DRD15 SERIES

DRD15 SERIES
DC - DC DIN RAIL MOUNTABLE POWER SUPPLY
INDUSTRIAL CONTROL EQUIPMENT
FEATURES
‧4:1 WIDE INPUT RANGE
‧SHORT CIRCUIT PROTECTION
‧INTERNAL INPUT FILTER
‧LOW PROFILE
‧3 YEARS WARRANTY
C
a
US
UL 60950-1
EN 60950-1
IND. CONT. EQ.
UL 508
MODEL LIST
MODEL NO.
INPUT
INPUT
OUTPUT OUTPUT OUTPUT
CURRENT
VOLTAGE (typ.) (max.) WATTAGE VOLTAGE CURRENT
EFF.
(min.)
EFF.
(typ.)
Single Output Models
DRD15-03
9-36 VDC
0.62 A
1.8 A
11.5 WATTS
+ 3.3 VDC
3.5 A
77%
79%
DRD15-05
9-36 VDC
0.70 A
1.9 A
13.5 WATTS
+ 5 VDC
2.7 A
78%
80%
DRD15-09
9-36 VDC
0.70 A
1.9 A
13.5 WATTS
+ 9 VDC
1.5 A
79%
81%
DRD15-12
9-36 VDC
0.76 A
2.1 A
15 WATTS
+ 12 VDC
1.25 A
80%
82%
DRD15-15
9-36 VDC
0.76 A
2.1 A
15 WATTS
+ 15 VDC
1A
81%
83%
DRD15-24
9-36 VDC
0.76 A
2.1 A
15 WATTS
+ 24 VDC
0.63 A
81%
83%
max.
unit
200
KHz
VDC
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
GENERAL
Characteristics
Switching frequency
Isolation voltage
Isolation resistance
Ambient temperature
Derating (see derating curve)
Storage temperature
Relative humidity
Temperature coefficient
MTBF
Altitude during operation
min.
Conditions
Vi nom, Io nom
Input-Output
Input-Output, @ 500VDC
Operating at Vi nom
100
-40
Vi nom, from +51 oC to +71 oC
Non operational
Free air convection
Vertical ( other direction may derating using )
www.chinfa.com
2015.08.06
C
% RH
% / oC
Hours
996,000
Hours
9V
1,055,000
Hours
12V
951,000
Hours
15V
998,000
Hours
24V
989,000
Hours
4,850
L91 x W18 x D56.5
Installation position
o
5V
IEC 60068-2-13
Cooling
MΩ
o
C
% / oC
1,066,000
3.3V
Dimension
Pollution degree
+ 71
2.5
+ 85
95
± 0.03
-40
20
Vi nom, Io nom
Vi nom, Io min
Bellcore Issue 6 @40 oC, GB
typ.
100
1,500
m
mm
2
[email protected]
P1
DRD15 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
INPUT SPECIFICATIONS
Characteristics
Conditions
Input voltage range
Ta min ... Ta max, Io nom
No load input current
Vi nom, Io = 0
Input voltage w/o damage
Io nom
Startup voltage
Io nom
Input filter
Pi type
min.
typ.
9
24
max.
unit
36
VDC
30
mA
40
VDC
VDC
8.5
OUTPUT SPECIFICATIONS
Characteristics
Conditions
Output voltage accuracy
Vi nom, Io max
Minimum load
Line regulation
Load regulation
Vi nom
Io nom, Vi min ...Vi max
Vi nom, Io min ...Io nom
Startup time
Transient recovery time
Ripple & noise
Power back immunity
Vi nom, Io nom
Vi nom, 1~0.5 Io nom
Vi nom, Io nom, BW = 20MHz
Vi nom, Io nom
Capacitor load
Vi nom, Io nom
min.
typ.
max.
unit
±1
%
%
%
%
%
ms
ms
0
±1
± 1.5
±1
50
1
100
3.3V
other
3.3V
5V
9V
12V
15V
24V
3.3V, 5V
3,500
2,200
1,000
9V
12V, 15V
24V
3.3V
5V
9V
12V
15V
24V
3.3V
5V
9V
12V
15V
24V
DC ON indicator threshold
at start up (Green LED)
Vi nom, Io nom
DC LOW indicator threshold
after start up (Red LED)
Vi nom, Io nom
Efficiency
Vi nom, Io nom, Po / Pi
mV
VDC
VDC
VDC
VDC
VDC
VDC
μF
μF
μF
μF
5.0
7.5
15
18
22
35
470
VDC
3.0
2.6
4.5
VDC
3.5
VDC
6.8
8.1
VDC
10.8
9
VDC
13.5
11
VDC
19.2
21.6
VDC
3.0
2.6
4.5
VDC
3.5
VDC
6.8
8.1
VDC
10.8
9
VDC
13.5
11
VDC
19.2
21.6
Up to 83%, See model list and typ efficiency curve
CONTROL AND PROTECTION
Characteristics
Input fuse
Internal surge voltage protection
Rated over load protection
Over voltage protection
Output short circuit
Degree of protection
www.chinfa.com
2015.08.06
min.
Conditions
typ.
max.
unit
T3A / 63VDC internal
IEC 61000-4-5
Vi nom (see typ current limited curve)
Vi nom, 0.8 Io nom
(Auto Recovery)
Varistor
3.3V
5V
9V
12V
15V
24V
110
3.8
5.75
10.35
14.4
17.25
28.8
165
4.3
6.5
11.7
16.2
19.5
32.4
Current limited (Auto-recovery)
%
VDC
VDC
VDC
VDC
VDC
VDC
IP20
[email protected]
P2
DRD15 SERIES
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
APPROVALS AND STANDARDS
UL / cUL
UL 508
CTUVUS
UL 60950-1 Recognized
TUV
EN 60950-1
CE
EN 61000-6-3, EN 55022 Class B
EN 61000-6-2, EN 55024, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4
EN 61000-4-5, EN 61000-4-6, EN61000-4-8, ENV 50204, EN 61204-3
Vibration resistance
meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
Case size
91 x 18 x 56.5 mm (3.58 x 0.71 x 2.22 inches)
Case material
Plastic
Weight
65g
Packing
0.11kg ; 120
/ 14.5kg / 2.28CUFT
MECHANISM & PIN CONFIGURATION
mm [inch]
CONSTRUCTION
Easy snap-on mounting onto the DIN-Rail
(TS35/7.5 or TS35/15), unit sits safely and
firmly on the rail; no tools required even to remove
2 1
Vo
+
INSTALLATION
12.00 [0.47]
11.00 [0.43]
18.00 [0.71]
Vi
+
3
91.00 [3.58]
4
56.50 [2.22]
49.60 [1.95]
32.30 [1.27]
51.50 [2.02]
91.00 [3.58]
45.00 [1.77]
Ventilation / Cooling
Normal convection
All sides 25m/m free space
For cooling recommended
Connector size range
AWG26-12 (0.2~2.5mm2) flexible / solid cable
-Connector can withstand torque at maximum
5 pound-inches.
4~5m/m stripping at cable end recommends.
Use copper conductors only, 60/75 oC
GENERAL TOLERANCE
0.00[0.00] - 30.00[1.18]
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
±0.50[0.02]
PIN ASSIGNMENT
2
3
OUT
Designation
1
IN
PIN NO
OTHER
4
www.chinfa.com
2015.08.06
Description
-
Negative output terminal
+
Positive output terminal
+
Positive input terminal
-
Negative input terminal
DC ON
Operation indicator LED
DC LO
DC Low indicator LED
[email protected]
P3
DRD15 SERIES
CIRCUIT SCHEMATIC
‧Block diagram for DRD15 series
Fuse
Vi +
Vo +
Line
Filter
Switching
Device
Rectifier
Vi -
Vo PWM
controller
Opto Isolation
Reference &
Error Amp.
Opto Isolation
Over Voltage
Detection
DC ON
(Green LED)
DC LO
(Red LED)
Output Level
Detection
DERATING CURVE
Input Voltage : 9.5V ~ 28V
Input Voltage :
50
Safe Operating Area
0
-40
51
50
Safe Operating Area
0
-40
71
51
-25
o
Input Voltage : >28V but
71
o
Temperature [ C ]
Temperature [ C ]
o
Ta : 50 C
36V
100
Power out [ % ]
100
Power out [ % ]
9V but <9.5V
100
Power out [ % ]
Power out [ % ]
100
Safe Operating Area
40
0
-40
41
80
Safe Operating Area
0
71
28
Input Voltage [ V ]
9
o
Temperature [ C ]
36
TYP. EFFICIENCY CURVE
Efficiency Vs Output Load
DRD15-12
85
85
84
80
83
Efficiency [ % ]
Efficiency [ % ]
Efficiency Vs Input Voltage
DRD15-12
82
81
80
70
65
60
79
78
75
Vi : 24VDC
Io : Full Load
9
12
www.chinfa.com
2015.08.06
15
18
21
24
27
Input Voltage (V)
30
33
36
55
10
20
30
40
50
60
70
Output Load (%)
80
90 100
[email protected]
P4