ETC 4.85182E+11

48 Series - Relay Interface Modules 8 - 10 - 16 A
48.31
48.52
48.61
- 1 pole, 10 A
- 35 mm rail (EN 50022) mounting
- 2 pole, 8 A
- 35 mm rail (EN 50022) mounting
- 1 pole, 16 A
- 35 mm rail (EN 50022) mounting
- Relay interface modules for use with
PLC systems, 15.5 mm wide
- AC or sensitive DC coil versions available
- Instant removal of relay using plastic
retaining clip
- Supply status indication or coil protection
module provided
- Identification label
- 35 mm rail (EN 50022) mounting
75.3
60.9
17.5
17.5
COM
11
14
NO
12
NC
21
11
COM
21
11
COM
24
14
NO
24
14
NO
22
12
NC
22
12
NC
A2
A1
COIL
A2
A1
COIL
78.6
25.9
15.8
32
A2
A1
* for 400 V applications, requirements for
pollution degree 2 are met.
COIL
Contact specifications
Contact configuration
Rated current/Maximum peak current
A
Rated voltage/Maximum switching voltage V AC
Rated load in AC1
VA
Rated load in AC15 (230 VAC)
VA
Single phase motor rating (230 VAC)
kW/HP
Breaking capacity in DC1: 30/110/220V
Minimum switching load
A
mW (V/mA)
Standard contact material
1 CO (SPDT)
2 CO (DPDT)
1 CO (SPDT)
10/20
8/15
16/30
250/400*
250/250
250/400*
2,500
2,000
4,000
500
400
750
0.37/0.6
0.3/0.4
0.55/0.8
10/0.3/0.12
8/0.3/0.12
16/0.3/0.12
300 (5/5)
300 (5/5)
500 (10/5)
AgNi
AgNi
AgCdO
12 - 24 - 110 - 120 - 230
12 - 24 - 110 - 120 - 230
12 - 24 - 110 - 120 - 230
12 - 24 - 125
12 - 24 - 125
12 - 24 - 125
1.2/0.5
1.2/0.5
1.2/0.5
Coil specifications
Nominal voltage (UN)
V AC (50/60 Hz)
V DC
Rated power AC/sens. DC
VA (50 Hz)/W
Operating range
AC (50 Hz)
(0.8…1.1)UN
(0.8…1.1)UN
(0.8…1.1)UN
DC/sens. DC
(0.73…1.75)UN
(0.73…1.75)UN
(0.8…1.5)UN
Holding voltage
AC/DC
0.8 UN /0.4 UN
0.8 UN /0.4 UN
0.8 UN /0.4 UN
Must drop-out voltage
AC/DC
0.2 UN /0.1 UN
0.2 UN /0.1 UN
0.2 UN /0.1 UN
Technical data
Mechanical life AC/DC
cycles
10 · 106/20 · 106
10 · 106/—
10 · 106/20 · 106
Electrical life at rated load AC1
cycles
200 · 103
150 · 103
100 · 103
10/10 - (15/12 sens.)
10/10 - (15/12 sens.)
10/10 - (15/12 sens.)
Insulation according to EN 61810-5
3.6 kV/3
3.6 kV/3
3.6 kV/3
Insulation between coil and contacts (1.2/50µs) kV
6 (8mm)
6 (8mm)
6 (8mm)
Operate/release time (bounce included)
Dielectric strenght between open contacts
Ambient temperature range
Protection category
Approvals (relay): (according to type)
ms
V AC
°C
1,000
1,000
1,000
–40…+70
–40…+70
–40…+70
IP 20
IP 20
BEAB
GOST
IP 20
RINA
®
C
US
41
48 Series - Relay Interface Modules 8 - 10 - 16 A
48.62
- Relay interface modules for use with
PLC systems, 15.5mm wide
- AC or sensitive DC coil versions available
- Instant removal of relay using plastic
retaining clip
- Supply status indication or coil protection
module provided
- Identification label
- 35 mm rail (EN 50022) mounting
- 2 pole, 10 A
- 35 mm rail (EN 50022) mounting
75.3
60.9
17.5
17.5
21
11
COM
24
14
NO
22
12
NC
A2
A1
COIL
78.6
25.9
15.8
32
* for 400 V applications requirements for
pollution degree 2 are met.
Contact specification
Contact configuration
2 CO (DPDT)
Rated current/Maximum peak current
A
10/20
Rated voltage/Maximum switching voltage V AC
Rated load in AC1
250/400*
VA
Rated load in AC15 (230 VAC)
2,500
VA
Single phase motor rating (230 VAC)
Breaking capacity in DC1: 30/110/220V
Minimum switching load
500
kW/HP
0.37/0.6
A
10/0.3/0.12
mW (V/mA)
300 (5/5)
Standard contact material
AgNi
Coil specifications
Nominal voltage (UN)
V AC (50/60 Hz)
—
V DC
Rated power AC/sens. DC
12 - 24 - 125
VA (50 Hz)/W
Operating range
—/0.5
AC (50 Hz)
—
DC/sens. DC
(0.8…1.7)UN
Holding voltage
AC/DC
0.8 UN /—
Must drop-out voltage
AC/DC
0.2 UN /—
Mechanical life AC/DC
cycles
—/20 · 106
Electrical life at rated load AC1
cycles
100 · 103
Technical data
Operate/release time (bounce included)
ms
10/10
Insulation according to EN 61810-5
3.6 kV/3
Insulation between coil and contacts (1.2/50µs) kV
6 (8mm)
Dielectric strenght between open contacts
Ambient temperature range
V AC
1,000
°C
–40…+70
Protection category
Approvals (relay): (according to type)
42
IP 20
®
C
US
GOST
RINA
48 Series - Relay Interface Modules 8 - 10 - 16 A
ORDERING INFORMATION
Example: a 48 series 35 mm rail (EN 50022) mount relay interface module with 2 CO (DPDT) 6 A, coil rated 24 V sensitive DC, green LED + diode.
A
4 8 . 5
2 . 7 . 0 2 4 . 0
Series
Type
3 = 35 mm rail mount
5 = 35 mm rail mount
6 = 35 mm rail mount
B
C
D
0
5
0
A: Contact material
0 = Standard
D: Special applications
0 = Standard
B: Contact circuit
0 = Standard
C: Options
5 = Standard for DC:
green LED + diode (polarity +A1)
6 = Standard for AC:
green LED + Varistor
No. of poles
1 = 1 CO (SPDT) for 48.31, 10 A
48.61, 16 A
2 = 2 CO (DPDT) for 48.52, 8 A
48.62, 10 A, DC only
Coil version
7 = Sensitive DC
8 = AC (50/60 Hz)
Coil voltage
see coil specifications
TECHNICAL DATA
INSULATION
INSULATION according to EN 61810-5
insulation rated voltage
rated impulse withstand voltage
V
250
kV
3.6
pollution degree
3 (48.31/61/62)
overvoltage category
III
2 (48.52)
IMMUNITY
CONDUCTED DISTURBANCE IMMUNITY
BURST (according to EN 61000-4-4) level 4 (4kV)
SURGE (according to EN 61000-4-5) level 3 (2kV)
OTHER DATA
VIBRATION RESISTANCE (10…55Hz): NO/NC
POWER LOST IN THE ENVIRONMENT
g/g
without contact current W
with rated current W
12 14
11
A1
1.2 (48.31)
1.3 (48.52)
12 14
22 24
12 14
22 24
11
11
21
11
21
+A1
–A2
DC
Type 48.31
3/3 (2 CO)
12 14
A2
AC
10/4 (1 CO)
0.7
A1
A2
1.2 (48.61)
(22) 12 14 (24)
AC
Type 48.52
Type 48.62
11 (21)
A2
+A1
–A2
DC
(22) 12 14 (24)
11 (21)
A1
+A1
1.2 (48.62)
–A2
DC
AC
Type 48.61
43
48 Series - Relay Interface Modules 8 - 10 - 16 A
CONTACT SPECIFICATIONS
10
7
10
6
10
5
F 48/2
CYCLES
CYCLES
F 48/1
1
0
2
8
4
12
10
7
10
6
10
5
16
H 48/2
1
2
3
10
6
4
2
B
A
1
0.2
0.1
60
100
140
180
220
DC VOLTAGE (V)
Breaking capacity for DC1 load.
1 - Type 48.61.
2 - Type 48.31.
3 - Type 48.52.
A - Load applied to 1 contact
B - Load applied to 2 contacts in series
• When switching a resistive load (DC1) having voltage and
current values under the curve the expected electrical life is
≥ 100·103 cycles.
• In case of DC13 loads the connection of a diode in parallel with
the load will permit the same electrical life as for a DC1 load.
Note: the release time of load will be increase.
DC BREAKING CURRENT (A)
H 48/1
DC BREAKING CURRENT (A)
Electrical life vs AC1 load.
Type 48.62 (10 A).
20
12
16
LOAD RATED CURRENT (A)
Electrical life vs AC1 load.
1 - Type 48.52 (8 A).
2 - Type 48.31 (10 A).
Type 48.61 (16 A).
20
44
8
4
0
LOAD RATED CURRENT (A)
20
10
6
4
2
B
A
1
0.2
0.1
20
60
100
140
180
220
DC VOLTAGE (V)
Breaking capacity for DC1 load.
1 - Type 48.62.
A - Load applied to 1 contact
B - Load applied to 2 contacts in series
• When switching a resistive load (DC1) having voltage and
current values under the curve the expected electrical life is
≥ 100·103 cycles.
• In case of DC13 loads the connection of a diode in parallel with
the load will permit the same electrical life as for a DC1 load.
Note: the release time of load will be increase.
48 Series - Relay Interface Modules 8 - 10 - 16 A
COIL SPECIFICATIONS
DC VERSION DATA (0.5 W sensitive)
AC VERSION DATA
Nominal
voltage
UN
V
12
24
110
120
230
Coil
code
Operating range
Umin
V
9.6
19.2
88
96
184
8.012
8.024
8.110
8.120
8.230
Umax
V
13.2
26.4
121
132
253
Rated coil
absorption
I at UN (50Hz)
mA
90.5
46
10.1
11.8
60.2
Nominal
voltage
UN
V
12
24
125
Coil
code
Umin*
V
8.8
17.5
92
7.012
7.024
7.152
Umax
V
21
42
218
Rated coil
absorption
I at UN
mA
41
22.2
4
*Umin = 0.8 UN for 48.61 and 48.62
R 48 sens. DC
R 48 AC
U 2.0
UN
U 2.0
UN
1.5
Operating range
1.5
1
1
1.0
1.0
48.61/62
48.31/52
2
2
0.5
0.5
-20
0
20
40
60
80
-20
0
AMBIENT TEMPERATURE (°C)
Operating range (sensitive DC version) vs ambient temperature.
1 - Max coil voltage permitted
2 - Min pick-up voltage with coil at ambient temperature
20
40
60
80
AMBIENT TEMPERATURE (°C)
Operating range (AC version) vs ambient temperature.
1 - Max coil voltage permitted
2 - Min pick-up voltage with coil at ambient temperature
ACCESSORIES
8-way jumper link for 48 series
095.18
15
15.8
15.8
15.8
15.8
15.8
15
10.3
- RATED VALUES: 10 A - 250 V
5.1
7
095.18
3.3
110.5
45