
±0.6% of rate
0.0035
100+0.1 % of rate
±
0.7m/s 0or less
Qv
Qv : Measuring flow velocity
0.7m/s or more
• Power consumption :
14VA or less
• Operating condition :
Ambient temperature;
–25 to 60˚C (Detector : PFA, TFE lining)
–20 to 60˚C (Converter)
Ambient humidity; 95% RH or less (Note)
Power voltage; 100 to 230V AC +10%,
-15%
Power frequency; 50/60Hz
(Note)
If ambient humidity exceeds 95% RH, select a submersible type in FMB model.
Length of straight pipe for installing the electromagnetic flowmeter
The length of the up-stream/down-stream straight pipe of the flowmeter should be long enough to ensure accurate measurements. See below.
1-1) Upstream reducer pipe
Flowmeter
Flowing direction
2-1) Downstream reducer pipe
Flowmeter
Flowing direction
5D
Downstream straight pipe unnecessary
1-2) Upstream diffuser pipe
Flowmeter
2-2) Downstream diffuser pipe
Flowmeter
Flowing direction
Flowing direction
5D
1-3) Various upstream valves
Flowmeter
Flowing direction
Downstream straight pipe unnecessary
2-3) Various downstream valves
Flowmeter
Flowing direction
Note)
10D
2
3D
Note) "5D" with sluice valve fully open
1-4) Upstream 90° bend
2-4) Downstream 90° bend
Flowmeter
Flowing
direction
Flowmeter
Flowing direction
2
5D
1-5) Upstream T-pipe
3D
2-5) Downstream T-pipe
Flowmeter
Flowing
direction
Flowmeter
Flowing direction
5D
2
3D
Minimum length of straight pipe between up-stream/down-stream joints and flowmeter.
Note 1) D=diameter of measuring pipe.
Note 2) Do not put any objects, which affect magnetic field, electromotive force and flow velocity profile, in the measuring pipe.
Note 3) Use a straight pipe (2D to 3D) on the down-steam side, if the drift to the up-stream side is affected by installing valves,
etc.
3
FMF1,2/FMH
Mounting posture of electromagnetic flowmeter
The flowmeter can be installed vertically, horizontally, or at other angle. When installing, be sure to observe the following points.
q The measuring pipe should always fill with fluid which flows in the piping.
Fluid may not fill up the pipe.
Air are apt to from.
Fluid may not
fill up the pipe.
Good
Good
Pump
Example of mounting posture
w The signal electrode should be at a level with the ground. And also signal electrode and ground electrode should always keep
contact with fluid. If the signal electrode or the ground electrode is upper position against the fluid, correct measurements
cannot be expected due to air bubbles on the fluid.
Signal electrode
Ground electrode
Ground
Ground
< Good >
< Good >
Ground electrode
Signal electrode
Ground
electrode
Signal electrode
Ground
Ground
< No good >
< No good >
Position of electrode
How to connect the grounding cable contacting with measuring liquid.
Since the electromagnetic flowmeter is provided with a grounding electrode, flow rate of liquid can be measured without an earth
ring. However, if stray potential exists in a pipeline, the potential in the pipeline may fluctuate.
In this case, the earth ring (option) of the same material as signal electrode and ground electrode should be mounted on the
upstream and downstream sides of the flowmeter to connect to the grounding terminal.
For liquid that contains attachments or deposits, take the liquid contacting ground from the optional earth rings and metallic pipe
(without lining).
Grounding connection
In case of metallic
pipe without linging
Without earth ring
4
With earth ring
CODE SYMBOLS
Separate type electromagnetic flowmeter Detector (wafer type)
1 2 3 4 5 6 7 8
FMF 1
9 10 11 12 13
1 -H0
14
A0 -
Description
Meter size (5th code)
3A
6A
15A
25A
40A
50A
80A
100A
S
A
C
D
T
E
F
G
Lining material (6th code)
TFE (adhesive Tefron) : applied for meter size 15A to 100A
PFA (mold Tefron) : applied for meter size 3A to 6A
T
P
Earth ring material (7th code)
None
Hasteroy C
0
H
Electrode matertal (9th code)
Hasteroy C
H
Flange (10th code)
None
0
Guide ring (11th code)
For JIS 10K
For JIS 75M (Meter size 80A, 100A only)
1
7
Wiring connection port size (12th code)
G1/2(PF1/2) female screw with water-proof gland
A
Application (13th code)
Standard
0
Y
A
Optional specifications (14th code)
None
Stainless tag plate
Note 1) Items with the asterisk mark
will be manufactured as order.
5
FMF1,2/FMH
Separate type electromagnetic flowmeter Detector (flange type)
1 2 3 4 5 6 7 8
FMF 2
T
9 10 11 12 13
14
1 - H 10A0 -
Description
Meter size (5th code)
15A
25A
40A
50A
80A
100A
150A
200A
250A
300A
C
D
T
E
F
G
H
J
K
L
Lining material (6th code)
TFE (adhesive Tefron)
T
Earth ring material (7th code)
None
Hasteroy C
0
H
Electrode matertal (9th code)
Hasteroy C
H
Flange (10th code)
For JIS 10K
1
Guide ring (11th code)
None
0
Wiring connection port size (12th code)
G1/2(PF1/2) female screw with water-proof gland
A
Application (13th code)
Standard
0
Y
A
Optional specifications (14th code)
None
Stainless tag plate
Note 1) Items with the asterisk mark
will be manufactured as order.
Separate type electromagnetic flowmeter Converter
1 2 3 4 5 6 7 8
F MH 1 N
9 10 11 12 13
A1 -
Y
Description
Application (4th digit)
Standard
1
Power supply (5th digit)
AC100 230V
N
Mounting method (6th digit)
Pipe mount
Wall mount
A
B
Wiring lead-in port (7th digit)
G1/2(PF1/2) female, with water-proof gland
A
Optional specification (9th digit)
None
With parameter setting function
Y
A
Cable termination (10th digit)
None
Y
0
0
0
0
0
0
6
0
1
2
3
4
5
0
0
0
0
0
0
Cable length (11 to 13th digit)
Nothing
10m
20m
30m
40m
50m
OUTLINE DIAGRAM (Unit: mm)
(Wafer type detector)
< Stainless tag >
Option
75
Wiring lead-in port
G 1/ 2
88
35
67.5
67
20
Water-proof
gland
15A
25A
40A
50A
80A
100A
W1
69
69
91
133
75
62
191
2
75
95
73
213
3.5
119
130
103
B
F
104
112
163
190
82
231
5
90
247
5.5
110
287
8
130
327
9
H
Meter size 3A,6A
F
H
Mass ( Kg )
62
191
2
B
W1
(Flange type detector)
< Stainless tag >
Option
75
Wiring lead-in port
88
67.5
35
Water-proof
gland
20
N-øB
Meter size
W1
W2
øC
F
øG
øD
H
øD
øC
N-øB
JIS 10K
T
flange
øG
H
F
Mass ( Kg )
0
W1 -3
W2 (Note)
T
15A 25A 40A 50A 80A 100A
66.5 87 100 116 100 130
200 200 200 200 200 250
95 125 140 155 185 210
70
90 105 120 150 175
4-12 4-15 4-15 4-19 8-19 8-19
14
20
20
22
18 20
52
70 85 100 130 155
191
62
3
213 231
73 82
4
6
247
90
287 327
110 130
8
16
17
(Note) W2 are dimensions after positioning to piping.
The lining flare sections are not glued before
positioning to piping
(There are about 30mm protruding of each side.)
7
FMF1,2/FMH
OUTLINE DIAGRAM (Unit: mm)
Wiring lead-in port G1/2
ø80
67
35
Water-proof
gland
F
N-øB
T
W1
W2 (Note)
150A
200A
250A
300A
< Stainless tag >
W1
170
300 -30
280
250
450 -50
400
355
12-25
250
500 -50
445
Option
W2
195
350 -30
330
290
JIS 10K
flange
øD
øC
N-øB
T
øG
H
F
Mass (kg)
240
8-23
25
12-23
212
268
30
320
368
430
179
53
486
207
79
148
29
28
400
16-25
31
370
572
250
81
(Note) W2 are dimensions after positioning to piping.
The lining flare sections are not glued before
positioning to piping
(There are about 30mm protruding of each side.)
8
75
Meter size
20
øD
øG
H
øC
OUTLINE DIAGRAM (Unit: mm)
(Pipe mount type converter)
49
Water-proof gland
78
229
288
310
ø120
26
199
329
108
70
35
U-bolt M8
Mounting pipe
JIS 2B
Wiring lead-in
port G1/2
(Wall mount type converter)
Water-proof gland
229
80
60
78
34
199
220
288
35
ø7
Wiring lead-in
port G1/2
ø7
9
FMF1,2/FMH
EXTERNAL CONNECTION DIAGRAM
Shield of flow rate
signal cable
Flow rate signal
Converter<FMH>
Excitation
V9 V8 P7 G2 X2 +
–
Total pulse
output
N
L
Outer shield
Detecter<FMF>
Inner shield
M2 M1 2S
2
1
1S 3
M2 M1
2
1
3
SE
Power supply
Special signal cable
Current output
Status output
Status input
Flow velocity [m/s]
m/s
FLOW RATE – FLOW VELOCITY CONVERSION DIAGRAM
3 4 5 6 810-2
2
3 4 5 6 810-1
2
3 4 56 8 1
2
3 4 5 6 8 10
2
3 4 5 6 8 102
2
3 4 56 8
10
8
6
5
4
3
2
3A
1
0.8
0.7
0.5
6A
A
15
A
25
A A
80 100
A
A
40 50
0A 00A 50A 00A
15
2
2 3
3
10-2
2
2
3 4 5 6 810-1
3 4 56 8 1
2
2
3 4 56 8 1
3 4 5 6 8 10
2
2
3 4 5 6 8 10
3 4 5 6 8102
Flow rate
2
2
3 4 5 6 8102
3 4 5 6 8103
2
2
3 4 5 6 8103
3 4 5 6 8104
2
2
3
3 4 5
m/h
L/min
SCOPE OF DELIVERY
HOW TO CONNECT CABLE
Detecter (mounting bolt and packing should be prepared
separately).
1. Press the terminal spring by inserting a minus driver
(small) through the opening at top.
Converter ×1 (with metal fixtures for pipe-mount or wallmount)
2. Insert terminated cable into the cable lead-in port as
shown below.
Special signal cable ×1 (length; by specifing)
3. When the driver is removed, the cable is fixed (connected)
by the spring force in the terminal.
Magnetic stick
SPARE PARTS
Guide rings (note) / for wafer type.
Minus driver (small)
10
15mm
Note) Not supplied for 80A and 100A JIS 10K.
Cable
ITEMS SPECIFIED AT ORDERING
1. Type, specification code.
2. Flow measurement range and mesurement fluid.
3. When ordering “with stainless tag plate,” specify Tag No.
(up to 16 alphanumeric characters) as needed.
4. When ordering “with parameter setting,” complete and
send the attached parameter designation table.
10
L/s
Note) Cable should be securely fixed with the supplied
water-proof gland.
If you want the instrument with certain parameters factory set as you desire, specify them in the following parameter designation
tables 1 and 2.
Company :
Name :
Measured fluid :
Sector :
Telephone No. :
<Parameter designation table 1>
Standard set value
Setting item
Range
(Note 1)
Damping
5.0s
1.0 to 99.0s
LCD
<1st line, 2nd line>
Real scale
1st line
indication
q Real scale indication
indication
Volume unit: mL, L, m3
Unit: m3/h
Mass unit: g, kg
Time unit: /s, /min, /h
w Arbitrary real scale unit
• Unit factor: 0.00001 to
9999999
• Unit name: Arbitrary value
of 4 characters
e Percent indication (%)
r Total real scale indication
Volume unit: mL, L, m3
Mass unit: g, kg
t Arbitrary total real scale unit
• Unit factor: 0.00001 to
9999999
• Unit name: Arbitrary value
of 4 charactes
y TAG No. indication
LCD
2nd line
indication
Total real scale
indication
u Bar graph indication
(Percent indication can also
be indicated simultaneously
in 1% step)
Unit: m3
i Non-display
Put check marks into
which precede items to modify for.
Item selection or
Example
value designation
.
[s]
020.0s
<Designation of 1st line indication> According to selection of left item,
Select an item from the following. designate necessary item and value.
Real scale indication
Volume unit: mL, L, m3
Mass unit: g, kg
Time unit: /s, /min, /h
Arbitrary real scale indication Unit factor: 0.00001 to
9999999
1000000
*Value converted the units into L
Item to select
Unit name:
Percent indication
None.
Total real scale indication Volume unit: mL, L, m3
Mass unit: g, kg
Arbitrary total real scale Unit factor: 0.00001 to
indication
9999999
*Value converted the units into L
t/h
1000000
Unit name:
t
None
None
None
According to selection of left item,
designate necessary item and value.
Volume unit: mL, L, m3
Mass unit: g, kg
Time unit: /s, /min, /h
Arbitrary real scale indication Unit factor: 0.00001 to
9999999
1000000
*Value converted the units into L
TAG No. indication
Bar graph indication
Non-display
<Designation of 2nd line indication>
Select an item from the following.
Real scale indication
Unit name:
t/h
Percent indication
None.
Total real scale indication Volume unit: mL, L, m3
Mass unit: g, kg
Arbitrary total real scale Unit factor: 0.00001 to
indication
9999999
*Value converted the units into L
1000000
Unit name:
t
Range
Instantaneous
output
low-cut point
Total
direction
Total constant
(Note 2)
(Total value
per pulse)
Total pulse
width
(Note 3)
Filter
By table-1
(Note 5)
0.5 to 10 m/s
converted to flow velocity.
0.0%
0.0% to 10.0%
TAG No. indication
Bar graph indication
Non-display
Volume unit: mL, L, m3
Time unit: /s, /min,
/h, /d
None.
None
None
None
Must be designated in 4 significant digits. 100.0
Value:
.
FORWARD
FORWARD
/REVERSE (Note4) FORWARD/REVERSE
Value: 0.001 to 1000
1m3
Unit : mL, L, m3
FORWARD
FORWARD/REVERSE
Volume unit:
mL, L, m3
30ms
0.1 to 2000ms
None.
off
on
off
on
off
%
3.5%
[ms]
50.0[ms]
None.
Value:
.
None.
11
FMF1,2/FMH
<Parameter designation table 2>
Standard set value
Setting item
(Note 1)
Empty detection off
on
function
off
Range
on
off
Upper/Lower Upper limit value
limit alarm
: 130%
Upper limit value: 0 to 130%
Lower limit value
: 0%
Lower limit value: 0 to 130%
Specific gravity 1.000g/cm3
TAG-NO
Blank unless
designated
Flow
STANDARD
direction
Item selection or
value designation
Alarm output value
3.6mA
4mA
24.8mA
Item to select
0.01 5g/cm3
Up to 16 alphanumerics
STANDARD
OPPOSITE
Upper limit alarm
Alarm output value
3.6mA
4mA
Lower limit alarm
24.8mA
Upper limit value:
Upper/Lower limit alarm . %
Lower limit value:
. %
None
g/cm3
None
Example
Upper limit
value:
120.0%
Lower limit
value:
0.0%
0.95g/cm3
F-100
None
STANDARD
OPPOSITE
(Note 1) Standard set value refers to parameter set value as factory set in case parameter setting is not designated.
(Note 2) Designate so that the number of total pulse outputs will be below 5kHz at the maximum flow rate (to meet the following equation).
Range [m3/h] / (total constant [m3] × 3600) 5000
(Note 3) Designate the total pulse width so as to hold: (Total constant [m3]) × 3600/range [m3/h] total pulse width [ms]/500
(Note 4) When selecting FORWARD/REVERSE from the total direction, total pulse is only outputted in the FORWARD direction.
(Note 5) Factory-set range before shipment (unless specified).
Table-1
Meter size
Range [m3/h]
Meter size
Range [m3/h]
Meter size
Range [m3/h]
3A
0.05
40A
14.0
150A
120.0
6A
0.2
50A
14.0
200A
220.0
15A
1.2
80A
35.0
250A
350.0
25A
3.5
100A
55.0
300A
350.0
(Material selection table of electrode/earth ring)
Material of
electrode/earth ring
Measurable liquid
Unmeasurable liquid
SUS316
Water and waste water, weak acid, weak alkali
Example: 25% acetic acid or less, hydroiodic acid,
butyric acid, aqueous ammonia or alike
Inorganic acid, organic acid, chloride or alike
Hastelloy C-4 or
equivalent
Suitable for intermediate oxidation and reduction
Chloride, high-temperature strong acids
(nitric acid, hydrochloric acid, sulfuric acid),
and can be used for various fields.
Example: Sea water, formic acid, acetic acid, aqueous ferric chloride or alike
ammonia, normal-temperature nitric acid and sulfuric
acid or alike
Titanium
Resistant to sea water, most oxidative acids, chloride,
sulfide and alkali.
Example: Sea water, saline water, aqueous ammonia,
chlorine water, polyelectrolyte, acetic acid, ferric
chloride or alike
Reductive acids such as hydrochloric acid,
sulfuric acid, phosphoric acid, oxalic acid
Tantalum
Resistant to most chemicals.
(particularly, strong acids)
Example: Hydrochloric acid, sulfuric acid, nitric acid,
aqua regia, ferric chloride, hypochlorous acid, sodium
hypochlorite, PAC (Polyaluminum chloride) or alike
Sodium hydroxide, potassium hydroxide,
hydroflouric acid, fuming sulfuric acid or
alike
Platinum-iridium (Pt-Ir)
Resistant to almost chemicals.
Aqua regia
(Note): The electrode/earth ring for E-series electromagnetic flowmeter use Hastelloy C-4 or equivalent.
If other material except Hastelloy C-4 is required, select a model that uses other material from the separate type
electromagnetic flowmeter (FMB/C series) of Fuji Electric.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan