FC SERIES MANUAL LOADER (CONTINUOUS OUTPUT TYPE) DATA SHEET PNB1 The FC series manual loader is available in two types, a manual control type and a remote control type used in combination with a compact controller. This instrument is equipped with a solid state indicator and pushbutton operation circuit to provide easy readouts and handling for process operation by man-machine communication. It can be directly connected to a thermocouple, resistance bulb or 4 to 20mA input optionally. FEATURES 1. High reliability The manual loader is a solid state instrument having few mechanical parts. The indicator and other units which formerly consisted of mechanical parts are also designed with solid state circuits to provide high reliability. 2. Application of international standards The instrument is compact, and the external dimensions comply with international IEC. The power supply and signal also comply with IEC standards (24V, 1 to 5V DC). Operation on 100V or 200V AC power supply is possible. 3. Front panel operation Process values, valve position input, etc. can be read accurately from the digital display on the panel front. Parameter setting and manual operation are also possible from the front of the panel. FUNCTIONAL DIAGRAM PV Linearize Square-root extraction MV Manual mode output (M) Filter Compensated process value signal (KPV) Process value input (PV) Control output (voltage) (MV) Limiter External MV input (Al1) H L M Prearranged valve position Valve position command (EXS) Manual mode command (SMV) MV Control output (current) (MI) HM Manual back up HMV FAULT FLT output High alarm output (H) KPV ALM Low alarm output (L) EDS11-103e Date Jul. 1, 1994 PNB1 SPECIFICATIONS 1. Input signal (1) Process value input signal: One input selctable from the following Voltage input signal Current input signal Thermocouple input Resistance bulb input 1 to 5V DC 4 to 20mA DC I+ I0 Type I– J: 0 to 600°C K: 0 to 1200°C E: 0 to 800°C R: 0 to 1600°C JPt100/Pt100 –50 to 500°C Input resistance, 1MΩ or more 24V ± 2V DC can be supplied to transmitter in case of AC power supply (approx. 3.5mA max) 10mV DC span or more cold junction compensation comprised Allow. error ± 0.2%/FS* Allow. error ± 0.2%/FS* 50°C span or more Allow. error ± 0.5%/FS* Allow. error ± 0.5%/FS* Note *: FS: Full scale (2) Analog input signal: 1 point External MV input signal AI 1 1 to 5V DC Input resistance, 1MΩ or more Allow. error ± 0.2%/FS (3) Digital input signal: 2 point Manual mode command SMV Valve position commend EXS Contact input (photo-coupler insulation) ON 0V, OFF 24V ( input current, approx. 11mA/24V DC) 2. Output signal (1) Control output signal: 1 point Current output Ml+ Ml– 4 to 20mA DC Allow. Ioad resistance, 600Ω or less Allow. error ± 0 2%/FS (2) Analog output signal: 2 points Compensated process value signal KPV Control output MV 1 to 5V DC Output resistance, 1Ω or less Allow error ± 0 2%/FS (3) Digital output signal: 4 points Fault output Manual mode output FLT Open-collector output (photocoupler insulation) M High alarm output H Low alarm output L Output rating, 30V x 0.1A DC, max. 3. Indication, setting, operating functions (1) Bargraph indication PV indicator MV indicator Indication method LED (red) LED (red) No of segments 101 + 2 51 + 2 Range 0 to 100%, linear 0 to 100%, linear Resolution 1 %/FS 2 %/FS Scale length 100mm 50mm 0 to 100% bargraph indication, 0 to 100% reverse bargraph indication, dot indication, –50 to +50% deviation indication Indication mode (2) Operation mode indication Indicating method: LED (red and green) Red: M, HM Green: A (3) Numerical indication, setting Indication method: LED (red), name in 3 digits + number in 5 digits (negative sign included) 2 Indication contents: Process value (industrial value), high/low alarm, limiter value, etc. Indication contents are selected with , keys on front panel. F/S , Setting method: By using F/S , , , , ST keys on front panel (4) Operating functions Manual operating method: By using of , , pushbuttons on front of the panel Setting speed, approx. 40 sec/FS Simultaneous press of button, approx. 8 sec/FS Auto operating method: By using external control input signal Output limiter: High limit setting range, –25 to 125% Low limit setting range, –25 to 125% Tracking speed setting range; 0 to 900 sec/FS Hard manual operating method: By using control knob on front panel of HMV unit (5) Operation mode selection By using A/M pushbutton and HM switch on front of the panel M M A A A HM selection HM selection M selection* HM selection HM selection* Balance bumpless Balanceless bumpless A M selection Note: * Balanceless bumpless by setting tracking speed (6) Alarm function High/low alarm can be set in industrial values for process value input signal. 4. Power failure processing functions Power failure detection: Control output holds at power failure detection. During power failure: Operating parameters backed up by capacitor when power failure occurs within 5 minutes. Initial value of control output is stored in non-volatile memory (lasts for 10 years expected at ambient temperature of 50 °C or less). Power failure recovery time: Initial or continuous start mode can be set for power failure within 5 minutes. Recovery from power failure lasting longer than 5 minutes is done by initial. Note: Control mode at initialization can be registered M: Manual mode or A: Auto mode 5. Self-diagnosis functions Process value input signal abnormality: FLT indicator lights and FLT contact output turns "ON" . Control output abnormality: FLT lamp lights and FLT contact output goes "ON". Other function is processed at all times. Fault contents indication: Cause of fault is indicated numerically on numerical indicator on the front panel. 6. Transmission functions (1) Transmission items Supervisory items: PNB host Process value, control output, operation mode, alarm information, fault information, various limiter values, constants, etc. Setting operation items: Host PNB Control output, operation mode, various limiter values, constants, etc. (2) Transmission setting inhibit: Parameter setting enable/inhibit can be designated by transmission from the host. Designation is done by keys on the front panel. (3) Communication interface (a) T-link: Private interface Transmission speed: 500Kbps No. of units connectable: 32 max. Transmission distance: 1km max. Transmission form: Multi-drop Control method: I/O transmission and message (b) RS-422A/485: Universal interface Transmission speed: 2400, 4800, 9600 or 19200bps configurable No. of units connectable: 31 max. Transmission distance: 1km max. Transmission form: Multi-drop Control method: Polling/selecting (c) CC data line: Private interface Transmission speed: 19.2Kbps No. of units connectable: 15 max. Transmission distance: 500m max. Transmission form: Multi-drop Control method: Polling/selecting 7. Other functions Data protective function by use of pass code 8. Additional functions (options) (1) Hard manual unit (HMV) Control output: 4 to 20mA DC Allowable load resistance: 600Ω or less (24V DC power only) 9. Operating conditions Power supply: Selected from the following 3 types 24V DC (20 to 30V DC) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) Power consumption: Approx. 11W (DC) Approx. 20VA (AC) Dielectric strength: 1500V AC, 1 min. Insulation resistance: 100MΩ or more at 500V DC Ambient temperature: 0 to 50°C Ambient humidity: 90% RH or less Enclosure: Steel case Rating plate (Name plate): 100 (H) x 72 (W) mm, white acryl Dimensions: 144 (H) x 72 (W) x 391 (D) mm, IEC (DIN) standards Mass {weight}: Approx. 2.9kg Mounting method: Flush with indoor panel; vertical mounting is standard. Mounting on tilted surface possible (angle "α") α=0° to 90° Finish color: Munsell N 1.5 for front panel and case Scope of delivery: Manual loader and mounting bracket Item to be ordered separately: Communication cable (type PNZ) CODE SYMBOLS 1 2 3 4 5 6 7 8 9 10 5 - PNB 1 Description Process value input signal 1 to 5V DC 4 to 20mA DC J thermocouple 10mV DC span or K thermocouple more, cold junction E thermocouple compensation R thermocouple comprised Resistance bulb, JPt 100, 3-wire, 50 °C span or more Resitance bulb, Pt100, 3-wire, 50 °C span or more A B C D E F G W Operating method M type A-M type A B Power supply 24V DC (20 to 30V DC) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) 1 2 3 Hard manual back-up unit (24V DC power only) None With 1 2 Y T R S C Transmission function None T-link RS-422A RS-485 CC data line Notes: Symbols of resistance bulbs are as follows. JPt100.....JIS C 1604-1981 Pt100.....IEC Pub 751-1983 (Selection of JPt100/Pt100 is possible by using front panel key.) 3 PNB1 OUTLINE DIAGRAM (Unit:mm) Terminal Terminal cover 16 144 Panel thickness 8mm or less 140 36 Support bracket Mounting bracket 200min. 72 355 Panel cutout 68 4 +0.7 0 138 +1 0 250min. +1 0 When mounting "n" units 138 200min. When mounting one unit (72.2n – 4) +1 0 No. of units n 2 CONNECTION DIAGRAM Block terminals (M4 screws) AO (Compensated PV signal) Process value input I+ (PV) I– (SC) DO (Manual mode) 11 32 13 33 14 SMV 15 AC 16 Io 31 12 M DI (Manual mode command) KPV 34 FLT 35 AC DO (FLT output) 71 52 72 53 73 AO (Control output) MV 54 74 AI, AO Common bus AO (Control output) Current output SC 55 75 MI+ 56 76 MI– 57 77 H 58 78 L 59 79 PC* 60 80 PCD 61 81 DO (High alarm) DO (Low alarm) Instrument power (24V DC, AC power) 24V power for DI, DO Instrument power (AC) 51 Earth – – G 62 AI1 AI (External MV point) SC AI, AO Common bus DI (Valve position command) EXS VP* 82 VPD + + Instrument power (24V DC, AC power) 24V power for DI, DO Note: * Symbols for AC instrument power are VPO, PCO. Output: Approx. 24V DC (0.1A max.) Process value input terminal connections 1 to 5V DC + The 5th digit of code symbols: B 4 to 20mA DC with inner DC power supply of CC-S The 5th digit of code symbols: B The 5th digit of code symbols: C,D,E,F 31 The 5th digit of code symbols: A 4 to 20mA DC Thermocouple 11 – 12 + + 11 – – 12 + 11 – 12 + + 11 – – 12 + 11 – 12 31 Resistance bulb The 5th digit of code symbols: G,W 31 31 + – 31 PC 60 5 PNB1 COMMUNICATION CONNECTOR 1 SIG GND 6 2 SHLD(SD) 7 8 RXD + 9 RXD – 3 INH 4 TXD+(T1) 1 SIG GND 6 2 SHLD(SD) Black 7 White 8 RXD + 9 RXD – 5 TXD–(T2) Green 3 INH 4 TXD+(T1) 5 TXD–(T2) Yellow Note:Symbol in ( ): T-link terminal symbol Brown Red 6 7 8 RXD + 9 RXD – 1 SIG GND 1 SIG GND 6 2 SHLD(SD) 7 3 INH 8 RXD + 4 TXD+(T1) 9 RXD – 5 TXD–(T2) LINE TERMINATION RESISTOR 2 SHLD(SD) Black 3 INH White 4 TXD+(T1) 5 TXD–(T2) Green Yellow Red Brown End station HOST MASTER CONTROLLER First station Host Termination Resistor Communication cable PNB1 PNB1 PNB1 PNB1 Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan