CRYDOM 3RHP2440D5

3RHP Series AC Control
• 40 and 50A output
• Voltage ratings to 600 VAC
• Lifetime 2 million operations at full load
• LED input status indicator
• Wire, lug or quick connect termination
• Industry Standard DP contactor mounting
PRODUCT SELECTION
Control Voltage
20-26 VAC
100-130 VAC
208-240 VAC
40A 280 VAC
50A 280 VAC
40A 600 VAC
50A 600 VAC
3RHP2840E
3RHP2840F
3RHP2840G
3RHP2850E
3RHP2850F
3RHP2850G
3RHP6040E
3RHP6040F
3RHP6040G
3RHP6050E
3RHP6050F
3RHP6050G
OUTPUT SPECIFICATIONS (voltage)
Description
Operating Voltage (47-63Hz) [Vrms]
Maximum Off-State Leakage Current per channel
280 VAC
600 VAC
24-280
0.05 mA @ 240 VAC
48-600
0.06 mA @ 480 VAC
OUTPUT SPECIFICATIONS (current)
Description
40A
Maximum Load Current per phase @ 40°C [Arms] (1)
40A Resistive / 30A Inductive
Power terminals
1/4" Quick Connect and 10x32 binder
head screws
Wire Size
8-14 AWG
50A
50A Resistive / 40A Inductive
1/4" Quick Connect and box lugs
6-14 AWG
INPUT SPECIFICATIONS
Description
Coil Voltage [50/60 Hz]
Min. Turn-On Voltage
Min. Turn-Off Voltage
Coil Power Consumption, inrush.
Coil Power Consumption, sealed.
SUFIX E
SUFIX F
SUFIX G
20-26 VAC
20 VAC
12 VAC
56 VA @ 220 VAC
6.6 VA @ 220 VAC
100-130 VAC
100 VAC
24 VAC
56 VA @ 220 VAC
6.6 VA @ 220 VAC
208-240 VAC
208 VAC
48 VAC
56 VA @ 220 VAC
6.6 VA @ 220 VAC
GENERAL SPECIFICATIONS
Description
Dielectric Strength, Input to Output
Dielectric Strength, Input/Output to ground
Contacts (2)
Ambient Operating Temperature Range (3)
Ambient Storage Temperature Range
Max. Turn-On Time 50/60 Hz
Max. Turn-Off Time 50/60Hz
Maximum Number of Operations
Lifetime Number of Operations @ Rated Current (4)
Weight (typical)
Screw Torque (input/Output) 40A
Screw Torque (input/Output) 50A
Parameters
4000 Vrms
2500 Vrms
Three Normally Open
-20 to 65 °C
-40 to 100 °C
20 ms / 16.6 ms
40 ms / 32 ms
30 per Minute
> 2 Million
1.19 lbs (540 g)
10 in lb (1.13 Nm) / 18 in lb (2.1 Nm)
10 in lb (1.13 Nm) / 25 in lb (2.9 Nm)
GENERAL NOTES
(1)
(2)
(3)
(4)
See Derating curves for additional operating conditions.
The R HP includes a Solid State Relay, therefore electrical isolation is not provided.
The R HP includes over temperature protection for the solid state relay.
40°C ambient temperature, 30 operations/min, maximum voltage control.
MECHANICAL SPECIFICATIONS
THERMAL DERATE INFORMATION
TYPICAL ELECTRICAL CONNECTIONS
AGENCY APPROVALS
UL/cUL
Rev. 011409
ACCESSORIES