ABSOLUTE PRESSURE TRANSMITTER FKA...5 DATA SHEET The FCX -AIII absolute pressure transmitter accurately measures absolute pressure and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. FEATURES 1. High accuracy 0.2% accuracy for all calibrated spans is a standard feature for all AP models covering 1.6kPa {0.016bar} range to 3000kPa {30bar} high pressure range. 0.1% accuracy is available as option. Fuji’s micro-capacitance silicon sensor assures this accuracy for all suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The “Advanced Floating Cell” design which protects the pressure sensor against changes in tempera ture, and overpressure substantially reduces total measurement error in actual field applications. 3. Fuji/HART® bilingual communications protocol FCX -AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART® compatible devices can communicate with FCX -AIII. 4. Application flexibility Various options that render the FCX -AIII suitable for almost any process applications include: – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit – Stainless steel electronics housing – Wide selection of materials 5. Burnout current flexibility (Under Scale: 3.2 to 4.0mA, Over Scale: 20.0 to 22.5mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 6. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. [ L-Type ] [ T-Type ] SPECIFICATIONS Functional specifications Service: Liquid, gas, or vapour Span, range, and overrange limit: Span limit [kPa abs] {bar abs} Type Min. FKA 01 FKA 02 FKA 03 FKA 04 1.6 {0.016} 1.6 {0.016} 5 {0.05} 30 {0.3} Overrange limit [MPa] {bar} Range limit [kPa abs] {bar abs} Max. 16 {0.16} 130 {1.3} 500 {5} 3000 {30} 0 to +16 {0 to +0.16} 0 to +130 {0 to +1.3} 0 to +500 {0 to +5} 0 to +3000 {0 to +30} 0.5 {5} 0.5 {5} 1.5 {15} 9 {90} Remark: To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications. – The maximum span of each sensor can be converted to different units using factors as below. 1MPa abs=103kPa abs=10bar abs=10.19716kgf/cm2 abs =145.0377psi abs 1kPa abs =10mbar abs=101.9716mmH2O abs =4.01463inH2O abs=7.50062mmHg abs Output signal: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal. Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. EDSX5-91h Date Aug. 10, 2011 FKA...5 Load limitations: see figure below [Ω] Load resistance 2000 1474Ω 1500 R= E-10.5 (Imax+0.9)x10-3 1000 577Ω Operating area 500 24V 250 0 10 45V 16.35 10.5V Power voltage (DC) 50 E[ V ] Note: For communication with HHC(1) (Model: FXW), min. of 250 is required. Hazardous locations: SEE TABLE2 Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw. Damping: Adjustable from HHC or local configurator unit with LCD display. The time constant is adjustable between 0.06 to 32 seconds. Zero elevation/suppression: Zero can be elevated within the specified range limit of each sensor model. Normal/reverse action: Selectable from HHC(1). Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction:Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.0mA to 22.5mA from HHC(1) “Output Underscale”: Adjustable within the range 3.2mA to 4.0mA from HHC(1) 3.2 4 20 22.5 [mA] Over scale Burnout Normal operating range Under scale Probable under range Burnout Probable over range Temperature limit: Ambient: −40 to +85°C (−20 to +80°C for LCD indicator) (−40 to +60°C for arrester option) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified by each standard. Process: −40 to +85°C for silicone fill sensor Storage: −40 to +90°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following items can be remotely displayed or configured. Note: HHC’s version must be higher than 7.0 (or FXW 1– 4), for FCX AIII. Local configurator with LCD display (option): Local confi gurator with 3 push button and LCD display can support following items. Items By communication By local configurator with FXW (with 3 push button) Display Set Display Set Tag No. v v v v Model No. v v v v Serial No. & Software Version v — v — Engineering unit v v v v Range limit v — v — Measuring range v v v v Damping v v v v Output mode v — v — Burnout direction v v v v Calibration v v v v Output adjust — v — v Data v — v — Self diagnoses v — v — Printer (In case of FXW with printer option) v — — — External switch lock v v v v Transmitter display v v v v Linearize v v — — Rerange v v v v Saturate current v v v v Write protect v v v v History – Calibration history – Ambient temperature history v v v — v v v — EMC Conformity: EN61326-1: 2006 Output Limits comforming the NAMUR NE43 by order. Loop-check output: Transmitter can be configured to provide constant signal 3.2mA through 22.5mA by HHC(1). (Note) 2 (1) HHC: Hand Held Communicator Process-wetted parts material: Performance specifications Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4 to 20mA analog output in linear mode. Accuracy rating: (including linearity, hysteresis, and repeatability). (Standard) For spans greater than 1/10 of URL: ±0.2% of span For spans below 1/10 of URL: ± 0.1 + 0.1 0.1 x URL % of span Span ( ) (Option) (code: 21th digit H) (Not available for Max span 16kPa abs, 130kPa abs) For spans greater than 1/10 of URL: ±0.1% of span For spans below 1/10 of URL: ± 0.05 + 0.05 0.1 x URL % of span Span ( ) Stability: ±0.2% of upper range limit (URL) for 10 years. Temperature effect: Effect per 28°C change between the limits of - 40°C and +85°C URL Zero shift: ± 0.125+0.1 % Span Total effect: ± 0.15+0.1 URL % Span ( ( ) ) Overrange effect: Zero shift; ±0.2% of URL for any overrange to maximum limit Supply voltage effect: Less than 0.005% of calibrated span per 1V Update rate: 60 msec Step response: Time constant: 0.08 s (at 23°C) Dead time: 0.12 s (without electrical damping) Mounting position effect: Zero shift, less than 0.1kPa{1mbar} for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting zero. Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100M at 500V DC. Internal resistance for external field indicator: 12 or less Physical specifications Electrical connections: G 1/2, 1/2-14NPT, Pg13.5, or M20 x 1.5 conduit, as specified. Process connections: 1/4-18 NPT or Rc1/4 on 54mm centers, as specified. l a i r e t aM e d o c t Process i g i d h tcover 7( e d oC “ n i symbols”) V H Diaphragm Wetted sensor body Vent/drain 316 316 stainless 316/316L 316L steel (*1) stainless steel stainless steel stainless steel Hastelloy-C 316 stainless 316/316L Hastelloy-C lining steel (*1) stainless steel Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM A351/A351M) Remarks: Availability of above material design depends on ranges. Refer to “Code symbols”. Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with polyester coating (standard), or 316 stainless steel (ASTM CF8M), as specified. Bolts and nut: Cr-Mo alloy (standard), 304 or 316 stainless steel Fill fluid: Silicone oil Mounting bracket: 304 or 316 stainless steel. Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting, or direct process mounting. Mass{weight}: Transmitter approximately 2.9 to 3.4kg without options. Add; 0.5kg for mounting bracket 4.5kg for stainless steel housing option Optional features Indicator: A plug-in analog indicator (2.5% accuracy) An optional 5-digit LCD meter with engineering unit is also available. Local configurator with LCD display: An optional 5 digits LCD meter with 3 push buttons can support items as using communication with FXW. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 50µs) Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. NACE specification: Metallic materials for all pressure boundary parts comply with NACE MR-01-75. 304 stainless steel bolts and nuts, ASTM B7M or L7M bolts and 2HM nuts (Class II) are available. Optional tagplate: An extra stainless steel tag for customer tag data is wired to the transmitter. Coating of cell: Cell’s surface is finished with epoxy/ polyurethane double coating. Specify if environment is extremely corrosive. 3 FKA...5 CODE SYMBOLS Digit 4 6, 7 9 10 11 1 2 3 4 5 6 7 8 Description <Connections> Process connection Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT <Span limit> Span limit [kPa abs]{bar abs}(*1) 1.6…16 {0.016…0.16} 1.6…130 {0.016…1.3} 5…500 {0.05…5} 30…3000 {0.3…30} Oval flange screw 7/16-20UNF 7/16-20UNF M10 M10 7/16-20UNF 7/16-20UNF 7/16-20UNF M10 M10 7/16-20UNF Conduit connection G1/2 1/2-14NPT Pg13.5 M20×1.5 Pg13.5 G1/2 1/2-14NPT Pg13.5 M20×1.5 Pg13.5 Note 0 9 10 11 12 13 5 Case type T type T type T type T type T type L type L type L type L type L type Process cover Diaphragm Wetted cell body 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316L stainless steel Hast. C 316L stainless steel Hast. C 316L stainless steel Hast. C 316L stainless steel Hast. C 316 stainless steel Hast. C lining 316 stainless steel Hast. C lining 316 stainless steel Hast. C lining 316 stainless steel Hast. C lining 5 6 7 8 9 S T V W X Note1 <Indicator and arrester> Indicator Arrester None None Analog, 0 to 100% linear scale None Analog, custom scale None None Yes Analog, 0 to 100% linear scale Yes Analog, custom scale Yes Digital, 0 to 100% linear scale None Digital, custom scale None Digital, 0 to 100% linear scale Yes Digital, custom scale Yes Digital, 0 to 100% linear scale (Local configurator unit with LCD display) None Digital, custom scale (Local configurator unit with LCD display) None Digital, 0 to 100% linear scale (Local configurator unit with LCD display) Yes Digital, custom scale (Local configurator unit with LCD display) Yes <Approvals for hazardous locations> None (for ordinary locations) TIIS, Flameproof (Cable gland seal) (*6) TIIS, Intrinsic safety FM, Flameproof (or explosionproof) (*9) FM, Intrinsic safety and nonincentive FM Combined of flameproof and intrinsic safety (*9) ATEX Flameproof (*8) ATEX Intrinsic safety ATEX Type n ATEX Combined of flameproof and intrinsic safety (*8) IECEx Scheme, Flameproof (*8) IECEx Scheme, Intrinsic safety CSA, Flameproof (or explosionproof) (*9) CSA, Intrinsic safety and nonincentive NEPSI, Flameproof (or exprosionproof) NEPSI, Intrinsic safety NEPSI, Combined of flameproof and intrinsic safety <Vent/ drain and mounting bracket> Vent/drain Mounting bracket Standard None Standard Yes, stainless steel (SUS304) Standard Yes, stainless steel (SUS316) Side None Side Yes, stainless steel (SUS304) Side Yes, stainless steel (SUS316) Note1: (*1) 100: 1 turn down is possible, but should be used at a span greater than 1/40 of the maximum span for better performance. 4 F KA 1V 1H 2V 2H 3V 3H 4V 4H A B D E F H L P Q S 1 2 4 5 Note6 Note9 Note9 Note8 Note8 Note8 Note9 A C G D H V X K P M R T E J F S U A C K D F L 14 15 21 Digit No. of code 1 2 3 4 5 6 7 8 Digit 12 13 14 15 21 Description Note <Options> Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None (*2) None None Yes Yes None Yes None Yes Yes (*5) Yes Yes Yes <Special applications and fill fluid> Treatment Fill fluid Standard Silicone oil Degreasing Silicone oil NACE specification Silicone oil (7th digit code "T" and 15th digit code "A", "B" are not available) <O-ring/Gasket and Teflon membrance> Teflon (gasket) <Bolt/nut> (*3) Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut NACE bolt/nut (ASTM A193 B7M/A194 2HM) NECE bolt/nut (ASTM A320 L7M/A194 2HM) 304 stainless steel bolt/304 stainless steel nut 316 stainless steel bolt/316 stainless steel nut <Other options> (*4) High accuracy type (*7) Instruction manual attached Opposite Vent/Drain Plug Position Instruction manual attached Instruction manual unattached High accuracy type(*7) Instruction manual unattached Opposite Vent/Drain Plug Position Instruction manual unattached F KA 0 9 10 11 12 13 14 15 21 5 Note2 Note5 Note5 Digit No. of code Y B M N P Q Y G N B Note 3 A B C D E U Note 4 Note 7 Note 7 H C L T P Note2: (*2) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select "Yes". Note3: (*3) In case of tropical use, select stainless bolts and nuts. Note4: (*4) If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. Note5: (*5) Not available for 10th digit code “C”. Note6: (*6) Available for 4th digit code "S". Note7: (*7) Available for 6th digit code "3", "4". Note8: (*8) Available for 4th digit code "6", "8", "T", "W". Note9: (*9) Available for 4th digit code "6", "T". ACCESSORIES ORDERING INFOMATION Oval flanges: When ordering this instrument, specify. 1. CODE SYMBOLS 2. Measuring range. 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale / Underscale Unless other wise specified, output hold function is supplied. 4. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S on 9th digit). 5. Tag No. (up to 14 alphanumerical characters), if required. (Model FFP, refer to Data Sheet No. EDS6128) Converts process connection to 1/2-14 NPT or to Rc1/2; in carbon steel or in 316 stainless steel. Hand held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) 5 FKA...5 OUTLINE DIAGRAM (Unit:mm) <AMP. case: T type> VENT/DRAIN PLUG (WHEN THE VENT/DRAIN PLUG ATTACHED ON THE UPPER SIDE OF THE DETECTOR) NOTE3) MTG. PIPE JIS 50A (2B) IN CASE OF 4TH DIGIT CODE "6" WITH ANALOG IND. WITH DIGITAL IND. "A" PRESS. CONN. ZERO ADJ. SCREW EARTH TERMINAL 8 10 41 IN CASE OF 4TH DIGIT CODE "5,7,8,9" (21) (11) 38 φ81 110 70 SCS13 100 ZERO VENT/DRAIN PLUG "B" CONDUIT CONN. 57 37 168 4 HOLES 9 DIA. 17 127 (171) U-BOLT M8 20 NOTE2) DETAIL "A" (PRESS. CONN.) φ18.5 OVAL FLANGE SCREW SEE TABLE1 SIDE VENT(OPTION) E F 41.3 8 2.5 φ15 226 H (229) NOTE2) DETAIL "B" (CONDUIT CONN.) L.P 10 D SEE TABLE1 SEE TABLE1 Conduit conn. Press. conn. 4th digit of the code symbols D E F H 5 G 1/2 18 2 Rc1/4 H.P 4-M8×12 Oval frange screw 7/16-20UNF SCREW DEPTH15 6 1/2-14NPT 16 4 1/4-18NPT 7/16-20UNF SCREW DEPTH15 7 Pg13.5 10.5 4.5 1/4-18NPT M10 SCREW DEPTH15 8 M20×1.5 16 4 1/4-18NPT M10 SCREW DEPTH15 9 Pg13.5 10.5 4.5 1/4-18NPT 7/16-20UNF SCREW DEPTH15 27 70 104 TABLE 1 CONNECTION DIAGRAM −/CK− CK+ 75 + <SS TAG PLATE> 20 6 NOTE2) WHEN THE 7TH DIGIT OF THE CODE SYMBOLS "H,M,T" NOTE3) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS ATTACHED ON THE UPPER SIDE OF THE DETECTOR (WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P). <AMP. case: L type> VENT/DRAIN PLUG (WHEN THE VENT/DRAIN PLUG ATTACHED ON THE UPPER SIDE OF THE DETECTOR) NOTE3) MTG. PIPE JIS 50A (2B) IN CASE OF 4TH DIGIT CODE "T" IN CASE OF 4TH DIGIT CODE "S,V,W,X" "A" PRESS. CONN. 120 φ81 41 8 103 70 φ81 103 41 10 ZERO ADJ. SCREW RO 38 57 "B" CONDUIT CONN. 37 4 HOLES 9 DIA. 172 (21) (175) (11) WITH ANALOG IND. U-BOLT M8 126 43 41 VENT/DRAIN PLUG WITH DIGITAL IND. NOTE2) OVAL FLANGE SCREW SEE TABLE1 DETAIL "B" (CONDUIT CONN.) φ18.5 SIDE VENT(OPTION) φ15 F 8 41.3 2.5 H E L.P 10 D SEE TABLE1 SEE TABLE1 Conduit conn. Press. conn. H.P 198 (201) NOTE2) DETAIL "A" (PRESS. CONN.) EARTH TERMINAL 4-M8×12 4th digit of the code symbols D E F H S G 1/2 18 2 Rc1/4 7/16-20UNF SCREW DEPTH15 T 1/2-14NPT 16 4 1/4-18NPT 7/16-20UNF SCREW DEPTH15 V Pg13.5 10.5 4.5 1/4-18NPT M10 SCREW DEPTH15 W M20×1.5 16 4 1/4-18NPT M10 SCREW DEPTH15 X Pg13.5 10.5 4.5 1/4-18NPT 7/16-20UNF SCREW DEPTH15 27 Oval frange screw 70 104 TABLE 1 OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN) 10th digit code C (Cable gland type) NOTE1) G1/2 DETAIL C φ33.5 φ13 <SS TAG PLATE> 19 106 17 CONNECTION DIAGRAM "C" CONDUIT CONN. G1/2 −/CK− CK+ CABLE GLAND 75 + 20 NOTE1) IN CASE OF 10TH CODE“C” , φ11 CABLE IS SUITBLE. NOTE2) WHEN THE 7TH DIGIT OF THE CODE SYMBOLS "H" NOTE3) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS ATTACHED ON THE UPPER SIDE OF THE DETECTOR (WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C,P). 7 FKA...5 TABLE 2 Authorities ATEX Authorities Intrinsic safety Ex II 1 G Ex ia IIC T5 Tamb = –40°C to +50°C Ex ia IIC T4 Tamb = –40°C to +70°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) Factory Mutual ATEX Ex II 2 GD Ex d IIC T6 IP66/67 T85°C Tamb = −40°C to +65°C Ex d IIC T5 IP66/67 T100°C Tamb = −40°C to +85°C Factory Mutual Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C CSA Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C Entity Parameters: Vmax=28V, Imax=94.3mA, Pi=0.66W, Ci=35.98nF, Li=0.694mH CSA Note) “Seal Not Required” enclosure is allowed. Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester), Ci=36nF (With Arrester), Li=0.6mH (Without analog meter), Li=0.7mH (With analog meter) TIIS Ex ia IIC T4 Tamb max = +60°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=38.4nF, Li=0.694mH IECEx Scheme Ex ia IIC T4 Tamb = –40°C to +70°C Ex ia IIC T5 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) NEPSI TIIS Ex do IIB+H2 T4 Tamb max = +60°C Maximum process temp. = +120°C IECEx Scheme Ex d IIC T5 IP66/67 Tamb = −40°C to +85°C Ex d IIC T6 IP66/67 Tamb = −40°C to +65°C NEPSI Ex d IIB+H2 T6 Tamb = −40°C to +60°C 13th digit Y,G,N Y,G,N Y,G,N Y,G,N ATEX Ex II 3 GD EEx nL IIC T5 Tamb = –40°C to +50°C EEx nL IIC T4 Tamb = –40°C to +70°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=25.18nF, Li=0.694mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH EEx nAL IIC T5 Tamb = –40°C to +50°C EEx nAL IIC T4 Tamb = –40°C to +70°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C Type n Nonincendive Authorities Ex ia IIC T4 Ex d IIB+H2 T6 / Ex ia IIC T4 Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H Flameproof Factory Mutual (pending) Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H Entity Parameters: Ui=42.4V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH CSA Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Ci=25.18nF (Without Arrester), Ci=35.98nF (With Arrester), Li=0.694mH Caution on Safety *Before using this product, be sure to read its instruction manual in advance. International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice. Printed in Japan