OMRON E5CS

Temperature Controller
E5CS-X
DIN-sized (48 48 mm) Temperature
Controller Features Automatic P
(proportional action) Tuning Function
Accurate to ±0.5% of full scale.
Multiple temperature ranges allow easy selection
for application.
Field-selectable temperature ranges in °C and °F.
Easy-to-read, 11-mm high LED digital display.
Tamper-proof setting, faulty-sensor detection, and
controller diagnostics.
8-function alarm available.
Nonvolatile memory.
Field-selectable control mode (ON/OFF or PID).
Ordering Information
Thermocouple Type
K (CA) Chromel-alumel
Input
In
ut
Standard temperature ranges
(switch selectable)
…………
…………………………………………
……………………………………………………………………………………………………………………
……………………………………………………………………………………………………………………
……………………………………………………………………………………………………………………
600
………………………………………………………………
……………………………………………………
500
500
…………………………………………………………………………
…………………………………………
400
400
…………………………………………………………………………………………………………
…………
300
300
…………
…………………………………………………………………………
…………
……………………
200
200
……………………………………………………………………………………
………………………………
……………………………………………………………………………………………………………………
……………………………………………………………………………………………………………………
0
0
0
0
0
0
0
0
0
0
0
Set no.
0
1
2
3
4
5
6
6
7
8
9
Temperature unit (selectable)
1,000
900
800
700
600
500
400
300
200
100
0
°C
°C
Measurement unit
With a
alarm
a
°C/°F
°C/°F
°C/°F
°C/°F
°F
°C
°C
°C/°F
°C/°F
1
Control mode
Without
ou a
alarm
a
J (IC) Iron-constantan
999
999
……………………………………………………
…………
ON/OFF or PID
Relay output
E5CS-RKJX
Voltage output
E5CS-QKJX
Relay output
E5CS-R1KJX
Voltage output
E5CS-Q1KJX
1
E5CS-X
E5CS-X
Platinum Resistance Thermometer Type
Input
In
ut
Standard temperature ranges
(switch selectable)
500
400
300
200
100
0
–100
Platinum resistance thermometer (Pt: 100 Ω, JIS and DIN standard types)
800
………… …………………… ………… ………… ………… ………… …………
600 …………
400
………… …………………… ………… ………… ………… …………
………… …………
300
………… ………… …………
………… …………………… ………… ………… …………
200
………… ………… ………… …………
………… …………………… ………… …………
80
99.9
50
50.0
…………
…………
…………
………… ………… ………… ………… …………
…………
………… …………………… ………… ………… ………… ………… ………… …………
0
0.0
0
0
0
0
0.0
…………
………… …………
…………
…………
…………
…………
………… …………
Temperature unit (selectable)
0
1
2
3
4
5
6
7
8
°C
°C
°C/°F
°C/°F
°C/°F
°C
°C
°C/°F
°C/°F
1
0.1
1
0.1
Measurement unit
Control mode
–20
–50
Set no.
1
ON/OFF or PID
Without
ou a
alarm
a
With a
alarm
a
Relay output
E5CS-RPX
Voltage output
E5CS-QPX
Relay output
E5CS-R1PX
Voltage output
E5CS-Q1PX
Thermistor Type
Standard temperature ranges
(switch selectable)
Input
In
ut
THE element interchangeable thermistor
500
400
300
200
100
0
–100
600
………… …………………… ………… ………… ………… ………… ………… ………… …………
400
…………
………… …………………… ………… ………… ………… ………… ………… …………
300
300
………… ………… …………
………… …………
………… …………………… ………… …………
100
150
200
200
300
…………
…………
………… ………… …………
………… ………… …………
………… …………
50
100
200
…………
………… …………………… ………… ………… ………… ………… ………… …………
100
100
150
…………
………… ………… …………
………… …………
………… …………………… …………
50
0
0
…………
………… ………… ………… …………
………… ………… …………
………… …………
Set no.
–50
–50
0
1
2
3
4
°C
Temperature unit (selectable)
7
8
9
1
Control mode
With a
alarm
a
6
°F
Measurement unit
Without
ou a
alarm
a
5
ON/OFF or PID
Relay output
E5CS-RGX
Voltage output
E5CS-QGX
Relay output
E5CS-R1GX
Voltage output
E5CS-Q1GX
The functions can be factory-set for shipment as shown in the table below, depending on the suffix attached to the model number when you
place your order. Two suffixes are selectable: “-DIN” or “-F”.
Example: E5CS-RKJX-DIN
Suffix
Suffix
S a da d temperature
Standard
e pe a u e
range
None
-DIN
-F
K(CA)/J(IC)
2 (0 to 400)
8 (0 to 400)
2 (0 to 400)
PT
3 (0.0 to 99.9)
3 (0.0 to 99.9)
3 (0.0 to 99.9)
THE
1 (–50 to 50)
1 (–50 to 50)
1 (–50 to 50)
Temperature unit (selectable)
°C
°C
°F
Control mode
ON/OFF
ON/OFF
ON/OFF
20
0s
20 s
20
0s
Proportional
opo o a pe
period
od
Relay output
Voltage output
2s
Control output
Reverse operation
Reverse operation
Reverse operation
Input shift
Cannot be set
Cannot be set
Cannot be set
Temperature sensor standard
JIS (ISO)
DIN
JIS (ISO)
Alarm mode
2 (upper-limit)
2 (upper-limit)
2 (upper-limit)
The functions can be factory-set in accordance with your needs. The above settings, however, can be easily changed using the internal DIP
switch. For details on the DIP switch settings, refer to Function Setting.
2
E5CS-X
E5CS-X
Accessories (Order Separately)
Protective Cover Y92A-48
The protective cover protects the front panel, particularly the setting
section, against dust, dirt, and water drip. It also prevents the set
values from being altered due to accidental contact with the setting
keys.
Y92A-48
Protective Cover
3
E5CS-X
E5CS-X
Specifications
Ratings
Supply voltage
100 to 240 VAC 50/60 Hz
Operating voltage range
85 to 110% of rated supply voltage
Power consumption
Control
Co
o ou
output
pu
Approx. 7 VA
Relay
3 A 250 VAC (resistive load), SPDT
Voltage
20 mA 12 VDC, w/short-circuit protection circuit
Alarm output
1 A 250 VAC (resistive load), SPST-NO
Characteristics
Setting accuracy
±0.5% of full scale, ±1 digit max.
Indication accuracy
Set value coincides with indicated value, since no relative error exists between these values.
Hysteresis
0.2% of full scale (during ON/OFF control)
Proportional band
3% to 20% (automatically adjusted according to the rise time of the controlled system)
Reset time
4 minutes (fixed)
Rate time
0.4 minutes (fixed)
Alarm output setting range
0 to full scale for all modes except the absolute-value alarm mode (see note)
Alarm output setting range
(Absolute-value alarm mode)
Same as switch-selectable standard temperature ranges shown at the top of the tables in
Ordering Information
Proportional period
2/20 seconds
Sampling period
500 ms (Output change period: 2 seconds; Indication change period: 2 seconds)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 minute (between current-carrying terminals of different polarity)
Vibration resistance
Malfunction: 2 to 55 Hz, 2 G for 10 minutes each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 0.75 mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance
Malfunction: 100 m/s2, in 6 directions, 3 times each
Destruction: 300 m/s2, in 6 directions, 3 times each
Ambient temperature
Operating: –10 to 55°C
Storage: –25 to 65°C
Humidity
35% to 85% RH
Degree of protection
IEC 144
Front panel: IP50
Rear panel: IP30
Terminals: IP00
Life expectancy
Mechanical: 10,000,000 operations min. (relay output)
Electrical: 100,000 operations min. (relay output)
Weight
Approx. 170 g (main enclosure only)
Note:
Set values must be within the allowable range limits for alarm values, control outputs, etc. If a set value does not satisfy the following
condition, select another range:
Minimum of temperature range x Tset ±X x Maximum of temperature range
where:
Tset=Set temperature, and
X=Alarm value.
4
E5CS-X
E5CS-X
Nomenclature
LED Deviation Indicators
n lights when the present temperature is higher than the set temperature, and o lights when it is lower.
The j indicator lights in green if
the deviation is within ±1% of the
full scale.
Main Display
Sequentially displays the present temperature, set
temperature, and an alarm value (in that order)
each time the temperature indication switching
(
) key is pressed.
Alarm Output Operation Indicator
Lights when the alarm output relay
is energized.
Mode Indicator
SP lights while the set temperature
is displayed on the main display,
and AL lights while an alarm value
is being displayed.
Protection Key
When program protection is selected
using the internal DIP switch, the
upward and downward setting keys
are locked.
However, authorized personnel may
change values using the upward and
downward setting keys by holding
down hidden protection key.
Control Output Indicator
Lights while the control output is being produced.
Upward Setting Key
When pressed, increases the set
temperature/alarm value.
Successively increases the
value when held down.
Temperature Indication Switching Key
Each time pressed, changes the value displayed on the main display in the following
sequence.
Downward Setting Key
When pressed, decreases the
set temperature/alarm value.
Successively decreases the
value when held down.
5
E5CS-X
E5CS-X
Operation
Temperature Setting
Press the temperature indication switching key until the SP indicator
lights. Then set the desired temperature value using the upward and
downward setting keys.
Alarm Setting
Press the temperature indication switching key until the AL indicator
lights. Then set the desired alarm value in units of °C or °F. If the
present temperature reaches the set alarm value, alarm output will
be enabled.
Sensor Failure
The error message “FFF” or “– – –” will appear on the main display if
the temperature sensor, such as the thermocouple or platinum resistance thermometer, short-circuits or breaks. (Refer to Error Messages for details of the messages displayed.)
Note: Neither the set alarm value is displayed nor the AL indicator
lights with the internal alarm mode selector switch set to 0
or 9. The alarm mode selector switch is provided inside the
housing, and is positioned differently on each model.
Function Setting
The various functions of the Temperature Controller are set using
the switches on the internal mechanism. To gain access to these
switches, the internal mechanism must be first drawn out from the
housing. Push the tab on the underside of the housing, and pull out
the mechanism.
The procedures for making actual settings are given below.
Setting the Temperature Range
Set the desired temperature range by using the temperature range
selector switch (“Set no.” setting in the tables below). Eight or nine
temperature ranges can be selected depending on the model.
Thermocouple Type
The display can indicate temperatures 10% beyond each of the set
ranges.
Platinum Resistance Thermometer Type
Select the desired temperature range using the temperature range
selector switch (rotary DIP type). Eight or nine temperature ranges
can be selected depending on the model.
The set temperature is automatically changed when the temperature range is changed. Be sure to confirm the set temperature.
Temperature range selector switch
Alarm mode selector switch
Right side view
Do not set the selector switch to “9.” Doing so will result in the error
message “FFF” or “– – –” being displayed.
Note: 1. The unit in which the temperature can be set is multiplied
by 10 when the temperature range is changed from 0.0
to 50.0 or 0.0 to 99.9 to a range in which the temperature
can be set in 1° units. Conversely, if the temperature
range is changed from one in which the temperature can
be set in 1° units to a range of 0.0 to 50.0 or 0.0 to 99.9,
the unit is decreased to 1/10 of the original unit.
2. The display can indicate temperatures 10% beyond
each of the set ranges.
Thermistor Type
Temperature unit (C° or F°), where a choice is available, is selected
using pin 6 of the internal DIP switch which is also used for other settings, such as the control mode and sensor compensation.
Note:
Internal DIP switch
Left side view
6
1. The temperature range selector switch is factory-set to
“0.” With a temperature range, such as 50° to 150°C,
that exceeds the setting range, the indication unit is automatically adjusted to the minimum value. The set temperature is displayed when power is turned ON.
2. The temperature range that can actually be indicated for
a set temperature range of –50° to 50°C is –50° to 60°C.
For other temperature range settings it is the full scale
±10%.
E5CS-X
E5CS-X
Temperature Indication Switching Key
Setting the Alarm Mode
If the set temperature is shifted outside the temperature range as a result of changing the range, the set
temperature is displayed. It is then
automatically changed to the maximum or minimum vale of the newly
set range.
If the alarm value is shifted outside
the temperature range as a result of
changing the range, it is automatically changed to the maximum value
of the newly set range.
If the alarm mode selector switch is set to “0” or “9”, no alarm value is
displayed.
On models without alarms, no alarm value is displayed.
The desired alarm mode can be chosen from one of the eight alarm
modes using the alarm mode selector switch as shown below.
Switch
setting
0, 9
No alarm function
1
Upper- and
lower-limit alarms
2
Upper-limit alarm
3
Lower-limit alarm
4
Upper- and
lower-limit range
alarm
5
Upper- and
lower-limit alarms
with standby
sequence (see note)
6
Upper-limit alarm
with standby
sequence (see note)
7
Lower-limit alarm
with standby
sequence (see note)
8
Absolute-value alarm
DIP Switch Settings
The control mode and other settings are selected using the internal
DIP switch as shown below.
ON
ON
P
Function
Protect
X
P
1
2
3
4
5
6
X
1
2
3
4
5
6
Mode
Alarm output
OFF
ON
OFF
---
Not
used
Note:
Control
mode
PID
ON
ON/OFF
OFF
Proportional
period
2s
ON
20 s
OFF
Control
output
Normal
ON
Reverse
OFF
Input shift
Setting
enabled
ON
Setting
disabled
OFF
The selector switch is factory-set to “2.”
The triangular mark Y indicates the set temperature.
X denotes alarm values.
Y denotes the set value value within the temperature range.
Operation of Standby Sequence
Alarm output set with standby sequence will operate in the way
shown below when the temperature rises above the upper-limit.
Temperature
sensor
standard
DIN
ON
JIS
OFF
Scale
indicator
(selectable)
°F
ON
°C
OFF
Alarm output set with standby sequence will operate in the way
shown below when the temperature drops below the upper-limit.
7
E5CS-X
E5CS-X
Control Mode Selection
ON/OFF Control
Pin 1 of the internal DIP switch is factory-set to OFF, so the Temperature Controller performs ON/OFF control.
ON
ON
Set pin 3 to ON when the Temperature Controller is used to control a
cooling device, such as a freezer.
ON
P
1
X
2
3
4
5
ON
P
6
X
1
2
3
4
5
6
Pin 1 OFF: Temperature Controller performs ON/OFF.
ON
Control output
Control output
ON
OFF
OFF
Set temperature
Set temperature
PID Control
Set pin 1 of the internal DIP switch to ON to make the Temperature
Controller perform PID control. Follow the steps described below.
ON
ON
Determining Control Output Operation
If the Temperature Controller is used to control a heater, the control
output can be set to perform reverse (inverted) operation. Set pin 3
of the control output mode selector switch to OFF.
ON
P
1
X
2
3
4
5
ON
6
Pin 1 ON: Temperature Controller performs PID control.
P
Determining Proportional Period
Set pin 2 of the DIP switch to OFF to select a proportional period of
20 seconds. This is used when PID control is performed with the
relay output of the Temperature Controller, or when using an external relay or contactor.
ON
1
X
2
3
4
5
6
ON
Reverse output
OFF
Set temperature
Conversely, if the Temperature Controller is used to control a cooling device such as a freezer, set pin 3 to ON.
ON
ON
P
1
X
2
3
4
5
ON
6
ON
P
Control output
X
1
2
3
4
5
6
OFF
20 seconds
ON
Normal output
When a quick response is required, set pin 2 to ON to select a proportional period of 2 seconds. Even when a solid-state relay (SSR)
is used, only set the 2-second proportional period where quick response is essential. With a relay control output, a proportional period of 2 seconds will greatly reduce the service life of the relay.
ON
ON
P
Control output
X
1
ON
OFF
2 seconds
8
2
3
4
5
6
OFF
Set temperature
When power is first turned ON, the proportional band is set to 3%.
The optimum proportional band, however, is automatically calculated and set within the range 3% to 20%, according to the changes
in the temperature of the controlled system. This automatic adjustment of the proportional band is possible regardless of whether the
controlled system is a heating or cooling system.
When the power is turned OFF once, and then ON again, the control
starts with the previous proportional band. A new proportional band,
however, is automatically calculated and set.
The calculation of the proportional band is not carried out, however,
if the temperature of the controlled system changes at a rate faster
than 7.5% of the full scale per 2 seconds (e.g., faster than 3.75°C
per second with a full scale of 100°C). In this case, the previously
calculated and set proportional band is used.
The Temperature Controller is provided with an overshoot prevention function that suppresses the second overshoot and those that
follow to a level less than the initial overshoot.
E5CS-X
E5CS-X
Input Shift Function
This function is used to shift the value displayed in the main display
from the value actual measured by a desired amount. This powerful
feature can be used for “fine tuning” compensation, while leaving
the set temperature unaffected.
The input shift function is activated by setting pin 4 of the internal
DIP switch to ON.
ON
Example
Main display
(without shift)
ON
(offset by +9°C)
(offset by –16°C)
P
X
1
2
3
4
5
6
This allows the setting of the temperature shift value. Press the tem) key repeatedly until “H 0” (in this
perature indication switching (
case, indicating a zero input shift) is displayed on the main display.
Then set the input shift value by using the upward and downward
setting keys.
Temperature
measured by
sensor
Temperature
displayed
100°C
100°C
100°C
109°C
100°C
84°C
The input shift value can be set within a range of –99 to 99, except
with a 0.0 to 99.9 platinum resistance thermometer, where the input
shift narrows to a range of –9.9 to 9.9.
When the desired shift has been entered, set pin 4 to OFF. The input
shift value remains in memory. Consequently, if the input shift function is not needed, with pin 4 activated set the input shift value to 0.
Sensor Failure Operation
Thermocouple Type
Condition
Display
Break in sensor
Control output
OFF
blinks
Note:
When the input is short-circuited, the room temperature is displayed.
Platinum Resistance Thermometer Type
Condition
Display
Break in sensor
Control output
OFF
blinks
OFF
blinks
Disconnection of two or three
wires
blinks
Short-circuit
OFF
OFF
blinks
Note:
The resistance of the platinum resistance thermometer is 100 Ω at 0°C. It increases to about 140 Ω at 100°C.
Thermistor Type
Condition
Display
Control output
Break in sensor
ON during heating (reverse)
OFF during cooling (normal)
Short-circuit
ON during heating (reverse)
OFF during cooling (normal)
9
E5CS-X
E5CS-X
Error Messages
The Temperature Controller is provided with self-diagnostic functions, and will display the following error messages if an error occurs.
Message
FFF
–––
FFF (blinks) (see note 1)
Cause
Control output
(1) Temperature has risen above set temperature range.
OFF during heating (reverse)
(2) Thermistor has been short-circuited.
ON during cooling (normal)
(1) Temperature has fallen below set temperature range.
ON during heating (reverse)
(2) Thermistor has broken.
OFF during cooling (normal)
(1) Failure has occurred in thermocouple or platinum
resistance thermometer.
OFF
(2) Temperature has risen to a value much greater than
the set temperature range.
– – – (blinks) (see note 1)
(1) Failure has occurred in platinum resistance
thermometer.
OFF
(2) Polarities (positive and negative) of thermocouple have
been reversed.
(3) Temperature has fallen to a value much smaller than
the set temperature range.
E11 or E33 (see note 1)
Note:
Memory failure (E11) or A/D converter failure (E33) has
occurred. Temperature Controller must be repaired if
normal operation is not restored by turning power OFF
once and ON again.
Both control output and alarm output
are OFF.
1. The key operations are disabled.
2. The models with alarm output produce alarm output according to the alarm output setting when the message “FFF” is displayed (or
blinks), indicating that the temperature has risen above the set temperature range. Similarly, the alarm output is produced when the
message ”–” is displayed (or blinks), indicating that the temperature has fallen below the set temperature range.
Connections
Voltage output type
20 mA 12 VDC
Relay output type
Thermocouple type
Platinum resistance
thermometer type
Thermistor type
10
100 to 240 VAC
Alarm output
E5CS-X
E5CS-X
Dimensions
Note:
All units are in millimeters unless otherwise indicated.
Panel cutout
Note:
1. The recommended panel thickness is 1 to 4 mm.
2. The Temperature Controller is contained in a mounting bracket, so close side-by-side Temperature
Controller mounting is possible. Provide a center-tocenter distance of at least 60 mm between two adjacent Temperature Controllers.
11
E5CS-X
E5CS-X
Precautions
Mounting
All Temperature Controllers in the E5CS-X Series conform to
DIN43700 standard.
The recommended panel thickness is 1 to 4 mm.
Flush Mounting
Insert the Temperature Controller, back end first, into the hole of the
mounting panel. Mount the adapter by pushing it forward from the
back of the Temperature Controller. Push the adapter as close as
possible to the front panel of the Temperature Controller to eliminate
the gap between them. Then, secure the adapter with screws as
shown in the figure below.
or high temperatures.
Separate the Temperature Controller from equipment that generates strong, high-frequency noise such as high-frequency welders.
Connection Examples
Solderless Terminal
Use M3.5 solderless terminals with the Temperature Controller’s
M3.5 self-rising pressure plate screws.
Solder-dipped Lead Wires
Strip the lead wire 6 to 12 mm and carefully arrange the wire tip.
Removal
Loosen the screws on the adapter and push the hook open to remove the adapter.
Do not tighten the terminal screw with excessive force.
Input Sensor Connection
Hook
Screw
The lead wires connecting the sensor to the Temperature Controller
must be separated from power lines and load lines wherever possible, to prevent them from being induced by noise.
Use the specified compensating conductors for the thermocouple
type Temperature Controllers.
Use lead wires with a small resistance for the Platinum resistance
thermometer type Temperature Controllers.
Sequence Circuit
Environment
Do not install the Temperature Controller in locations subject to dust
or corrosive gases. Do not install the Temperature Controller in locations subject to heavy vibrations or shocks, splashes of water or oil,
Several seconds are required until the relay is turned ON after power is supplied to the Temperature Controller. Therefore, take this
time lag into consideration when designing a sequence circuit which
incorporates the Temperature Controller.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H032-E1-2A In the interest of product improvement, specifications are subject to change without notice.