FUJI EDS6-85E

FCX – A SERIES
DIFFERENTIAL PRESSURE TRANSMITTER
FHC, FKC...2
DATA SHEET
The FCX –A differential pressure transmitter accurately
measures differential pressure, liquid level or gauge pressure
and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitive silicon
sensor with state-of-the-art microprocessor technology to
provide exceptional performance and functionality.
FEATURES
1. High accuracy
0.1% accuracy for all calibrated spans is a standard
feature for all DP models covering 0.1kPa{1m bar} draft
range to 3000kPa{30 bar} high differential. Fuji's microcapacitance silicon sensor assures this accuracy for all
elevated or suppressed calibration ranges without
additional adjustment.
2. Minimum environmental influence
The "Advanced Floating Cell" design which protects the
pressure sensor against changes in temperature, static
pressure, and overpressure substantially reduces total
measurement error in actual field applications.
3. Smart / Traditional convertible
Fuji micro-electronics manufacturing technology offers
free selection of Smart / Traditional transmitters.
A small plug-in communication module upgrades your
model FHC to smart type model FKC, which has full
remote communication capabilities. A Hand Held
Communicator (HHC), model FXW can remotely display
or reconfigure all transmitter parameters at any point
on the loop without affecting the transmitter signal.
4. Fuji/HART bilingual communication module
The communication module is "bilingual" to speak both
Fuji proprietary protocol and HART. Any HART compatible
devices can communicate with FCX-A/C series transmitters.
5. Application flexibility
Example options that render the FCX –A suitable for
almost any process applications includes.
– Analog indicator at either the electronics side or
terminal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrestor
– 4 12 digits LCD meter
– Stainless steel electronics housing
– Wide selection of materials
SPECIFICATIONS
Functional specifications
Type:
Model FHC: 4 to 20mA, Traditional type
Model FKC: 4 to 20mA with digital signal, Smart type
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Span limit [kPa]
{m bar}
Type
Static pressure
[MPa] {bar}
Min.
FHC
F C 11 –0.1 to + 3.2
{–1 to + 32}
F C 22 –0.1 to + 10
{–1 to + 100 }
F C 23 –0.1 to + 10
{–1 to + 100 }
F C 24 –0.1 to + 10
{–1 to + 100 }
F C 25 –0.1 to + 10
{–1 to + 100 }
F C 26 –0.1 to + 10
{–1 to + 100 }
F C 33 –0.1 to + 16
{–1 to + 160 }
F C 34 –0.1 to + 16
{–1 to + 160 }
F C 35 –0.1 to + 16
{–1 to + 160 }
F C 36 –0.1 to + 16
{–1 to + 160 }
F C 38 –0.1 to + 16
{–1 to + 160 }
F C 43 –0.1 to + 42
{–1 to + 420 }
F C 44 –0.1 to + 42
{–1 to + 420 }
F C 45 –0.1 to + 42
{–1 to + 420 }
F C 46 –0.1 to + 42
{–1 to + 420 }
F C 47 –0.1 to + 42
{–1 to + 420 }
{
{
{
{
{
{
{
{
{
{
{
{
{
{
{
{
0.1
1}
0.6
6}
3.2
32 }
6.4
64 }
13
130 }
50
500}
3.2
32}
6.4
64 }
13
130 }
50
500 }
300
3000 }
3.2
32 }
6.4
64 }
13
130 }
50
500 }
200
2000 }
FKC
{
{
{
{
{
{
{
{
{
{
{
{
{
{
{
{
0.1
1}
0.1
1}
0.32
3.2 }
0.64
6.4 }
1.3
13 }
5
50 }
0.32
3.2 }
0.64
6.4 }
1.3
13 }
5
50 }
30
300 }
0.32
3.2 }
0.64
6.4 }
1.3
13 }
5
50 }
20
200 }
Range limit
[kPa] {m bar}
Max.
FHC/FKC
{
{
{
{
{
{
{
{
{
{
{
{
{
{
{
{
+/–
1
{ +/–
10 }
+/–
6
{ +/–
60 }
+/–
32
{ +/–
320 }
+/–
64
{ +/–
640 }
+/–
130
{ +/– 1300 }
+/–
500
{ +/– 5000 }
+/–
32
{ +/–
320 }
+/–
64
{ +/–
640 }
+/–
130
{ +/– 1300 }
+/–
500
{ +/– 5000 }
+/– 3000
{ +/– 30000 }
+/–
32
{ +/–
320 }
+/–
64
{ +/–
640 }
+/–
130
{ +/– 1300 }
+/–
500
{ +/– 5000 }
+/– 2000
{ +/– 20000 }
1
10 }
6
60 }
32
320 }
64
640 }
130
1300 }
500
5000 }
32
320 }
64
640 }
130
1300 }
500
5000 }
3000
30000 }
32
320 }
64
640 }
130
1300 }
500
5000 }
2000
20000 }
Remark : To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
EDS6-85e
Date
May. 31, 2000
FHC, FKC...2
– Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor: See Fig. 1
F C 38 and F C 47: –0.5kgf/cm2
Fluorinated fill sensor: 66kPa abs (500mmHg abs)
at temperature below 80°C
– The maximum span of each sensor can be converted
to different units using below factors.
1MPa= 103KPa=10bar=10.19716kgf/cm2=
145.0377psi
1kpa=10mbar=101.9716mmH2O=4.01463inH2O
Over range limit: To maximum static pressure limit
Output signal:
Model FHC: 4 to 20mA DC 2-wire, linear signal
Model FKC: 4 to 20mA DC (linear or square root) with
digital signal superimposed on the 4 to
20mA signal
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
Load limitations: see figure below
[Ω]
Load resistance
2000
1533Ω
1500
1000
600Ω
Operating
area
500
24V
250
10
16.1
10.5V
Power voltage
45V
50
[V]
Note: For communication with FXW, min. of 250 Ω required.
Hazardous locations:
Authorities
BASEEFA
Factory
Mutual
CSA
RIIS
SAA
Flameproof
Ex ds IIC T5, T6
Class I II III
Div. 1
Groups B thru. G
Class I II III
Div. 1
Groups C thru. G
Ex ds IIB+H2 T4
Ex d II C T5, T6
IP66/67
Intrinsic safety
EEx ia IIC T4, T5
Class I II III
Div. 1
Groups A thru. G
Class I II III
Div. 1
Groups A thru. G
—
Ex ia IIC T5, T6
IP66/67
Type N
Nonincendive
Ex N II T5
Class I II III
Div. 2
Groups A thru. G
Class I II III
Div. 2
Groups A thru. G
—
Ex n IIC T5, T6
IP66/67
Model FKC: Zero and span are adjustable from the
HHC. Zero is also adjustable externally
from the adjustment screw.
Damping:
Adjustable electrical damping.
Model FHC: The time constant is adjustable to 0, 0.3,
1.2, 4.8, or 19.2 seconds.
Model FKC: The time constant is adjustable between 0
to 38.4 seconds. (4 steps)
Zero elevation/suppression:
–100% to +100% of URL
Normal/reverse action:
Model FHC: Selectable by moving a jumper pin located
on the electronics unit.
Model FKC: Selectable from HHC
Indication:
Analog indicator or 4 12 digit LCD meter, as
specified.
Burnout direction:Output hold
Output 21.6mA selectable
Output 3.8mA
Model FHC: Unless otherwise specified, the burnout is
in hold position.
Model FKC: Selectable from HHC
Loop-check output:
Model FHC: Transmitter can output constant signal of
4mA, 12mA, or 20mA if MODE SWITCH
is set to the loop check mode.
Model FKC: Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA by
HHC.
Temperature limit: Ambient: – 40 to +85°C
(–20 to +80°C for LCD indicator)
(– 40 to +60°C for arrester option)
(–10 to +60°C for fluorinated oil filled
transmitters)
For explosionproof units (flameproof or
intrinsic safety), ambient temperature
must be within the limits specified in
each standard.
Process: – 40 to +120°C for silicone fill
sensor
–20 to +80°C for fluorinated oil fill sensor
Storage: – 40 to +90°C
Humidity limit:
0 to 100% RH
Communication: (Model FKC only)
With HHC (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
}
Items
Zero/span adjustment:
Model FHC: Zero is adjustable from the external adjustment screw.
The adjustment screw can also function
to adjust span when MODE SWITCH (located on the electronics unit) is in the
span mode. INHIBIT mode to disable the
adjustment screw is also available.
Tag No.
Model No.
Serial No.
Engineering unit
Range limit
Measuring range
Damping
Output mode
Burnout direction
Adjustment
Output adjust
Data
Self diagnoses
Printer
External switch lock
Transmitter display(*)
Display
Set
v
v
v
v
v
v
v
v
v
v
—
v
v
—
v
v
v
v
—
v
—
v
v
v
v
v
v
—
—
—
v
v
Note: (*) HHC's version must be more than 5.0 (or
FXW
1– 2), to use this function.
2
Performance specifications
Accuracy rating: (including linearity, hysteresis, and repeatability)
For spans greater than 1/10 of URL: ± 0.1% of span
For spans below 1/10 of URL (Model FKC only):
0.1 × URL
± 0.05+0.05
% of span
Span
Option 0.075%
Linearity:
0.05% of calibrated span
Stability:
± 0.1% of upper range limit (URL) for 24
months
Temperature effect:
Effects per 55°C change between the limits of – 40°C and +85°C
)
(
Range code
(6th digit in Code Zero shift
symbols)
“1”/1kPa
{10mbar}
max. span
“2”/6kPa
{60mbar}
max. span
Total effect
± 0.25+0.2 URL %/55°C
Span
(
)
“3”/32kPa
{320mbar} max.
span
“4”/64kPa
{640mbar} max.
span
“5”/130kPa
{1300mbar} max.
± 0.2+0.05 URL %/55°C
span
Span
“6”/500kPa
{5000mbar} max.
span
“7”/2000kPa
{20000mbar} max.
span
“8”/3000kPa
{30000mbar} max.
span
(
)
± 0.3+0.2 URL %/55°C
Span
(
)
± 0.25+0.05 URL %/55°C
Span
(
)
“1” /1kPa {10m bar} sensor
“2” /6kPa {60 m bar} sensor
“2”
“3”
“4”
Zero shift
(% of URL)
Range code
Time constant
“1”
0.8 s
“2”
0.5 s
“3”
0.3 s
“4” through “8”
0.2 s
Dead time
approx. 0.3 s
Mounting position effect:
Zero shift, less than 0.12kPa {1.2m bar} for
a 10° tilt in any plane.
No effect on span.
This error can be corrected by adjusting Zero.
(Double the effect for fluorinated fill sensors)
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator: 12Ω or less.
Performance specifications for square root output:
(Model FKC only)
Accuracy rating:
Span
Output
Double the effects for material code (7th
digit in Code symbols) “H”, “M”, “T”,
“B”, “L” and “U”.
Static pressure effect:
Static pressure code
(5th digit in Code symbols)
Supply voltage effect:
Less than 0.05% of calibrated span per 10V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Step response: (without electrical damping)
Span shift
(% of calibrated span)
±0.2% / 1MPa{10bar} –0.2% /3.2MPa{32bar}
±0.2% / 3.2MPa{32bar} –0.2% /3.2MPa{32bar}
±0.1%/10MPa{100bar} –0.2%/10MPa{100bar}
Double the Zero shift for material code
(7th digit in Code symbols) “H”, “M”,
“T”, “B”, “L” and “U”.
Overrange effect:
over 0.1 × URL
below 0.1 × URL
50 to 100%
± 0.1%
± (0.05+0.05 × 0.1 × URL/Span)%
20 to 50%
± 0.25%
± 2.5 × (0.05+0.05 × 0.1 × URL/Span)%
10 to 20%
± 0.5%
± 5 × (0.05+0.05 × 0.1 × URL/Span)%
Temperature effect:
effect per 55°C change between the limits of – 40°C and +85°C
Range code
“1” and “2”
“3” through “8”
Shift at 20% output point
URL
± 0.6+0.5 Span %/55°C
URL
± 0.5+0.125 Span %/55°C
(
(
)
)
Low flow cut-off: Customer configurable for any point between 7 to 20% of output
Physical specifications
Static pressure code
(5th digit in Code symbols)
Zero shift (% of URL)
“1” / 1kPa {10m bar} sensor
“2” / 6kPa {60m bar} sensor
“2”
“3”
“4”
± 0.3% / 1MPa
± 0.3% / 3.2MPa
± 0.3% /10MPa
± 0.3% /16MPa
± 0.5% /42MPa
{10bar }
{32bar }
{100bar }
{160bar }
{420 bar}
Double the effects for material code (7th
digit in Code symbols)“H”, “M”, “T”,
“B”, “L” and “U”.
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5
conduit, as specified.
Process connections:
1/4-18 NPT or Rc1/4 on 54mm centers, as
specified.
Meets DIN 19213.
3
FHC, FKC...2
Process-wetted parts material:
V
H
M
T
316 stainless
steel(*1)
316 stainless
steel(*1)
Diaphragm
316L stainless 316 stainless
steel
steel
Hastelloy-C
Hastelloy-C
lining
316 stainless
steel(*1)
316 stainless
steel(*1)
B
L
U
Hastelloy-C
lining
Monel lining
Tantalum
lining
Wetted
sensor body
Monel
Monel lining
Tantalum
Tantalum
lining
Hastelloy-C
Hastelloy-C
lining
Monel lining
Tantalum
lining
Monel
Tantalum
Vent/drain
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
Hastelloy-C
Monel
Tantalum
Notes: (*1) SCS14 per JIS G 5121
Remark:
Chlorine service: The fill fluid is fluorinated oil.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
ASTM B7M or L7M bolts and 2HM nuts
(Class II) are available.
Static pressure rating for code “3” (16
MPa) is degraded to 10MPa.
Vacuum service: Special silicone oil and filling procedure
are applied.
See figure × 1.
Sensor O-rings: Viton and teflon selectable.
Availability of above material design depends on
ranges and static pressure. Refer to “Code symbols”.
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy (standard), finished
with epoxy/polyurethane double coating, or 316 stainless steel, as specified.
Bolts and nuts: Cr-Mo alloy (standard),
304 stainless steel (for static pressure
code “1”, “2”, and “3” only), or 630
stainless steel (for static pressure code
“3” and “4” only). Static pressure rating for code “3” with 304 stainless
steel bolts is degraded to 10MPa.
Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil)
Mounting bracket: Carbon steel with epoxy coating or 304 stainless steel, as
specified
Environmental protection:
IEC IP67 and NEMA 4X
Mounting:
On 60.5mm(JIS 50A) pipe using mounting
bracket, direct wall mounting, or direct
process mounting.
Mass{weight}:
Transmitter approximately 4.4kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
Silicone oil (Code:Y,G,N)
Silicone oil (Code:R)
[kPa abs]
{mbar abs}
101
{1010}
Operating pressure
Material
code
(7th digit Process cover
in Code
symbols)
Operating
area
20
{200}
4
{40}
2.7
{27}
None-operating
area
–40
A plug-in analog indicator (1.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
1
An optional 4 2 digits LCD meter is also
available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4kV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
4
60 85 120
Fig. 1 Relation between process temperature and
operating pressure
Customer tag:
Coating of cell:
A stainless steel tag with customer tag
data is wired to the transmitter.
Cell's surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive.
ACCESSORIES
Oval flanges:
Optional features
Indicator:
–15
Process temperature[°C ]
(Model FFP, refer to Data Sheet No.
EDS6-10)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Equalizing valves:
(Model FFN, refer to Data Sheet No.
EDS6-10)
Available in CS or in 316 stainless steel
and in pressure rating 16MPa or 42MPa.
Hand-held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
Communication module: (standard for model FKC)
When using this module for model FHC,
remote setting function becomes available.
Remark: When the communication module is connected, the operation mode of external
zero/span adjustable screw is changed to
zero adjustment.
CODE SYMBOLS
1 2 3 4 5 6 7 8
9 10 11 12 13
14 15
Description
2
Type
4 to 20mA, Traditional type
4 to 20mA with digital signal, Smart type
FHC
FKC
Connections
S
T
V
W
X
Process
connection
Oval flange
screw
Conduit
connection
Rc1/4
1/4-18NPT
1/4-18NPT
1/4-18NPT
1/4-18NPT
7/16-20UNF
7/16-20UNF
M10 (or M12)(*1)
M10 (or M12)(*1)
7/16-20UNF
G 1/2
1/2-14NPT
Pg 13.5
M20×1.5
Pg 13.5
Span and materials
11V
11H
22V
Static
pressure
[MPa]
{bar}
–0.1 to
+3.2
{–1 to +32}
[kPa]
(m bar)
0.1/0.1…1/1
{1/1…10/10}
–0.1 to +10
{–1 to 100}
0.6/0.1…6/6
{6/1…60/60}
Span limit (*2) FHC/FKC
22H
33V
–0.1 to +16 3.2/0.32…32/32
{–1 to +160} {32/3.2…320/320}
33H
33M
33T
34V
6.4/0.64…64/64
{64/6.4…640/640}
34H
34M
34T
35V
13/1.3…130/130
{130/13…1300/1300}
35H
35M
35T
36V
50/5…500/500
{500/50…5000/5000}
36H
36M
36T
38V
43V
300/30…3000/3000
{3000/300…30000/30000}
–0.1 to +42 3.2/0.32…32/32
{–1 to +420} {32/3.2…320/320}
43H
43M
44V
6.4/0.64…64/64
{64/6.4…640/640}
44H
44M
45V
13/1.3…130/130
{130/13…1300/1300}
45H
45M
46V
50/5…500/500
{500/50…5000/5000}
46H
46M
47V
23B
23L
23U
24B
24L
24U
25B
25L
25U
26B
26L
26U
200/20…2000/2000
{2000/200…20000/20000}
–0.1 to +10
{–1 to+100}
3.2/0.32…32/32
{32/3.2…320/320}
6.4/0.64…64/64
{64/6.4…640/640}
13/1.3…130/130
{130/13…1300/1300}
50/5…500/500
{500/50…5000/5000}
Process
cover
Diaphragm
Wetted
cell body
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316 stainless
steel
316L stainless
steel
Hast. C
316 stainless
steel
Hast. C lining
316L stainless
steel
Hast. C
316 stainless
steel
Hast. C lining
316L stainless
steel
Hast. C
316 stainless
steel
Hast. C lining
Monel
Monel lining
Tantalum
Tantalum lining
316L stainless
steel
Hast. C
316 stainless
steel
Hast. C lining
Monel
Monel lining
Tantalum
Tantalum lining
316L stainless
steel
Hast. C
316 stainless
steel
Hast. C lining
Monel
Monel lining
Tantalum
Tantalum lining
316 stainless steel
Hast. C
316 stainless
steel
Hast. C lining
Monel
Monel lining
Tantalum
Tantalum lining
316 stainless steel
316L stainless
steel
Hast. C
316 stainless
steel
316 stainless
steel
Hast. C lining
Monel
Monel lining
316L stainless
steel
Hast. C
316 stainless
steel
Hast. C lining
Monel
Monel lining
316L stainless
steel
Hast. C
316 stainless
steel
Hast. C lining
Monel
Monel lining
316 stainless steel
Hast. C
316 stainless
steel
Hast. C lining
Monel
Monel lining
316 stainless steel
316 stainless
steel
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
Hast. C
Monel
Tantalum
Hast. C
Monel
Tantalum
Hast. C
Monel
Tantalum
Hast. C
Monel
Tantalum
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
Hast. C lining
Monel lining
Tantalum lining
Notes: (*1) The thread is M12, if 42MPa {420bar} static pressure is specified.
(*2) 100: 1 turn down is possible for model FKC, but should be used at the span greater than
1/40 of the maximum span for better performance.
5
FHC, FKC...2
1 2 3 4 5 6 7 8
FHC
2
F KC
2
9 10 11 12 13
14 15
Description
Indicator and arrester
Indicator
None
Analog, 0 to 100% linear scale
Analog, 0 to 100% sq. root scale
Analog, custom scale
Analog, double scale
None
Analog, 0 to 100% linear scale
Analog, 0 to 100% sq. root scale
Analog, custom scale
Analog, double scale
Digital, 0 to 100%
Digital, custom scale
Digital 0 to 100% square root
Digital, 0 to 100%
Digital, custom scale
Digital 0 to 100% square root
A
B
C
D
J
E
F
G
H
K
L
P
M
Q
S
N
A
B
C
D
E
M
N
H
J
K
P
R
T
Q
A
B
C
D
E
F
Approvals for hazardous locations
None (for ordinary locations)
JIS, Flameproof (Conduit seal)
JIS, Flameproof (Cable gland seal)
FM, Flameproof (or explosionproof)
CSA, Flameproof (or explosionproof)
BASEEFA, Flameproof (Conduit seal)
BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only)
FM, Intrinsic safety and Nonincendive
CSA, Intrinsic safety and Nonincendive
CENELEC, Intrinsic safety
CENELEC, Intrinsic safety and BASEEFA, Type N
SAA, Flameproof (Conduit seal) (*5)
SAA, Intrinsic safety (*5)
SAA, Type N (Non-sparking) (*5)
Side vent/ drain and mounting bracket
Side vent/drain
Mounting bracket
None
None
Specify "A", "B", or "C" for the
None
Yes, carbon steel
None
Yes, stainless steel 7th digit code "B", "L", or "U"
Yes
None
Yes
Yes, carbon steel
Yes
Yes, stainless steel
Stainless steel parts
Stainless steel tag plate
Stainless steel elec, housing
Coating of cell
None
None
None
Yes
None
None
None
Yes
None
Yes
Yes
None
None
None
Yes
Yes
None
Yes
None
Yes
Yes
Yes
Yes
Yes
Special applications and fill fluid
Treatment
Fill fluid
None (standard)
Silicone oil
None (standard)
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code, "V" only)
Chlorine service
Fluorinated oil (7th digit code "H", "T", "B", "U")
NACE specification
Silicone oil (Not available for 7th digit code "T", "U" and 15th digit code "A", "B")
Vacuum service
Silicone oil for vacuum use
Sensor O-ring
Viton
Teflon
Bolt/nut
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt/nut
NACE bolt/nut (ASTM A193 B7M/A194 2HM)
(*6)
NACE bolt/nut (ASTM A320 L7M/A194 2HM)
304 stainless steel/304 stainless steel
} (*7)
(*9)
630 stainless steel/304 stainless steel
} (*8)
}
Y
B
C
E
M
N
P
Q
Y
W
G
A
D
N
R
A
B
A
B
C
D
E
F
}
}
Notes:
6
Arrester
None
None
None
None
None (*3)
Yes
Yes
Yes
Yes
Yes (*3)
None
None (Model FKC only) (*4)
None
Yes
Yes (Model FKC only) (*4)
Yes
(*3)
The scale is selectable "JIS and SI unit" or "Linear and sq. root" or "Linear and sq. root by 10".
(*4) Incase of FKC, specified the output mode linear or sq. root. Unless specified, the output mode
is linear. In case of 9th digit code "P", "S" with FKC, specified the output indication. Unless
specified, the indication is output mode.
(*5) Available for 4th digit code "S", "T", "W".
(*6) Static pressure should be –0.1 to +10MPa{–1 to +100bar}.
(*7) Available for 5th digit code "1", "2", "3". In case of stainless steel bolt
with 5th digit code "3", static pressure should be –0.1 to +10MPa {–1 to + 100bar}.
(*8) Available for 5th digit code "3", "4".
(*9) In case of tropical use, select a stainless bolts and nuts.
OUTLINE DIAGRAM (Unit:mm)
4th of Code symbols
"S, V, W, X" type is not attached
U-bolt M8
Zero/span adj. screw
(10)
"A" Press conn.
52.5
88
Field ind.
(option)
*Cable gland
(option)
(27)
"B" Conduit conn.
Vent/drain plug
154
With field ind.
Details of "A"
Details of "B"
φ13
φ15
2.5
17
8
E F
φ7
43
59
Earth terminal
(both side)
See table 1
Details of "C"
"C"
Conduit conn.
Oval flange
screw
See table 1
D
Side vent
(option)
See table 1
Conduit conn.
D
E
F
41.3
G1/2
See table 1
Press. conn.
G
Oval flange
screw
Earth
terminal
H.P.
L.P.
S
G1/2
17 8
Rc1/4
7/16-20UNF
screw depth 13
M4
T
1/2-14NPT
16 5
1/4-18NPT
7/16-20UNF
screw depth 13
No. 8-32UNC
V
Pg13.5
1/4-18NPT
M10 or M12
screw depth 13
M4
54
W
M20x1.5
1/4-18NPT
M10 or M12
screw depth 13
M4
70
104
X
Pg13.5
1/4-18NPT
7/16-20UNF
screw depth 13
M4
8
4.5
16 5
8
4.5
Table 1
231
4 holes
9 dia.
4th of Code
symbols
Down
37
210
φ80
105
φ80
Up
70
38
58
G
φ18.5
Fastener
(flameproof model only)
130
120
43.5
Mtg. pipe
JIS 50A (2B)
CONNECTION DIAGRAM
Note *: Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
S
T
H
F K CV
W
X
V
H
M 2
T
+
–
CK+ CK–
+ –
ORDERING INFORMATION
When ordering this instrument, specify:
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality is occurred in the transmitter.
(Unless otherwise specified, output hold function is supplied).
4. Output mode in case of FKC (linear or square root output).
(Unless otherwise specified, output mode is linear).
5. Indication method (indicated value and unit) in case of the digital indicator/actual scale (codes P and S on 9th digit) when
FKC is in the square root output mode.
(Unless otherwise specified, the indication is square root 0 to 100%).
6. TAG No. (up to 26 alphanumerical characters), if required.
7
FHC, FKC...2
4th of Code symbols
"S, V, W, X" type is not attached
"A" or "B"
Press. conn.
U-bolt
M8
Zero/span adj. screw
Oval flange
screw
See table 1
58
Fastener
(flameproof model only)
(10)
Mtg. pipe
JIS 50A (2B)
φ80
120
105
52.5
70
φ80
Up
88
Down
38
58
*Cable gland
40
4 holes
9 dia.
(27)
210
Details of "C"
Earth terminal
(both side)
See table 1
G
φ4
234
F
17
2
1
0
–0.1
+0.2
43
91
φ13
φ15
φ16
186
Details of "D"
4th of code symbols
"S" type
φ12+0.1
"D"
Conduit conn.
"C"
Conduit conn.
With field ind.
Vent/drain plug
Details of "A"
Field ind. (option)
G1/2
E
See table 1
Details of "B"
4th of Code symbols
"T, V, W, X" type
φ16
10
1/4–18NPT
φ4
Conduit conn.
4th of Code
symbols
E
F
S
G1/2
T
1/2-14NPT 16
V
Pg13.5
W
M20x1.5
X
Pg13.5
17
G
Oval flange
screw
8
7/16-20UNF
screw depth 13
Earth
terminal
L.P.
H.P.
M4
7/16-20UNF
screw depth 13
8 4.5 M10
screw depth 13
M10
16 5
screw depth 13
7/16-20UNF
8 4.5
screw depth 13
4–M8x12
No. 8-32UNC
5
M4
54
M4
70
M4
104
Table 1
The applicable standards used to demonstrate compliance are :-
Note *: Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
EMI (Emission) EN 50081-1 :-1992
CONNECTION DIAGRAM
S
H T
F K CV
W
X
+
B
L 2
U
–
Test item
Applicable Electromagnetic
Radiation Disturbance
CK + CK –
+ –
Frequency ranme
30-1000MHz
Basic standard
EN55022
Class B
EMS (Immunity) EN 50082-1 :-1992
The product conforms to the requirements of the Electromagnetic compatibility Directive 89/336/EEC as detailed within the technical construction file number
TN510412.
No.
Test item
1
Electrostatic
discharge
Radio-frequency
electromagnetic
field.
Fast transients
common mode
2
3
Test specification Basic standard Performance
criteria
8kV (Air)
IEC 801-2 : 1984
27-500MHz
3V/m
IEC 801-3 : 1984
(Unmodulated)
0.5kV, 5/50(Tr/Th)ns
IEC 801-4 : 1988
5kHz Rep.
B
A
B
"LVD - The transmitter is not covered by the requirements
of the LVD standard."
Head office
11-2 Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032 Japan
Phone: 81-3-5435-7111
http://www.fujielectric.co.jp/eng/sg/KEISOKU/welcome.htm
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202
Fax: 81-42-585-6187
Information in this catalog is subject to change without notice.
Printed in Japan