INTEGRAL TYPE ELECTROMAGNETIC FLOWMETER DATA SHEET FMA1, 2 The electromagnetic flowmeter is an instrument to measure the volumetric flow rate of liquid simply by applying a magnetic field from the outside utilizing the fact that an electric conductor which crosses a magnetic field at a certain velocity causes voltage to be induced in proportion to the velocity, which is known as Faraday’s law. This flowmeter is designed with the latest electronics technology and magnetic/electric field analyzing technology, realizing a compact and light-weight structure and measurement with high accuracy. FEATURES 1. High accuracy The adoption of the optimum magnetic field design using the 3-dimentional finite element method has minimized the effects of flow velocity profile and materials of adjacent piping. At flow velocity of more than 1m/sFS,the measurement accuracy is as high as ± 0.5% of indicatedvalue when the flow is above 20%FS. 2. Wide range Measurement range: 0 to 0.1 ... 15m/sec in flow velocity 3. High-reliability structure The converter case is a sealed 2-chamber structure, practically free from dew condensation and sudden submergence. The adoption of stainless housing assures excellent anti-environment efficiency. 4. Easy-to-see display LCD with back-light allows easy check of display even in a dark place. Instantaneous flow and integral volmetric flow are displayed at the same time. 5. Free power supply The flowmeter operates on power supply 100 to 240V AC, 50/60 Hz, eliminating the need for selection of power voltage. • Mounting method : Mounted via flange insertion type on opposite (wafer type) (with Guide rings) ··· 2.5 to 200A Note 1) Guide ring : A ring-shaped guide used for centering the sensor when a water type is mounted on the piping. or flange mounting ··· 6 to 300A Note 2) Flange with meter size 2.5A or 6A can be used for 15A. • Liquid pressure : -100 to 2000kPa or flange operating • Meter size and measurement range Measuring range is equivalent to flow velocity 0.1 to 15m/s. 6. Application of international standards The overall length of flange type flowmeter conforms with ISO draft standards. (Meter size : 6A-200A) SPECIFICATIONS Sensor • Measurement item : General-use industrial water, tap-water, sewage, waste water, chemicals slurry, and other liquids with conductivity of more than 3µs/cm. • Structure : Wafer type or flange type Meter size Min.measurement range [m3/h] Max. measurement range [m3/h] 2.5A Note 3) 0 to 0.00177 0 to 0.265 6A 0 to 0.0102 0 to 1.52 15A 0 to 0.0637 0 to 9.54 25A 0 to 0.177 0 to 26.5 40A 0 to 0.453 0 to 67.8 50A 0 to 0.707 0 to 106 80A 0 to 1.81 0 to 271 100A 0 to 2.83 0 to 424 150A 0 to 6.37 0 to 954 200A 0 to 11.3 0 to 1696 250A 0 to 17.7 0 to 2650 300A 0 to 25.5 0 to 3817 Note) Meter size 2.5A: Wafer type only EDS6-69b Date Oct. 29, 2001 FMA1, 2 • Liquid temperature : –10 to +120˚C (Tefron lining) –10 to +50˚C (Polyurethane lining) [˚C] Liquid temperature Tefron lining 120 80 50 Polyurethane lining -10 -20 20 50 60 [˚C] Ambient tempertaure Ambient temperature-liquid temperature allowable range Parts in contact with Liquid Note 1) • Material : Lining Tefron(PFA, TFE) Polyurethane Electrode SUS316L Hasteroy C Titanium Tantalum Platinum iridium SUS316L Earth ring SUS316 Hasteroy C Titanium Tantalum SUS316 Housing case Flange Note 2) SUS304 SUS304 or carbon steel Note 1) Materials of parts in contact with liquid should be selected in consideration of erosion due to measuring liquid. Refer to the table of material selection on the attached sheet. Note 2) Flange type only SUS304: Unpainting Carbon steel: Polyurethane corrosion-resistant painting (Silver) Conveter • Exciting system : Square low-frequency exciting • Input/output signal : Current output; 4 to 20mA DC Load rasistance 0 to 1KΩ Pulse output; open-collector Capacity; DC30V, 0.2A or less ON voltage; 0.6V or less 0.0001 to 1000P/s Status output; open-collector Capacity: DC30V, 0.2A or less ON voltage; 2V or less Status input; no- voltage contact Note) Status signal input or output, either one, can be • Pulse output : Integrated pulses are outputted by setting integral constant. Pulse width 0.5 to 80ms • Span setting : Flow FS can be set by setting flow unit and flow value. Flow velocity can also be set. Display cubic volume, length; m3, L, mL, m Display time unit ; /d, /h, /min, /s • Multi-range : Automatic 2-range selection in 2-range select mode. External 2-range selection with status input is possible. • Flow direction change : Flow direction can be reversed in flow direction mode. • Flow display : Real time flow display, % display or user unit display is possible in 7 codes, max. 2 • Integration display : Integrated volumetric flow can be displayed by setting the unit of cubic volume. Displayed cubic volume; m3, L, mL • Fault diagnosis turction : Various faults can be diagnosed by hardware check and process check. • Zero point adjustment : Zero point is automatically calibrated with one-push operation. • Output low cut : 0 to 10% FS Momentary output can be cut to 0% at flow rate below the set cutoff point. • Integration low cut : 0 to 10% FS Integration of display and output are prevented at flow rate below the set cutoff point. • 0% signal lock : Display and output can be locked to 0% with status input. • Slurry noise cut : 0 to 10% FS, 0 to 60 sec Slurry noise (spike noise) can be cut by setting rate limit. • Empty detection : Absence of liquid is detected and status signal is outputted. • Flow switch : –10 to 110% FS Status signal is outputted by setting high/ low limit flow. • Dumping time constant : 1 to 200 sec • Converter case : Aluminum alloy • Arrester : Built-in power supply arrester and current output arrester • Wiring connection port : G1 /2, NPT1 /2, Pg 13,5, M20 x 1,5 • Painting : Body case; Polyurethane corrosion-resistant painting (Silver) Body cover; Polyurethane corrosion-resistant painting (Blue) • Structure : JIS C 0920 immersion-proof (IP67) • Grounding : D-class grounding (100Ω or less) OTHER SPECIFICATIONS When replacing Fuji' s former type sensors, flanges with short pipe are available. For details, contact our office. Standard performance • Accuracy rating : Meter size 2.5A to 15A 25A to 200A FS flow velocity Flow velocity≥50%FS: _ 1m/s or more ±0.5% of rate Flow velocity<50%FS: ±0.25% FS Flow velocity≥20%FS: _ ±0.5% of rate Flow velocity<20%FS: ±0.1% FS FS flow velocity ±0.5% FS 0.3m/s or more less than 1m/s Flow velocity≥50%FS: _ ±0.5% of rate Flow velocity<50%FS: ±0.25% FS FS flow velocity ± (0.075/Vs+0.25)% FS Flow velocity≥50%FS: _ 0.1m/s or more (Vs:FS Flow velocity ± (0.075/Vs+0.25)%f rate less than 0.3m/s [m/s]) Flow velocity<50%FS: ± (0.0375/Vs+0.125)% FS • Power consumption : 12W or less • Operating condition : Ambient temperature; –20 to 60˚C (Tefron lining sensor) –20 to 50˚C (Urethane lining sensor) Ambient humidity; 95% RH or less Power voltage; 100 to 240V AC ± 10% Power frequency; 50/60Hz 3 FMA1, 2 Length of straight pipe The length of the up-stream/down-stream straight pipe of the flowmeter should be long enough to ensure accurate measurements. See below. 2-1) Downstream reducer pipe 1-1) Upstream reducer pipe Flowmeter Flowing direction Flowmeter Flowing direction Downstream straight pipe unnecessary 5D 1-2) Upstream diffuser pipe 2-2) Downstream diffuser pipe Flowmeter Flowing direction Flowmeter Flowing direction 5D Downstream straight pipe unnecessary 1-3) Various upstream valves 2-3) Various downstream valves Flowmeter Flowing direction Flowmeter Flowing direction Note) 10D Note) "5D" with sluice valve fully open 1-4) Upstream 90° bend 2 to 3D 2-4) Downstream 90° bend Flowmeter Flowing direction Flowmeter Flowing direction 5D 1-5) Upstream T-pipe 2 to 3D 2-5) Downstream T-pipe Flowmeter Flowing direction Flowmeter Flowing direction 5D 2 to 3D Minimum length of straight pipe between upstream/downstream joints and flowmeter. Note 1) L=a multiple of diameter D of measuring pipe. Note 2) Do not put any objects, which affect magnetic field, electromotive force and flow profile, in the measuring pipe. Note 3) Use a straight pipe (2D to 3D) on the downsteam side, if the drift to the upstream side is affected by installing valves, etc. 4 Mounting posture The flowmeter can be installed vertically, horizontally, or at other angle. When installing, be sure to observe the following points. q The measuring pipe should always fill with fluid which flows in the piping. Fluid may not fill up the pipe. Air are apt to form. E S C. E S C. I N C. SHIFT I N C. SHIFT E N T. E N T. E S C. I N C. SHIFT E N T. Fluid may not fill up the pipe. E S C. I N C. SHIFT E N T. Good E S C. I N C. SHIFT E N T. Good Pump Example of mounting posture w The electrode should be at a level with the ground and should always keep contact with fluid. (If the electrode is vertical to the ground air bubbles appear on the fluid and hence contaminated with deposits.) Electrode E S C. I N C. SHIFT < Good > Ground E N T. Electrode < Good > Ground Ground < No good > Electrode mounting position e Use of a bypass valve will provide easy zero adjustment and maintenance. Install a bypass line so that fluid flow is not interrupted. A bypass line installed as illustrated in the following figure (a) and (b) allows the inside of the pipe to be washed and cleaned without removing the flowmeter. Bypass Bypass SHIFT SHIFT I N C. E N T. I N C. E S C. E S C. Stop valve E N T. Flowmeter Stop valve FLOW Short pipe Short pipe Flowmeter Coupling flange (a) Horizontal bypass line FLOW (b) Vertical bypass line 5 FMA1, 2 Material selection table The following table indicates examples of recommended materials, contacting with liquid, to be used with the typical liquids measured with electromagnetic flowmeter. Evaluation of those materials has been conducted according to various documents and experience in actual use. 1. Characteristics of lining materials Material Abrasion resistance [ Heat resistance Corrosion resistance : Excellent, : Very good, Adhesion resistance : Good, : No good] Remarks Ideal for the use with corrosive or adhesive fluids. Not suitable for abrasive fluid (such as slurry.) Pay attention to permeability of TFE. Note that TFE is not suitable for use with hightemperature + negativepressure fluid. Teflon PFA Teflon TFE Has inferior heat resistance or corrosion resistance. Best for slurry or the like with no corrosive properties. Poly-urethane 2. Material selection table of electrode/earth ring 6 Material Measurable liquid Unmeasurable liquid SUS316 Water and waste water, weak acid, weak alkali Example: 25% acetic acid or less, hydroiodic acid, butyric acid, aqueous ammonia or alike Inorganic acid, organic acid, chloride or alike Hastelloy C-276 or equivalent Suitable for intermediate oxidation and reduction and can be used for various fields. Example: Sea water, formic acid, acetic acid, aqueous ammonia, normal-temperature (lower than 40°C) nitric acid, hydrochloric acid and sulfuric acid or alike Chloride, high-temperature strong acids (nitric acid, hydrochloric acid, sulfuric acid), high temperature (higher than 40°C) or high concentration (more than 40%) ferric chloride or alike Titanium Resistant to sea water, most oxidative acids, chloride, sulfide and alkali. Example: Sea water, saline water, aqueous ammonia, chlorine water, polyelectrolyte, acetic acid, ferric chloride or alike Reductive acids such as hydrochloric acid, sulfuric acid, phosphoric acid, oxalic acid Tantalum Resistant to most chemicals. (particularly, strong acids) Example: Hydrochloric acid, sulfuric acid, nitric acid, aqua regia, ferric chloride, hypochlorous acid, sodium hypochlorite, PAC (Polyaluminum chloride) or alike Sodium hydroxide, potassium hydroxide, hydroflouric acid, fuming sulfuric acid or alike Platinum-iridium (Pt-Ir) Resistant to almost chemicals. Aqua regia CODE SYMBOLS Integral type electromagnetic flowmeter (wafer type) 1 2 3 4 5 6 7 8 F MA 1 9 10 11 12 13 1 - 0 14 - Description Meter size (5th code) 2.5A 6A 15A 25A 40A 50A 80A 100A 150A 200A S A C D T E F G H J Lining material (6th code) PFA mold Tefron Polyurethane rubber (7th & 9th code; W only) Note) Polyurethane rubber with less than 15A of meter size cannot be used. P U Earth ring material (7th code) SUS316 Hasteroy C Titanium Tantalum W H C T Electrode material (9th code) SUS316L Hasteroy C Titanium Tantalum Platinum iridium W H C T P Flange (10th code) None 0 Guide ring (11th code) For JIS 10K For JIS 20K For JIS 75M (Meter size of less than 50A cannot be used) For ANSI 150LB For ANSI 300LB For DIN/PN 16K For DIN/PN 40K 1 2 7 5 6 8 9 Wiring connection port size (12th code) G1/2 female screw G1/2(PF1/2) female screw with water-proof gland G1/2(PF1/2) female screw with union and water-proof gland NPT1/2 female screw Pg 13.5 female screw M20 ×1.5 female screw Y A B C D E Direction of indicator (13th code) See Fig 1 Horizontal mounting Vertical mounting 1 2 Y A B C Optional specifications (14th code) None Stainless tag plate Parameter setting Parameter setting and stainless tag plate Note) When parameter setting function is used, specify parameters in parameter designation tables 1 and 2. Fig 1 Direction of indicator ESC. Upper Lower INC. SHIFT ENT. CONTRAST ESC. INC. SHIFT ENT. CONTRAST Horizontal mounting (Code 1) Vertical mounting (Code 2) 7 FMA1, 2 Integral type electromagnetic flowmeter (flange type) 1 2 3 4 5 6 7 8 F MA 2 9 10 11 12 13 1 - 0 14 - Description Inside diameter (5th code) 6A Note 15A 25A 40A 50A 80A 100A 150A 200A 250A 300A Note) Flange size for meter size 6A is 15A or 1/2B. A C D T E F G H J K L Lining material (6th code) PFA mold Tefron Note 1 TFE Tefron Note 2 Polyurethane rubber Note 3 (7th & 9th codes: W only) Note 1) PFA 6A to 200A Note 2) TFE 250A, 300A Note 3) Polyurethane rubber with less than 15A of meter size cannot be used. P T U Earth ring material (7th code) SUS316 Hasteroy C Titanium Tantalum W H C T Electrode material (9th code) SUS316L Hasteroy C Titanium Tantalum Platinum iridium W H C T P Flange standard Flange material (10th code) JIS 10K SUS304 JIS 20K SUS304 JIS 75M SUS304 Note 2 ANSI 150LB SUS304 ANSI 300LB SUS304 DIN PN16 SUS304 DIN PN40 SUS304 Note 1 JIS 10K Carbon steel JIS 20K Carbon steel Note 3 JIS 75M Carbon steel Note 2 ANSI 150LB Carbon steel ANSI 300LB Carbon steel DIN PN16 Carbon steel DIN PN40 Carbon steel Note1 Note 1) Meter size 100A or more cannot be used. Note 2) Meter size 50A or less cannot be used. Note 3) Meter size 250A or 300A can be selected only for A, B and D. 1 2 4 5 6 7 8 A B D E F G H Guide ring (11th code) None 0 Wiring connection port size (12th code) G1/2 female screw G1/2(PF1/2) female screw with water-proof gland G1/2(PF1/2) female screw with union and water-proof gland NPT1/2 female screw Pg 13.5 female screw M20×1.5 female screw Y A B C D E Direction of indicator (13th code) See Fig.1 Horizontal mounting Vertical mounting 1 2 Y A B C 8 Optional specifications (14th code) None Stainless tag plate Parameter setting Parameter setting and stainless tag plate Note) When parameter setting function is used, specify parameters in parameter designation tables 1 and 2. OUTLINE DIAGRAM (Unit: mm) (Wafer type sensor) Wiring lead-in port A 135 222 *2 H *3 *1 *1 With water-proof gland *2 With union and water-proof gland *3 For vertical mounting type, it is mounted with the indicator turned clockwise by 90. øD ød W Note) When earth ring material is tantalum, W is shortened by 4mm. (Stainless tag) Option Detail of "A" 75 ø15 M L1 L2 20 Meter size W ød øD H Mass (Kg) M L1 L2 2.5A 85 2.5 50 226 4 G1/2 13.5 18.5 16 21 6A 85 6 50 226 4 NPT1/2 15A 85 12 50 226 4 Pg13.5 10.5 15 25A 93 22.6 68 244 4.5 M20×1.5 16 21 40A 100 35.6 86 262 5.5 50A 105 47.8 96 272 6 80A 150 72.3 125 301 9.5 100A 160 97.6 160 346 12 150A 190 150 211 397 16.5 200A 205 200 271 457 26.5 9 FMA1, 2 OUTLINE DIAGRAM (Unit: mm) (Flange type sensor) *1 With water-proof gland *2 With union and water-proof gland *3 For vertical mounting type, it is mounted with the indicator turned clockwise by 90. Wiring lead-in port A *2 *1 135 222 *3 H Eye-bolt, meter size 80A or more ød F øD øG øC N-øB T 0 W1 –3 +1 W2 –3 Inside diameter 80A or more Note) When earth ring material is tantalum, W is shortened by 4mm. JIS 10K flange Mass (Kg) 5.5 5.5 7.5 9.5 10.5 øD øC N-øB T JIS 20K øG flange ød H F Mass (Kg) 95 70 4-15 14 46 6 248 — 5.5 5.5 8 10 10.5 øD øC N-øB T JIS 75M øG flange ød H F Mass (Kg) — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 16.5 37.5 18.5 23.5 41 59.5 211 238 290 342 168 195 247 299 4-19 4-19 6-19 8-19 18 18 22 22 121 152 202 260 72.3 97.6 150 200 344 385 436 492 113 124 163 176 19 23.5 36.5 M L1 L2 20 51 95 125 140 155 200 225 305 350 70 90 105 120 160 185 260 305 4-15 4-19 4-19 8-19 8-23 8-23 12-25 12-25 14 16 18 18 22 24 28 30 46 66 82 92 121 152 202 260 12 22.6 35.6 47.8 72.3 97.6 150 200 248 272 28.9 301 339 379 444 496 — — — — 108 118 160 179 Note 1 : For inside diameter 6A, use flange JIS 15A. 10 20.5 (Stainless tag) Option Detail of "A" 75 15A 25A 40A 50A 80A 100A 150A 200A 200 200 200 200 200 250 300 350 206 206 206 206 206 256 306 356 95 125 140 155 185 210 280 330 70 90 105 120 150 175 240 290 4-15 4-19 4-19 4-19 8-19 8-19 8-23 12-23 12 14 16 16 18 18 22 22 46 66 82 92 121 152 202 260 12 22.6 35.6 47.8 72.3 97.6 150 200 248 272 289 301 331 371 431 486 — — — — 102 112 144 171 ø15 6A (Note1) 200 206 95 øD 70 øC 4-15 N-øB 12 T 46 øG 6 ød 248 H — F Meter size W1 W2 54 M L1 L2 G1/2 13.5 18.5 NPT1/2 16 21 Pg13.5 10.5 15 M20×1.5 16 21 Meter size 1/4B (Note2) W1 W2 200 206 89 60.3 4-16 11.5 46 6 245 – øD øC N-øB T ANSI 150LB øG flange ød H F Mass (Kg) øD øC N-øB T ANSI 300LB øG flange ød H F Mass (Kg) 1/2B 200 206 89 60.3 4-16 11.5 46 12 245 – 5 5 95 66.7 4-16 14.5 46 6 248 – 95 66.7 4-16 14.5 46 12 248 – 5.5 5.5 1B 200 206 108 79.4 4-16 14.5 66 22.6 264 – 7 11/2B 2B 3B 4B 6B 8B 200 200 200 250 300 350 206 206 206 256 306 356 127 152 191 229 279 343 98.4 120.6 152.4 190.5 241.3 298.4 4-16 4-20 4-20 8-20 8-23 8-23 17.5 19.5 24 24 25.5 29 82 92 121 152 202 260 35.6 47.8 72.3 97.6 150 200 282 300 334 380 431 493 – – 104 120 144 176 9 11 19 24.5 35.5 58.5 124 156 165 210 254 318 381 88.9 114.3 127 168.3 200 269.9 330.2 4-20 4-23 8-20 8-23 8-23 12-23 12-26 17.5 21 22.5 29 32 37 41.5 66 82 92 121 152 202 260 22.6 35.6 47.8 72.3 97.6 150 200 343 393 450 512 272 297 306 – – – 112 130 165 193 8 11.5 12 22 32 50.5 78.5 Note 2 : For meter size 1/4B, use flange ANSI 1/2B. 6A(Note3) 200 206 95 øD 65 øC N-øB 4-14 16 T øG 46 6 ød H 248 – F Mass 6 (Kg) 15A 200 206 95 65 4-14 16 46 12 248 – øD øC N-øB T øG ød H F Mass (Kg) 95 65 4-14 16 46 6 248 – 6 6 Meter size W1 W2 DIN PN16 flange DIN PN40 flange 25A 200 206 115 85 4-14 18 66 22.6 267 – 40A 200 206 150 110 4-18 18 82 35.6 274 – 50A 200 206 165 125 4-18 20 92 47.8 306 – 80A 100A 150A 200A 200 250 300 350 206 256 306 356 200 220 285 340 160 180 240 295 8-18 8-18 8-22 12-22 20 20 22 24 121 152 202 260 72.3 97.6 150 200 339 376 434 472 108 116 151 175 6 8 10.5 12 18.5 22 35 54 95 65 4-14 16 46 12 248 – 115 85 4-14 18 66 22.6 267 – 150 110 4-18 18 82 35.6 294 – 165 125 4-18 20 92 47.8 306 – 200 160 8-18 24 121 72.3 338 108 – – – – – – – – – – – – – – – – – – – – – – – – 7.5 10.5 12 19.5 – – – Note 3 : For meter size 6A, use flange DIN 15A. 11 FMA1, 2 OUTLINE DIAGRAM (Unit: mm) *1 With water-proof gland *2 With union and water-proof gland *3 For vertical mounting type, it is mounted with the indicator turned clockwise by 90. Wiring lead-in port A *2 *1 135 222 *3 Eye-bolt H N-øB H1 øD øC T W1 W±3 Flange (Stainless tag) Option Detail of "A" Meter size 250A 300A W 595 595 W1 320 360 H 543 598 H1 220 250 400 445 øD JIS 10K øC flange N-øB T Mass (Kg) øD øC JIS 20K N-øB flange T Mass (Kg) øD øC JIS 75M N-øB flange T Mass (Kg) 12 355 400 12-25 16-25 36 38 97 115 430 480 380 430 12-27 16-27 46 48 100 120 410 464 360 414 8-23 10-23 36 38 97 115 75 ø15 M L1 L2 20 L1 L2 G1/2 13.5 18.5 NPT1/2 16 21 Pg13.5 10.5 15 M20×1.5 16 21 M EXTERNAL CONNECTION DIAGRAM Status input / output ST – Power supply ST + PLS – N L – O– PLS + – O+ – Integrated pulse output + Current output FLOW RATE-FLOW VELOCITY CONVERSION DIAGRAM 15.0 Flow velocity [m/ s] 10.0 5.0 2. 1.0 6A 5A 15 A 25 A 40 A 50 A A 0A 80 10 15 0A 00A 50A 00A 2 2 3 0.5 0.1 0.05 0.01 0.05 0.1 0.5 1 5 10 50 100 500 1000 4000 3 Flow rate [m / h] SCOPE OF DELIVERY Main unit (mounting bolt and packing should be prepared separately) Spare parts (spare fuse (1A), guide rings / for wafer type (Note), 1set spare water-proof gland / for water-proof gland type) Note) Not supplied for 2.5A-25A ANSI 150LB and 100A, 200A JIS 10K. ITEMS SPECIFIED AT ORDERING 1. Type, specification code 2. Flow measurement range and mesurement fluid. 3. Stainless tag plate, and tag No. (less than 16 alphanumeric characters). 4. If you want the instrument with certain parameters factory set as you desire, submit the parameter designation tables 1 and 2 when specifying them. 13 FMA1, 2 If you want the instrument with certain parameters factory set as you desire, specify them in parameter designation tables 1 and 2. Company : Name : Measured fluid : <Parameter designation table 1> Standard set value Setting item (Note 1) Damping 3.0s LCD Real scale 1st line indication indication Unit: Factory set as per range designation Sector : Telephone No. : Put check marks into Range 1.0 to 200.0s <1st line, 2nd line> q Flow velocity indication (m/s) w Real scale Volume unit: mL, L, m3 Time unit: /s, /min, /h, /d e Percent indication (%) which precede items to modify for. Item selection or value designation _ _ _._ [s] <Designation of 1st line indication> According to selection of left item, Select an item from the following. designate necessary item and value. □Flow velocity indication Unit: m/s fixed. □Real scale indication Volume unit: □mL, □L, □m3 Time unit: □/s, □/min, □/h, □/d None. □Percent indication □Arbitrary unit indication User factor: ______ Or, for mass flow rate indication, designate the density of measured fluid instead of user factor. Density of fluid:_ _ _ _ _ User unit: ______ Item to select r Arbitrary unit indication User factor: 0.0001 to 99999. User unit: Up to six ASCII code characters. • Must be designated for mass flow rate indication, etc. • If mass flow rate indication (*) □Integrated real scale indication is designated, designate the □Integrated pulse indication density of measured fluid □Integration arbitrary unit instead of user factor. indication t Integrated real scale indication Volume unit: mL, L, m3 y Integrated pulse indication • Separately designate the “integration constant” together. LCD 2nd line indication Percent indication u Integration arbitrary unit indication User factor: 0.0001 to 99999. User unit: Up to four ASCII code characters. •Must be designated for mass flow rate indication, etc. • If mass indication (*) is designated, designate the density of measured fluid instead of user factor. i Status I/O indication Indication of function and action of status I/O selected on 2nd line of LCD (can specify 2nd line only). o NO FUNCTION Do not indicate LCD 2nd line (can specify 2nd line only). 1st range Instantaneous output low-cut point Current output burnout Integration direction Integration constant (Note 2) (integration value per pulse) Integrated pulse width (Note 3) Integration preset value (*): Electromagnetic flow meter is a volumetric flow meter. In case of mass or mass flow rate indication, therefore, any change of density of measured fluid causes an error. Range designated 0.1 to 15 m/s at order placing converted to flow velocity. <Designation of 2nd line indication> Select an item from the following. □Flow velocity indication □Real scale indication □Percent indication □Arbitrary unit indication Example 020.0s 0.9765 t/h 3 Volume unit:□mL, □L, □m * Designate “integration constant” separately. User factor: ______ Or, for mass flow rate indication, designate the density of measured fluid instead of user factor. 0.9765 Density of fluid:_ _ _ _ _ User unit: t ______ According to selection of left item, designate necessary item and value. Unit: m/s fixed. Volume unit: □mL, □L, □m3 Time unit: □/s, □/min, □/h, □/d None. User factor: ______ Or, for mass flow rate indication, designate the density of measured fluid instead of user factor. 0.9765 Density of fluid:_ _ _ _ _ User unit: t/h ______ □Integrated real scale indication □Integrated pulse indication □Integration arbitrary unit indication Volume unit:□mL, □L, □m3 * Designate “integration constant” separately. User factor: ______ Or, for mass flow rate indication, designate the density of measured fluid instead of user factor. 0.9765 Density of fluid:_ _ _ _ _ User unit: t ______ □Status I/O indication □NO FUNCTION Volume unit:□mL, □L, □m3 Time unit: □/s, □/min, □/h, □/d None. None. None. Must be designated in 4 significant digits. 100.0 Value:_ _ _ _ _ _ _ . _% 0.0% 0.0% to 10.0% UNDER SCALE (2.4mA) NOT USED (hold) OVER SCALE (21.6mA) UNDER SCALE (2.4mA) FORWARD REVERSE Value: 0.000000000 to 9999999999. Unit : mL, L, m3 □NOT USED □OVER SCALE □UNDER SCALE □FORWARD □REVERSE Volume unit: □mL, □L, □m3 None. 30ms 0.5 to 80ms None. _ _ . _ [ms] 50.0[ms] 0m3 Value: –9999999999 to +9999999999 Unit : Linked with unit of integration constant. None. __________ 100000 FORWARD 0m3 3.5% None. Value: __________ (Note 1) Standard set value refers to parameter set value as factory set in case parameter setting is not designated. (Note 2) Designate so that 0.0001 to 1000 pulses integrated will be output per second (so that following expression will hold) when flow rate is maximum. 0.0001≦range [m3/h] / (integration constant [m3] × 3600) ≦1000 (Note 3) Designate the integrated pulse width so as to hold: (Integration constant [m3]) × 3600/range [m3/h] ≧ integrated pulse width [ms]/500 14 <Parameter designation table 2> Standard set value Item selection or Setting item Range Item to select Example (Note 1) value designation 3.0% 0.0 to 10.0% _ _._ [%] Integration 5.0% None low-cut point HOLD HOLD None Integration □HOLD COUNT burnout □COUNT NO FUNCTION According to selection on the left, Status Select one of functions designate item and value. function below. None q NO FUNCTION □NO FUNCTION Must be designated in 4 significant digits. w External 2 range changeover □External 2 range 2nd range: _ _ _ _ • 2nd range: 0.1 to 15 m/s 10.00 changeover Volume unit: □mL, □L, □m3 converted to flow velocity. Time unit: □/s, □/min, □/h, □/d • Status input: □INPUT CLOSED INPUT CLOSED (Note 4) □INPUT OPEN INPUT OPEN e External forward/reverse range changeover □External forward/reverse Must be designated in 4 significant digits. • 2nd range: 0.1 to 15 m/s 2nd range: _ _ _ _ 10.00 range changeover converted to flow velocity. Volume unit: □mL, □L, □m3 Time unit: □/s, □/min, □/h, □/d • Status input: □INPUT CLOSED INPUT CLOSED (Note 4) □INPUT OPEN INPUT OPEN □INPUT CLOSED r 0% signal lock □0% signal lock □INPUT OPEN • Status input: INPUT CLOSED (Note 4) INPUT OPEN t External zero adjustment □External zero adjustment □INPUT CLOSED □INPUT OPEN • Status input: INPUT CLOSED (Note 4) INPUT OPEN □INPUT CLOSED □External integration y External integration preset □INPUT OPEN preset • Status input: INPUT CLOSED (Note 4) INPUT OPEN * Designate preset value separately in item of “integration preset value”. Must be designated in 4 significant digits. u Automatic 2 range changeover □Automatic 2 range • 2nd range: 0.1 to 15 m/s 2nd range: _ _ _ _ 10.00 changeover converted to flow velocity. Volume unit: □mL, □L, □m3 Time unit: □/s, □/min, □/h, □/d • Changeover hysteresis: 0.0 to 20.0% (with respect to smaller range). Hysteresis: _ _ . _ % 5.0% • Status output: OUTPUT ON (Note 5) □OUTPUT ON OUTPUT OFF □OUTPUT OFF i Automatic forward/reverse changeover □Automatic forward/reverse Must be designated in 4 significant digits. • 2nd range: 0.1 to 15 m/s 2nd range: _ _ _ _ changeover 10.00 converted to flow velocity. Volume unit: □mL, □L, □m3 Time unit: □/s, □/min, □/h, □/d • Changeover hysteresis: 0.0 to 10.0% (with respect to smaller range). Hysteresis: _ _ . _ % 5.0% • Status output: OUTPUT ON (Note 5) □OUTPUT ON OUTPUT OFF □OUTPUT OFF □Flow switch o Flow switch Upper limit: _ _ _ . _ [%] +90.0[%] • Upper limit: -10.0 to 110.1% Lower limit: _ _ _ . _ [%] –02.0[%] (if 110.1% is selected, upper limit is invalid). • Lower limit: -10.1 to 110.0% □OUTPUT ON (if -10.1% is selected, lower limit is invalid). □OUTPUT OFF • Status output: OUTPUT ON (Note 5) OUTPUT OFF !0 Integration switch □Integration switch Set value: • Set value: ___________ –9999999999 to +9999999999 □OUTPUT ON • Status output: □OUTPUT OFF OUTPUT ON (Note 5) OUTPUT OFF * Unit is the same as set value for integration constant. □Alarm output • Alarm selection !1 Alarm output □ALL FUNCTION • Alarm selection □HARDWARE FAULT ALL FUNCTION, □PROCESS FAULT HARDWARE FAULT, PROCESS FAULT • Status output: • Status output: □OUTPUT ON OUTPUT ON (Note 5) □OUTPUT OFF OUTPUT OFF Empty detection INHIBIT □INHIBIT None INHIBIT function □ENABLE ENABLE TAG-NO Blank unless None ________ F-100 Up to 16 alphanumerics designated ________ Flow FORWARD □FORWARD None FORWARD direction □REVERSE REVERSE (Note 4) Status input specifications: No-voltage contact. 1 kΩ or less when closed. 50 kΩ or more when open. (Note 5) Status output specifications: Capacity; 30V DC or less, 0.2A or less, ON voltage; 2V or less 15 FMA1, 2 Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan