FUJI EDS11-119D

FC SERIES
COMPACT CALCULATOR
DATA SHEET
PNM3
The FC series compact calculator is a high cost-performance, flexible, and highly functional calculator which inputs
5 analog signals and 6 digital signals, digitally performs complex calculations such as arithmetic, square root extraction,
time-factor calculations, etc., and then provides 5 analog
and 6 digital outputs.
FEATURES
1. Highly functional calculator using a microprocessor
A variety of calculating functions are coordinated into
functional units called wafers. Complex calculations are
thus performed flexibly and accurately through connection
of the computational wafers.
2. International standards
This instrument is compact in size, conforming to international standards IEC. It operates on 24V DC power to
deliver 1 to 5V DC signals as recommended by IEC
standards.
100V and 200V AC power are also available for convenience of operation.
3. Contents of calculation are changeable on the spot
The contents of calculation can be specified on the spot
by means of key operation on the front. And the contents
are retained even at power failure due to utilization of a
non-volatile memory.
FUNCTIONAL DIAGRAM
EDS11-119d
Date
Aug. 15, 1996
PNM3
SPECIFICATIONS
1. Computational functions
(1) Wafers
The wafer is a functional software package which realizes
the computational functions needed for instrumentation control. A calculator which responds flexibly to the application
purpose is realized through combination of these wafers
having their own individual functions.
The PNM is capable of executing a total of either 24, 48 or
64 wafers. The wafers given in the table below are standardequipped which enables selection according to the purpose of
application.
• For computation: A variety of computations are feasible by
combining the wafers in Table 1.
(2) Internal input/output terminals
Various internal terminals for connecting external analog
input/outputs and digital input/outputs with wafers are provided.
(3) Constants
These can be freely defined as parameters for use in calculation. (32 constants with 24 wafers, 48 constants with 48
wafers, 64 constants with 64 wafers)
Table 1 List of computational wafers
Wafer name
Kinds
Outline of functions
Logical computation
6
Performs logical computation such as AND, OR, NOT, EOR and a combination of these.
Arithmetic computation
5
Performs computation such as addition, subtraction, multiplication and division.
Temperature/pressure
compensation
1
Performs temperature/pressure compensation using differential pressure, correcting pressure and/or proper
temperature.
Linearize
3/6/8
Performs segmented line approximation using 15 segmented line functions (6 kinds with 48 wafers, 8 kinds with
64 wafers).
Flip-flop
1
RS flip-flop
Pulse width integration
1
Adds the input change amount at each basic cycle to the previous integrated value.
Selector
1
Compares two input values, and outputs the result of high/low judgment as HIGH output (higher one) or LOW
output (lower one).
Changeover
1
A switch function which selects either input or output. An analog hold circuit can also be combined.
Timer
1
Outputs an on-delay/off-delay timer signal via input signal start according to the timer setting.
Square root computation
1
Subjects an input value to square root extraction and outputs the result. Also has a low input cutoff function.
Lead, lag
3
Subjects the input to lead or lag computation and outputs the result. Used for analog filter function and various
compensations.
Limiter
1
Limits the input within the range of upper/lower limit setting and outputs the result. Also outputs an upper/lower
limit alarm signal.
Absolute value sign
inversion
1
Subjects the input to absolute value processing and outputs the result. Also judges the input value sign (positive,
negative) and outputs the results.
Ramp function
2
Outputs a signal which changes in ramp-like form toward the target value within the set full-scale time. Includes
two kinds for minute and hour unit.
Analog average
1
Subjects the input data to sequential integration, calculates the average for each average value calculation time
and outputs the result.
Analog integration
1
Integrates the value obtained by multiplying the input data via a proportional constant, and outputs the result.
Pulse generation
1
Outputs a pulse at a set time interval.
Dead band
1
Adds dead band compensation to the input and outputs the result.
Pulse number counter
1
Detects the rise of a pulse and counts the number of pulses.
Pulse number output
1
Integrates the input signal, converts it to number of pulses and outputs the result.
Decoder
1
Decodes binary input of two bits and outputs it at 4 terminals.
Moving average
2
Calculates moving average for the input data and outputs the result.
Sample hold
1
Holds the input value according to sample time and outputs it successively.
Dead time
9
Usable for dead time compensation control, etc. Data sampling is available in units of 1 second and 1 minute.
On-off
1
Outputs an on-off signal with hysteresis versus the input.
Alarm
1
Compares the input with the set value, and outputs the judgment result.
Position type pulse width
change
1
Performs output processing for time-proportional PID control.
Various applications are feasible by combining encoder, saw-tooth wave generating and sine wave generating wafers.
2
2. Input signal
(2) Digital data
(1) Analog input signal Al1:
One point selectable from the following inputs
Input/output status
Data
ON (contact closed)
0.01%
0.00%
Voltage input
signal
1 to 5V DC
Input resistance: 1MΩ or more;
accuracy: ± 0.2%/FS(*)
OFF (contact open)
Current input
signal
4 to 20mA DC
24 ± 2V DC can be supplied to
transmitter when using AC
source; accuracy: ± 0. 2%/FS
5. Indication, setting, operating functions
Type
J :0 to 600°C
K:0 to 1200°C
E:0 to 800°C
R:0 to 1600°C
10mV DC span or more; cold
junction compensation
comprised
accuracy: ± 0.5%/FS
Pt100
–50 to 500°C
50°C span or more; accuracy:
± 0.5%/FS
Thermocouple input
I+
I0
I–
Resistance
bulb input
(2) Analog input signal: 4 points
Analog input
AI2
Analog input
AI3
Analog input
AI4
Analog input
AI5
Input resistance: 1MΩ or more
Accuracy: ± 0.2%/FS
1 to 5V DC
(3) Digital input signal: 4 points
Digital input
DI1
Digital input
DI2
Digital input
DI3
Digital input
DI4
Contact input
(photocoupler
insulation)
ON/0V, OFF/24V (input current
approx. 11mA/24V DC)
(4) Pulse width or pulse number input signal: One set
Pulse width
input signal
Pulse number input
signal
Contact input
(photocoupler
insulation)
PI+
PI–
ON/0V, OFF/24V (input current
approx. 11mA/24V DC)
ON/0V, OFF/24V (approx.
11mA/24V DC); input max.
frequency: 500Hz
3. Output signal
(1) Current output signal: One point
MI+
MI–
Current output
4 to 20mA DC
Allowable load resistance:
600Ω or less; accuracy:
± 0.2%/FS
(2) Analog output signal: 4 points
Analog output
AO1
Analog output
AO2
Analog output
AO3
Analog output
AO4
1 to 5V DC
Output resistance: 1Ω or less;
accuracy: ± 0.2%/FS
(3) Digital output signal: 6 points
Fault output
FLT
Digital output
DO1
Digital output
DO2
Digital output
DO3
Digital output
DO4
Digital output
DO5
(1) Bargraph indication
Indicator
RV indicator
Indication type
LED (red)
LED (green)
No. of segments
101+2
101+2
Range
0 to 100% linear
0 to 100% linear
Resolution
1%/FS
1%/FS
Scale length
100mm
100mm
Indication mode
0 to 100% bargraph indication
0 to 100% reverse bargraph indication
dot indication
–50 to +50% deviation indication
GV indicator
(2) Run mode indication
Indicating method:
LED (red); red, H/L
(3) Numerical indication, setting
Indication method:
LED (red), name in 3 digits+numerals 5
digits (including negative sign)
Indication contents:
Indication contents such as constants,
segmented line and wafers selectable by
and
keys on the front.
F/S ,
Setting method: By operation of F/S , , , , and ST
keys on the front.
6. Power failure processing function
Power failure detection:
Calculation stops at power failure detection.
During power failure:
Operating parameters retained by capacitor backup within 5 minutes. Constants,
segmented line, wafers, parameters etc.
are stored in non-volatile memory (lasts
for 10 years expected at ambient temperature below 50 °C).
At power recovery:
Initial or continuous start mode can be set
versus power failure within 5 minutes.
Recovery from power failure lasting
longer than 5 minutes is done by initial.
7. Self-diagnosis functions
Open collector output
(Photocoupler insulation)
Output rating
30V x 0.1A DC
max.
4. Internal uniform data conversion
(1) Analog data
Standard
Minimum
Maximum
0.00 to 100.00%
–327.6%
327.67%
Computing circuit fault:
H, L lamp simultaneously lit FLT contact
output ON, computation stops
Input/output signal fault, run output disconnection:
H, L lamp simultaneously lit; FLT contact
output ON, computation and output processing for other than run output continue.
Fault contents indication:
Cause of fault is numerically indicated on
front-panel numerical indicator
Note: *FS: Full scale
3
PNM3
8. Transmission functions
(1) Transmission items
Monitor items: PNM
host
Fault information, constants, analog input/
output, digital input/output, etc.
Setting, operating items:
Host
PNM
Constants, etc.
(2) Transmission setting inhibit:
Parameter setting enable/inhibit can be designated by
transmission from the host. Deisgnation is done by keys
on the front panel.
(3) Transmission interface
(a) T-link: Private interface
Transmission speed: 500Kbps
No. of units connectable: 32 max.
Transmission distance: 1km max.
Transmission form: Multi-drop
Control method: I/O transmission and message
(b) RS-422A/485: Universal interface
Transmission speed: 2400, 4800, 9600 or 19200bps
configurable
No. of units connectable: 31 max.
Transmission distance: 1km max.
Transmission form: Multi-drop
Control method: Polling/selecting
9. Other functions
Mounting method:
Indoor panel mounting, vertical mounting
standard, can be tilted within following
angle
α = 0° to 90°
Finish color:
Front panel; Munsell N1.5
Casing; Munsell N1.5
Scope of delivery: Calculator and mounting bracket
Item to be ordered separately:
Transmission cable (type PNZ)
CODE SYMBOLS
1 2 3 4 5 6 7 8
P NM 3
9 10 11
Description
5 - 0
Measured input signal
1 to 5V DC
4 to 20mA DC with 24V DC power supply
J thermocouple
10mV DC span or
K thermocouple
more, with cold juncE thermocouple
tion compensation
R thermocouple
Resistance bulb, Pt100
3-wire type, 50 °C span or more
A
B
C
D
E
F
G
Data protective function using pass code
10. Usage conditions
Power supply:
Selectable from three types
24V DC (20 to 30V DC), 100V AC (85 to
132V AC/47 to 63Hz), 200V AC (187 to
264V AC/47 to 63Hz)
Power consumption:
Approx. 12W (DC), approx. 20VA (AC)
Dielectric strength:
1500V AC for 1 minute
Insulation resistance:
100MΩ or more at 500V DC
Ambient temperature:
0 to 50 °C
Ambient humidity:
90% RH or less
Enclosure:
Steel plate casing
Casing protective structure:
Front section (IP65, IEC 529)
Rating plate (Name plate):
100 (H) x 70 (W), white acrylic resin
Outer dimensions:
144 (H) x 72 (W) x 407 (D) mm, conforming to IEC (DIN) standards
Mass {weight}: Approx. 2.9kg
4
Auxiliary input
four 1 to 5V DC input
two 4 to 20mA DC with 24V DC power
supply plus two 1 to 5V DC input
B
C
Power supply
24V DC (20 to 30V DC)
100V AC (85 to 132V AC/47 to 63Hz)
200V AC (187 to 264V AC/47 to 63Hz)
1
2
3
Transmission functions
None
T-link
RS-422A
RS-485
Y
T
R
S
0
2
4
Available wafer numbers
24 wafers
48 wafers
64 wafers
The product conforms to the requirements of the
Electromagnetic compatibility Directive 89/336/EEC as
detailed within the technical construction file number
TN510402. The applicable standards used to demonstrate
compliance are :-
EN 55011 : 1991 CLASS A
Conducted and Radiated emissions
EN 50082-1 :-1992
Radiated immunity, ESD and FBT
OUTLINE DIAGRAM
(Unit:mm)
Panel thickness 8mm or less
16
144
Terminals
Supporting
bracket
52
Mounting
bracket
200min.
72
355
Panel cutout
When mounting "n" units
138
+1
0
250 or more
138
+1
0
200 or more
When mounting 1 unit
68 +0.7
0
(72.2n – 4)
CONNECTION DIAGRAM
01
AI2
I+
31
02
AI3
Io
32
03
AI4
I–
33
04
AI5
AO1
34
05
AO4
AO2
35
AO3
36
AO
(Aux. analog output)
AO
(Aux. analog output)
AO
(Aux. analog output)
SC
37
AI, AO Common bus
Not use
06
Al, AO Common bus
07
SC
08
SC
SC
38
09
SO1
SO2
39
10
IR1
IR2
40
11
IO1
IO2
41
12
MI+
DI4
42
13
MI–
DI1
43
14
PI+
DI2
44
15
PI–
DI3
45
16
DO4
DO2
46
17
DO5
DO1
47
18
FLT
DO3
48
19
PCD
VPD
49
20
PCD
VPD
50
21
PC*
VP*
51
G
AC AC
71
72
Analog input (AI1)
1 to 5V DC signal output
1 to 5V DC signal output
–
+
AO
(current output)
+
–
DI
(Pulse input)
DO
(Aux. digital output)
DO
(Aux. digital output)
DO
(FLT output)
24V DC power for DI, DO
24V DC power for DI, DO
Instrument power
(24V DC)
+1
0
Compression Terminal
AI
(Aux. analog input)
AI
(Aux. analog input)
AI
(Aux. analog input)
AI
(Aux. analog input)
AO
(Aux. analog output)
DC power for
Transmitter
No. of units
n=
>2
–
–
–
–
+
+
+
+
DC power for
Transmitter
DO
(Aux. digital output)
DI
(Aux. digital input)
DI
(Aux. digital input)
DI
(Aux. digital input)
DO
(Aux. digital output)
DO
(Aux. digital output)
DO
(Aux. digital output)
24V DC power for DI, DO
Instrument power
(24V DC)
Note: * symbols for AC instrument power are VPO, PCO.
Output: Approx. 24V DC (0.1A, max.)
73
Ground
Instrument power (AC)
Instrument power (AC)
5
PNM3
Analog input (AI1) terminals connections
1 to 5V DC
+
Thermocouple
31
The 5th digit of
code symbols
C,D,E,F
32
The 5th digit of
code symbols A
4 to 20mA DC
The 5th digit of
code symbols B
–
33
+
+
31
–
–
33
+
31
–
33
+
+
31
–
–
33
+
31
–
33
32
Resistance bulb
The 5th digit of
code symbols G
32
32
+
4 to 20mA DC
with inner DC
power supply
of CC-S
–
32
The 5th digit of
code symbols B
PC
21
Transmission connector
1 SIG GND
6
7
8 RXD +
9 RXD –
1 SIG GND
6
2 SHLD(SD)
3 INH
4 TXD + (T1)
2 SHLD(SD)
Black
7
White
8 RXD +
9 RXD –
5 TXD – (T2)
Green
3 INH
4 TXD + (T1)
5 TXD – (T2)
Yellow
Note:Symbol in ( ):
T-link terminal symbol
Brown
Red
6
7
8 RXD +
9 RXD –
1 SIG GND
1 SIG GND
6
2 SHLD(SD)
7
3 INH
8 RXD +
4 TXD + (T1)
9 RXD –
5 TXD – (T2)
2 SHLD(SD)
Black
3 INH
White
4 TXD + (T1)
5 TXD – (T2)
TERMINATION
RESISTOR
Green
Yellow
Red
Brown
Final controller
HOST
MASTER
CONTROLLER
1st controller
Host
Termination
resistor
Transmission cable
PNM3
PNM3
PNM3
PNM3
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan