PD-Series - Carling Technologies

16 | PD-Series - Introduction
PD-Series
Ground Fault Circuit Protection
SmartGuard is an equipment ground fault protection
device that functions as a standard high-quality
Carling hydraulic/magnetic circuit breaker, offering
customized overload and short circuit protection.
In addition, this breaker senses and guards against
faults to ground using a state of the art integrated
circuit developed by Carling. This new technology
detects faults and when a fault occurs, the breaker
trips and an LED illuminates. The LED gives a clear
indication that the trip occurred as a result of leakage.
This protection helps prevent serious equipment
damage and fire.
Agency Certifications:
Features:
Š Overload, short circuit and ground fault protection UL Standard 1077 Component Recognition
in a single package
Program as Equipment
Š Handle style actuators with optional
Leakage Circuit Interrupter
“handleguard”
and, Protectors, Supplementary
Š Wiping Contacts - Mechanical linkage with two(FTTJ2, File E177510).
step actuation – cleans contacts, provides high,
UL Standard 943 Tested as Ground Fault Circuit
positive contact pressure & longer contact life
Interrupters for Equipment
Š A trip-free mechanism, a safety feature which
Protection.
makes it impossible to manually hold the contacts CSA Certified
Component Equipment Leakage
closed during overload or fault conditions.
Current Interrupter with
Š A common trip linkage between all poles, another
Supplementary Protector, under
safety feature, ensures that an overload in one
Class C22.2,No. 144-M91, File
pole will trip all adjacent poles.
LR47848-50
Š Front panel or DIN rail mounting options
TUV Certified
IEC 947-2 and appendix B: Circuit
Š “State of the art” integrated circuit developed by
Breakers incorporating Residual
Carling
Current Protection. Complies
Š Equipment leakage sensitivity from 10 to 100
with waveform requirements of
milliamps
IEC 1008-1, Type A.
Š Integral push-to-test button and LED “tripped”
indicator
Š Immediate reset after fault has been cleared
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PD-Series Circuit Breaker - General Specifications | 17
Electrical Tables
Table A: Lists UL Recognized & CSA Certified configurations
and performance capabilities as a Component Supplementary
Protector.
Table B: Lists TUV Certified configurations and performance
capabilities as a Circuit breaker incorporating residual current
protection.
PD-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTOR & EARTH LEAKAGE CURRENT INTERRUPTER
VOLTAGE
CIRCUIT
CONFIGURATION
SERIES
INTERRUPTING
CURRENT RATING
FULL
GENERAL
LEAKAGE
CAPACITY (AMPS)
CURRENT
UL / CSA
MUST - TRIP
MAX RATING
FREQUENCY
LOAD
PURPOSE
WITHOUT
RATING
VOLTS
HERTZ
PHASE
AMPS
AMPS
BACKUP FUSE
(MILLIAMPS)
120/208
50/60
1
1-50
---
5000
7-100
120/208
50/60
31
1-50
---
5000
7-100
208-240
50/60
3
1-50
---
2000
7-100
480Y
50/60
3
1-30
30.1-50
2000
7-100
Electrical
Mechanical
Maximum Voltage AC, 480 WYE/277 VAC, 50/60 Hz
Endurance
Standard Current Ratings 1.00, 2.50, 5.00, 7.50, 10.0, 15.0,
20.0, 25.0, 30.0, 35.0, 40.0 & 50.0
Trip Free
amps. For other ratings, consult factory.
Insulation Resistance
Minimum of 100 Megohms @ 500 VDC.
Dielectric Strength
1960 VAC, 60 Hz for one minute
between all electrically isolated
terminals.
Trip Indication
Resistance, Impedance From Line to Load Terminal
(Values Based on Series Trip Circuit
Breaker)
RESISTANCE, IMPEDANCE VALUES
from Line to Load Terminals
Ampere Rating
10,000 ON-OFF operations @ 6 per
minute; with rated current and voltage.
All SmartGuard equipment leakage
circuit breakers will trip on overload
or leakage to ground, even when
actuator is forcibly held in the ON
position.
The actuator moves to the OFF
position when an overload or earth
leakage ground fault causes the
breaker to trip. The LED is illuminated
when leakage to ground causes the
circuit breaker to trip.
Physical
20.1 - 50.0
Pulse Tolerance Curve
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
Multiple of
Rated Current
Ir
Time Delay Curves
22, 24, 26
12x
t
4.165
Leakage To Ground
Standard Must Trip
Leakage Current Ratings
Trip Time
Test Button
Leakage Trip Indicator
8.33
16.67
Time in
Milliseconds
Number of Poles
2, 3 & 4
Length (included switched
or unswitched neutral)
4.2 inches ( 106.7 mm)
Width
2-pole: 3.0 inches (76.2 mm)
3-pole: 3.75 inches (95.3 mm)
4-pole: 4.5 inches (114.3 mm)
Depth
2.5inches (63.5mm).
Weight: 2-pole
16.0 oz. (453.6 gm)
3-pole: 21.4 oz. (606.7 gm)
4-pole: 26.9 oz. (762.6 gm)
Standard Colors
Housing - gray;
Actuator - black, red, or white
Mounting
Front Panel or Standard 35mm
Symmetrical DIN Rail (35 x 7.5 or
35 x 15mm per DIN EN5002).
Termination
Box Lug
7, 10, 15, 30, 50 & 100 milliamps. For
other ratings, consult factory.
300 ms Max. @ 100%, 40ms Max. @
Environmental
500% of must trip leakage current.
Operating Temperature +10°C to +50°C
On breaker face above actuator.
Red LED on breaker face above
actuator.
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
18 | PD-Series – Circuit & Terminal Diagrams
Notes:
1
All dimensions are in inches [millimeters].
2
Tolerance ±.020 [.51] unless otherwise specified.
Notes:
Other time delay values available, consult factory.
Delay Curves 21,22,24,26: Breakers to hold 100% and must trip at 125%
of rated current and greater within the time limit shown in this curve.
Delay Curve 20: Breakers to hold 100% and must trip at 150% of rated
current and greater within the time limit shown in this curve.
All Curves: Curve data shown represents breaker response at ambient
temperature of 77°F (25°C) with no preloading. Breakers are mounted in
standard wall-mount position.
The minimum inrush pulse tolerance handling capability is 12 times the
rated current. These values are based on a 60 Hz 1/2 cycle, 8.33 ms pulse.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
PD-Series – Circuit & Terminal Diagrams | 19
Notes:
1
All dimensions are in inches [millimeters].
2
Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
20 | PD-Series – Ordering Scheme
PD R – B – 24 – 650 – B – 2 A 1 – 1 – C
1
Series
3
Circuit
2
System
Voltage/Poles
4
Frequency
& Delay
5
Current Rating
2 SYSTEM VOLTAGE / POLES1
System Voltage
120VAC 1Ø
A
120/240 VAC 1Ø
B
120/208 VAC 1Ø,
C
120/240 VAC 1Ø
120/208 VAC 1Ø,
D
120/240 VAC 1Ø
208/240 VAC 3Ø
E
208/240 VAC 3Ø
F
208/240 VAC 3Ø
G
480Y VAC 3Ø
P
480Y VAC 3Ø
Q
480Y VAC 3Ø
R
Poles
One plus unswitched neutral
Two
Two plus unswitched neutral
Two plus switched neutral
Three
Three plus unswitched neutral
Three plus switched neutral
Three
Three plus unswitched neutral
Three plus switched neutral
3 CIRCUIT
Series Trip (Current)
4 FREQUENCY & DELAY
20
22
410
512
415
517
420
522
425
527
430
435
440
24
26
50/60Hz Instantaneous
50/60Hz Short
AMPERES
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
3.000
3.500
4.000
8
Actuator
9
Actuator
Color
10
Mounting
11
Agency
Approval
445
450
455
460
465
470
475
480
485
490
495
4.500
5.000
5.500
6.000
6.500
7.000
7.500
8.000
8.500
9.000
9.500
7 TERMINAL
2
Front Connected Box Lug
8 ACTUATOR
A
Handle
B
Handle w/ handleguard
9 ACTUATOR COLOR & LEGEND4
Acuator Color
I-O
ON-OFF
White
A
B
Black
C
D
Red
E
F
Dual
1
2
3
Legend Color
Black
White
White
10 MOUNTING3
1 THREADED INSERT 6-32 X 0.195 INCHES
2 THREADED INSERT ISO M3 X 6.5 MM
50/60Hz Medium
50/60Hz Long
11 AGENCY APPROVAL
UL Recognized & CSA Certified
C
TUV Certified
U
5 CURRENT RATING (AMPERES)
CODE
7
Terminal
6 EQUIPMENT LEAKAGE - TRIP CURRENT (MILLIAMPS)2
B
7
D
15
F
50
C
10
E
30
G
100
1 SERIES
PD
B
6
Equipment
Leakage Trip Current
610
710
611
711
612
712
613
614
615
616
617
10.000
10.500
11.000
11.500
12.000
12.500
13.000
14.000
15.000
16.000
17.000
Time Delay Curves
618
620
622
624
625
630
635
640
650
18.000
20.000
22.000
24.000
25.000
30.000
35.000
40.000
50.000
Notes:
1
Units with a switched or unswitched neutral connection are the same size as a unit with
an additional breaker pole (e.g. a 2-pole unit with a switched or unswitched neutral is the
same physical size as a 3-pole unit.)
Switched neutral poles contain the same overcurrent protection as the other poles.
2
The leakage currents shown will cause the breaker to trip (must-trip current). The musthold current is 67% of the must-trip current.
3
All breakers are front panel mountable using screw size shown. Breakers may also be
mounted on either 35mm x 7.5mm or 35mm x 15mm symmetrical DIN rail.
4
TUV certifed units must have I-O or Dual legends
Instantaneous
Medium
Short
Long
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com