BB-BATTERY AA7562

Time control technique
Time relay AA 7562, release delay
minitimer
0232906
•
•
•
•
•
•
Function diagram
According to IEC/EN 60 812-1
Delay up to 180 s
Repeat accuracy < ± 5 %
without auxiliary voltage
1 changeover contact delayed, 1 changeover contact without delay
Width 45 mm
Approvals and marking
Deutschland
Notes
The mounting distance should not be smaller than 8 mm.
Technical data
Time circuit
Time ranges:
Time setting:
Repeat accuracy:
Min. transition time:
Temperature influence:
Circuit diagram
A1 15 21
15
A1
0,2 ... 30 s 0,2 ... 180 s
infinitely
≤ ± 5 % of the final range value
25 ms
0,5 % / K
under certain circumstances, variation
and temperature errors can be added.
21
Input
A2
18
16
24
16 18 22 24 A2
22
M2533_a
Nominal voltage UN:
Voltage range:
AA 7562.32
Nominal consumption:
Nominal frequency:
AC 24, 42, 110, 127, 230, 240 V
50 or 60 Hz
DC 24 ... 220 V
AC 0,85 ... 1,1 U N
DC 0,8 ... 1,1 U N
Initial position
Active position
22 VA
7 VA
5,5 W
5,5 W
50 Hz
Output
Contacts
AA 7562.32:
1 changeover contact, without delay
1 changeover contact, delayed
Operating time of contacts: < 50 ms
Release time of contacts:
< 25 ms
Thermal current I th:
4A
Nominal breaking capacity AC 110 V
AC 230 V
cos ϕ 1 ... 0,7:
2A
2A
cos ϕ 0,4:
1A
1A
DC 110 V
DC 220 V
ohmic:
0,25 A
0,25 A
inductive:
0,03 A
0,02 A
Electrical life:
1,2 x 10 6 switching cycles
1 500 switches/h
at 30 % of the switching capacity
0,8 x 10 6 switching cycles
1 000 switches/h
at 50 % of the switching capacity
0,3 x 10 6 switching cycles
500 switches/h
at 100 % of the switching capacity
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
1
AA 7562 / 19.03.08 e
Technical data
Permissible switching
frequency:
Short circuit strength
max. fuse rating:
Mechanical life:
1 500 switching cycles / h
2 A gL
IEC/EN 60 947-5-1
> 3 x 10 6 switching cycles
General data
Operating mode:
Temperature range:
Clearance and creepage
distances
overvoltage category /
contamination level:
EMC
Electrostatic discharge:
HF-irradiation:
Fast transients:
Surge voltages
between
wires for power supply:
between wire and ground:
HF-wire guided:
Interference suppression:
Degree of protection
Housing:
Terminals:
Housing:
Vibration resistance:
Climate resistance:
Terminal arrangement:
Terminal designation:
Wire connection:
Wire fixing:
Mounting:
Weight:
Continuous operation
- 10 ... + 55 °C
4 kV / 2
8 kV (air)
10 V/m
2 kV
1 kV
2 kV
10 V
Limit value class
IEC 60 664-1
IEC/EN 61 000-4-2
IEC/EN 61 000-4-3
IEC/EN 61 000-4-4
IEC/EN
IEC/EN
IEC/EN
B
61 000-4-5
61 000-4-5
61 000-4-6
EN 55 011
IP 40
IEC/EN 60 529
IP 10
IEC/EN 60 529
Thermoplast with V0-behaviour
according to UL subject 94
Amplitude 0,35 mm
frequency 10...55Hz,IEC/EN 60 068-2-6
The device is only to be used in dry
rooms, in closed switch cabinets or
switch boxes
DIN 46 199-5
EN 50 005
2 x 2,5 mm 2 solid or
2 x 1,5 mm2 stranded wire with sleeve
DIN 46 228-1/-2/-3/-4
Flat terminals with self-lifting
clamping piece
IEC/EN 60 999-1
DIN rail
IEC/EN 60 715
270 g
AC-version
310 g
DC-version
Dimensions
Widht x height x depth:
45 x 77 x 124 mm
Standard type
AA 7562.32 AC 230 V 50 Hz 0,2 ... 30 s
Article number:
0009431
stock item
• Output:
1 changeover contact, instantaneous
1 changeover contact, delayed
• Nominal voltage U N:
AC 230 V
• Time range:
0,2 ... 30 s
• Width:
45 mm
Variant
AA 7562.32/001:
DC-version, as option for:
DC 12, 24, 42, 48, 110, 220 V,
DC 12 ... 220 V
Ordering example for variant
AA 7562 .32 /001
DC 24 V
180 s
Time range
Nominal voltage
Variant, if required
Contacts
Type
E. DOLD & SÖHNE KG • D-78114 Furtwangen •
e-mail: [email protected] • internet: http://www.dold.com
PO Box 1251 • Telephone (+49) 77 23 / 654-0 • Telefax (+49) 77 23 / 654-356
2