Active Single channel Analog signal Isolation barrier (Vin & Iout) T51/52/61/62_B APPLICATIONS PRODUCT PROGRAM Part Number Power Supply conditioner with electrical insulation between input and output, which can receive the standard or T5230B non-standard analog signal input from the scene, T5130B and transmit a standard output signal to the Analog signal isolating barrier, is a signal control room or DCS, to get three-port isolated among power supply, input and output. It is designed for translating signals of apparatus in hazardous area, isolating and transforming these signals into standard signals which can be Isolation Channels Power Output Input Output 24V 0-10V 0-20mA NONE 24V 0-10V 4-20mA NONE 1 T6135B 24V 0-5V 4-20mA 12V 1 T6230B 24V 0-5V 0-20mA NONE 1 T6233B 24V 0-5V 0-20mA 24V 1 T6235B 24V 0-5V 0-20mA 12V 1 1 Note: We could also offer customer design for special input and output. accepted by industry computer, DCS, PLC, or user-specified special signals. It is widely used in ELECTRICAL CHARACTERISTICS the industrial measurement systems, medical Power Supply (Nominal Power Supply)±5% Power Dissipation ≤2W electricity isolated technology to achieve signal Power Protection Reverse protection isolation, with characteristics of high output Output Voltage (Nominal)±10% electronic equipment, electrical equipment etc. We adopt high efficiency magnetism and accuracy, good linearity and low temperature drift. Power Supply Data Isolation Power Output Data Output Current ≤25mA Input Signal See above Input Impedance ≥10MΩ FEATURES Overload ≤15V ● Three port Isolation(input, output, power supply) Output Signal See above Load ≤500Ω(At Output =20mA) Input Data ● High accuracy (0.1% F.S.) Output Data ● High linearity (0.1% F.S.) ● Isolation voltage(2500VDC/60S) ● High frequency response(15KHz) TRANSMISSION CHARACTERISTICS Offset 0.1%F.S. ● Industry class(Operation temp.: -25℃ to +71℃) Gain Error 0.1%F.S. ● High reliability(MTBF>500,000 hours) Temperature Drift 0.0035%F.S./℃ (-25℃ to +71℃) ● Low temperature drift(35PPM/℃) ISOLATION CHARACTERISTICS MODEL SELECTION TXXXXB Package style Isolation power output Power supply Output Input Isolation amplifier MORNSUN Science & Technology co.,Ltd. Address: 2th floor 6th building, Huangzhou Industrial District, Guangzhou, China Tel: 86-20-38601850 Fax:86-20-38601272 Http://www.mornsun-power.com Galvanic Isolation Three port Isolation(input, output, power supply) Isolation Voltage 2.5KVDC (Tested for 1minute and 1mA max, humidity < 70%) Insulation Resistance 100MΩ,500VDC(Among signal input ,signal output, power supply and isolation power output) OTHER CHARACTERISTICS Ambient temperature Operation temperature:-25℃ to +71℃ Package 35mm DIN-rail package Safety Class IP20(IEC60529 / EN60529) EMC compliance GB/T 18268(IEC61326-1) Weight About 60g Application environment No dusts, gases of fiercely vibration, impulsion or gases that may erode to the components surrounded Transport and Storage temperature:-50℃ to +105℃ Note: 1. All specifications measured at TA=25°C, humidity<75%, nominal input voltage and rated output load unless otherwise specified. 2. Only typical models listed, specifications of custom product may be different. Please contact our service people directly for certain conditions. The copyright and authority for the interpretation of the products are reserved by Mornsun Specifications subject to change without notice. T51/52/61/62_B A/1-2008 Page 1 of 2 SINGLE CHANNEL SCHEMATIC DIAGRAM CONNECTION 2+ Power supply 1- 2 2 1. Cross section area of wiring: 0.5mm -2.5 mm ; 2. Multi-strand wire, the length of bare wire is 8+ Isolation power output 7- about 8mm, fixed by the M4 bolt. 6+ 4+ 5- Output 3- Input Application Note 1. Please read the user manual carefully before using. If any questions please contact our APPLICATION CIRCUIT DIAGRAM technical support department. 2. Please do not use this product in hazardous area. 5(-) 1(-) 6(+) 2(+) 7(-) 3(-) 3. The power supply of this product should be DC Power supply Input Isolation power output power source. It is forbidden to use 220VAC power supply. 4. To avoid equipment invalidation, or any failure, users’ disassembling this product is forbidden. Output 8(+) 4(+) AFTER SERVICE PACKAGING SIZE AND TERMINAL DESCRIPTION 1. Products are carefully inspected and controlled before going out from our factory. If they Power supply- 2+ Power supply+ 3- Output- 4+ Output+ 5- Input- 6+ Input+ 7- Isolation power output- operated abnormally or there were anything wrong in the inner parts, please contact with our agents near you or technical support in our company as soon as possible. 2. 3 years warranty since the delivery date. During the period of quality guarantee, our 98 94.5 MORNSUN 1- company will repair or change free of charge if product has any quality problem in the process of normally using. 8+ Isolation power output+ 41 25 Unit: mm Tolerance:±0.5 INSTALLATION DISASSEMBLY DIN35mm standard rail installation 1. Upside of the instrument card in the rail; 1. Use a screwdriver (Width of edge≤6mm), cut in the metal card lock from the underside; 2. Push underside of the instrument into the rail. 2. Boost up the screwdriver and prize the metal card lock downwards; 3. Pull the instrument out of the rail. 1 3 2 1 2 The copyright and authority for the interpretation of the products are reserved by Mornsun Specifications subject to change without notice. T51/52/61/62_B A/1-2008 Page 2 of 2