MPD AD1072-12F

AD1072F Series
Very Low Cost, 72W
DIN Rail Mount
Single Output
AC/DC Power Supplies
Key Features:
• 72W Output Power
• DIN Rail Mountable
• Universal AC Input
• UL 508 Compliant
• EN60950 Compliant
• 12, 24 & 48 VDC Outputs
• Cond./Rad. EMI Class B
• >150 kH MTBF
• LOW COST!
New Industrial
Supplies!!
Electrical Specifications
Specifications typical @ +25°C, nominal input voltage & rated output current, unless otherwise noted. Specifications subject to change without notice.
Input
Parameter
Conditions
Universal
Input Voltage Range
Input Frequency
Min.
100
127
47
110 VAC
220 VAC
264 VAC
Inrush Current, Cold Start
Leakage Current
Typ.
Max.
240
370
63
22
44
1.8
Units
VAC
VDC
Hz
A
A
mA
Output
Parameter
Output Voltage Accuracy
Output Voltage Adjustment Range
Line Regulation
Load Regulation (Note 1)
Hold Time
RoHS Compliant
Models available
to 360W! Call
today for details
MicroPower Direct
292 Page Street
Suite D
Stoughton, MA 02072
USA
T: (781) 344-8226
F: (781) 344-8481
E: [email protected]
W: www.micropowerdirect.com
Ripple & Noise (20 MHz) (Note 2)
Output Power Protection
Transient Recovery Time (Note 3)
Transient Response Deviation
Temperature Coefficient
Output Short Circuit
Conditions
Min.
Typ.
Max.
±0.5
±10.0
Vin = Min to Max
±1.0
Iout = 20% to 100%
±1.0
110 VAC, Full Load
10
220 VAC, Full Load
20
See Model Selection Guide
Power Limit 130
160
2
50% Load Change
5
±0.04 ±0.05
Continuous With Autorecovery
Units
%
%
%
%
mSec
%
mS
%
%/ºC
General
Parameter
Isolation Voltage
Isolation Resistance (Note 4)
Switching Frequency
Conditions
Input - Output
Input - FG (Frame Ground)
Output - FG (Frame Ground)
500 VDC
Fixed
Min.
3,000
2,000
500
100
Typ.
Max.
Units
VAC
80
MΩ
kHz
Environmental
Parameter
Operating Temperature Range
Storage Temperature Range
Cooling
Humidity
Vibration
Conditions
Min.
Typ.
Max.
Units
-20
+25
+50
ºC
-20
+85
ºC
Free Air Convection
RH, Non-condensing
95
%
10 Hz ~ 2 kHz; 2G 10 min./1 Cycle; X, Y, Z axis each 1 hour
Ambient
Physical
Case Size
Case Material
Connection
4.76 x 4.33 x 2.2 Inches (121.0 x 110.0 x 56.0 mm)
Aluminum (Base) and Steel (Cover)
Screw Terminal
Reliability Specifications
Parameter
MTBF
Safety Standards
EMI Compliance
EMS Immunity Compliance
Conditions
MIL HDBK 217F, 25ºC, Gnd Benign
Min.
Typ.
Max.
Units
150
kHours
UL 1950, EN 60950, IEC 60950
Compliance to EN55011, EN55022 (CISPR22) Class B
EN6100-4-2,3,4,5,6,8,11 Level 3
Model Selection Guide
Model
Number
Rated
Power
(W)
AD1072-12F
AD1072-24F
AD1072-48F
72
72
72
Input
Voltage (VAC)
Output
Current (A)
Universal Range 115 VAC 230 VAC
100 - 240
1.0
0.5
100 - 240
1.0
0.5
100 - 240
1.0
0.5
Notes:
1. Load regulation is specified for a load change
of 20% to 100%.
2. Ripple & noise is measured using equipment
with 20 Mhz of bandwidth with the unit under
test operating at rated load and a 110 VAC
input. Connection to the unit is made with a
0.1 μF / 630V metalized capacitor & a 47 μF
electrolytic capacitor connected in parallel.
3. Transient recovery is measured to within a 1%
error band for a load step change of 50% to
100%.
4. Isolation resistance is given for Input/Output
and Input/FG. For Output/FG., it is 50 MΩ
5. Overload protection is power limiting. The
unit recovers automatically when the fault is
removed.
6. Over voltage protection is a shut down type.
The unit recovers automatically when the fault
is removed.
7. To mount the unit to the DIN rail, tilt the unit
rearwards from the top, fitting the mount over
the top of the rail. Press back on the bottom
front of the unit until it locks in place on the
rail. To remove the unit from the rail, pull the
removal clip at the bottom rear of the unit
downward with a screw driver. With the clip
down, lift up on the unit from the bottom
front until it clears the rail. Before installation
or removal all wiring should be disconnected
and the main power to the system shut off.
8. When wiring the supply, all lines should be
as thick and short as possible. AWG 14 wire is
recommended for the AD1072F series.
9. The units should be mounted so they are
vertically orientated. Air flow (if it is provided)
would optimally flow from the bottom to the
top of the unit.
10. It is recommended that a fuse be used on the
input of a power supply for protection. For
the AD1072F series a 250VAC 2.0A is recommended.
Voltage Current (A) Current (A)
(VDC)
Max)
Range
12
24
48
6.0
3.0
1.5
Overvoltage
Protection
(VDC)
Ripple &
Noise
15 ~ 17
27 ~ 30
52 ~ 56
100
150
250
0 ~ 6.0
0 ~ 3.0
0 ~ 1.5
(mV p-p)
Efficiency
(%, Typ)
78
81
82
Derating Curve
Mechanical Dimensions
Units with the optional “FT” outputs may be
easily connected for “Fault Tolerant operation.
Contact the factory for details
Connections TB 1
Pin
Function
1
DC Output (+V)
2
DC Output (-V)
3
FT (Optional)
4
FT (Optional)
5
Frame Ground (FG)
6
AC Input - Neutral
7
AC Input - Live
Notes:
• All dimensions are typical in inches (mm)
• Tolerance x.xx = ±0.01 (±0.25)
MicroPower Direct
www.micropowerdirect.com
292 Page Street Ste D Stoughton, MA 02072
•
TEL: (781) 344-8226
•
FAX: (781) 344-8481
•
E-Mail: [email protected]