CRYDOM 3RHP2450D5

3RHP Series DC Control
• 40 and 50A output
• Voltage ratings to 240 VAC
• Lifetime 2 million operations at full load
• LED input status indicator
• Wire, lug or quick connect termination
• Industry Standard DP contactor mounting
PRODUCT SELECTION
Control Voltage
4.5-5.5 VDC
10-15 VDC
22-27 VDC
40A 120 VAC
50A 120 VAC
40A 240 VAC
50A 240 VAC
3RHP1240D5
3RHP1240D12
3RHP1240D24
3RHP1250D5
3RHP1250D12
3RHP1250D24
3RHP2440D5
3RHP2440D12
3RHP2440D24
3RHP2450D5
3RHP2450D12
3RHP2450D24
OUTPUT SPECIFICATIONS (voltage)
Description
Operating Voltage (47-63Hz) [Vrms]
Maximum Off-State Leakage Current per channel
120 VAC
240 VAC
100-120
0.05 mA @ 120 VAC
208-240
0.06 mA @ 240 VAC
OUTPUT SPECIFICATIONS (current)
Description
40A
Maximum Load Current per phase @ 40°C [Arms] (1)
40A Resistive / 30A Inductive
Power terminals
1/4" Quick Connect and 10x32 binder
head screws
Wire Size
8-14 AWG
50A
50A Resistive / 40A Inductive
1/4" Quick Connect and box lugs
6-14 AWG
INPUT SPECIFICATIONS
Description
Coil Voltage
Max. Reverse Voltage
Input Current
Min. Turn-On Voltage
Min. Turn-Off Voltage
SUFIX D5
SUFIX D12
SUFIX D24
4.5-5.5 VDC
-5.5 VDC
12mA @ 5 VDC
4.5 VDC
1 VDC
10-15 VDC
-15.5 VDC
12mA @ 12 VDC
9.5 VDC
2 VDC
22-27 VDC
-27.5 VDC
12mA @ 24 VDC
9.5 VDC
2 VDC
GENERAL SPECIFICATIONS
Description
Dielectric Strength, Input to Output
Dielectric Strength, Input/Output to ground
Contacts (2)
Ambient Operating Temperature Range (3)
Ambient Storage Temperature Range
Max. Turn-On Time 50/60 Hz
Max. Turn-Off Time 50/60Hz
Maximum Number of Operations
Lifetime Number of Operations @ Rated Current (4)
Weight (typical)
Screw Torque (input/Output) 40A
Screw Torque (input/Output) 50A
Parameters
4000 Vrms
2500 Vrms
Three Normally Open
-20 to 75 °C
-40 to 100 °C
20 ms / 16.6 ms
40 ms / 32 ms
30 per Minute
> 2 Million
1.19 lbs (540 g)
5.31 in lb (0.6 Nm) / 18 in lb (2.1 Nm)
5.31 in lb (0.6 Nm) / 25 in lb (2.9 Nm)
GENERAL NOTES
(1)
(2)
(3)
(4)
See Derating curves for additional operating conditions.
The R HP includes a Solid State Relay, therefore electrical isolation is not provided.
The R HP includes over temperature protection for the solid state relay.
40°C ambient temperature, 30 operations/min, maximum voltage control.
MECHANICAL SPECIFICATIONS
THERMAL DERATE INFORMATION
TYPICAL ELECTRICAL CONNECTIONS
AGENCY APPROVALS
UL/cUL
Rev. 011409
ACCESSORIES
ANNEX - ENVIROMENTAL INFORMATION