Technical Data

FlexTop 2202 Temperature Transmitter
4...20 mA transmitter for Pt100 sensors
2-, 3- or 4-wire sensors
Accuracy better than 0.25°C
Sensor offset correction
Automatic/configurable cable resistance
compensation (2-wire)
Sensor error detection
2-way configuration
Configurable damping and status indication
Engineering unit °C or °F
PC datalogging
Excellent temperature stability
Ex ia IIC T5/T6, ATEX II 1G
Description
FlexTop 2202 is a 4...20 mA loop-powered transmitter for Pt100 sensors.
The Flex-Program has a datalogging facility enabling the user to monitor measuring results or calibrate the measuring setup.
Either 2-, 3- or 4-wire sensors can be used. For 2-wire sensors an
automatic balancing of the sensor cable resistance is possible with
shorted sensor cable. The cable resistance can be manually configured as well.
FlexTop 2202 is embedded in silicone which makes it resistant to
humid environments.
Using a PC, the Windows-based Flex-Program and a FlexProgrammer
configuring unit, the following parameters can be configured via the
output connectors (2-way communication): TAG no., number of wires,
cable resistance, error detection level, measuring range/unit, damping,
offset and status indication.
www.baumerprocess.com
Design and specifications subject to change without notice
FlexTop 2202, fitting into the DIN B housing, has a 6 mm center hole
for quick sensor replacement. The spring loaded mounting screws
ensure a safe fastening even in vibrating environments.
Data Sheet 2202-1
Page 1
Technical Data
Input
Environmental conditions
Accuracy
Operating temperature-40...85°C
Span < 250°C: Span > 250°C: < 0.25°C {2}
0.1% of span
Storage temperature-55...90°C
Humidity
< 98% RH, cond. (IEC 68-2-38)
Sample time
< 0.7 sec.
Vibrations
GL, test 2 (IEC 68-2-6)
Pt100 Standard
IEC/DIN/EN 60 751-2
Long-term test
IEC 770 6.3.2
RTD measuring current
0.3 mA, continuously
Sensor type
2-, 3- or 4-wires {1}
Sensor short detection
< -225°C
Sensor break detection
> 875°C
Error detection delay
< 10 sec.
Compensation for
cable error
< 0.02°C/Ohm (3-wire)
Cable resistance
Max. 20 Ohm /wire {1}
Measuring range
Internal inductivityLi < 10 µH
-200...850°C {1}
Internal capacity Measuring unit
°C or °F {1}
Barrier dataU < 28 Vdc ; I < 0.1 A ; P < 0.7 W
EMC data
Minimum span25°C
Generic standards
EN 61000-6-3, EN 61000-6-2
Product standards
EN 61326
NAMUR
NAMUR NE21
Approval Ex ia IIC T5/T6, ATEX II 1G
Supply range
8...28 Vdc
Ci < 10 nF
Protection
+/- 35 Vdc
Temperature class
Suppression
50 and 60 Hz
Resolution
Mechanical data
14 bit
Dimensions
ø44 x 19 mm
Repeatability
< 0.1°C
Protection class
Housing: IP 40
Ripple immunity
IEC 770 6.2.4.2
T1...T5: T6: -40 < Tamb < 85°C
-40 < Tamb < 50°C
Other data
Offset AdjustmentMax. + 10°C {1}
Output
Temperature drift
Typ. 0.003% per °C
Max. 0.01% per °C
10 sec.
Signal span
4...20 mA, 2-wire
Power-on time
Accuracy
< 0.1% of signal span
Supply range
8...35 Vdc
Test conditions
Ripple immunity
3 Vrms
Configuration0...100°C
Load equationRL < (Vcc - 8)/23 [kOhm]
Amb. temperature
23°C +/- 2°C
Power supply
24 VDC
Up/Down scaling limits
23 mA/3.5 mA {1}
Damping
0...30 sec. {1}
Protection
Reversed polarity protection
According to national laws or by returning to Baumer
Resolution
12 bit
Notes
Disposal of product and packing
Effect of variations in supply voltage:
{1}Configurable
Output current
0.01% per volt
{2}
TAG No.
15 characters {1}
Lower range limit < 100°C
Measuring Ranges
Type
Standard
Pt100
DIN/EN/IEC 60751 Lin. resistance
Range
-200...850°C {2}
0...500 Ohm
Min. span
25°C
5 Ohm
Accuracy
0.25°C
1 Ohm
Ordering details - FlexTop 2202
2202 000x (x)
Type
8´ Digit
Not configured, standard safety
Not configured, Ex ia IIC T5/T6, ATEX II 1G
Not configured, Ex nA II T5, ATEX II 3G
1
2
3
Configuration
9´ Digit
Configuration according to customer specifications (default is 0...120°C, 3-wire)
C
www.baumerprocess.com
Design and specifications subject to change without notice
Data Sheet 2202-1
Page 2
Non-Ex Application
230 VAC
Pt100
5
3
4
1
2
4
3
6
2
1
-
+
-
+
+
24 VDC
4...20 mA
FlexTop 2202
FlexView
Power supply
Ex Application
Zone 0/1
Pt100
230 VAC
Safe area
3
4
1
2
4
5
6
3
1
2
-
+
-
+
+
-
24 VDC
4...20 mA
FlexTop 2202
Barrier
FlexView
Power supply
Configuration
2
2
1
Note:
Disconnect loop supply before connecting the FlexProgrammer
to FlexTop 2202.
1
www.baumerprocess.com
Design and specifications subject to change without notice
Data Sheet 2202-1
Page 3
Electrical Installation
RTD
Potentiometer
R
Resistance
R
RTD
No compensation {3}
RTD
No compensation {3}
Potentiometer
Resistance
R
R
UK/2013-02-10 This data sheet may only be reproduced in full.
No cable
compensation {3}
RTD
3-wire cable
compensation
3-wire compensation for
transfer resistance {4}
RTD
3-wire cable
compensation
Potentiometer
Resistance
R
R
4-wire compensation for
transfer resistance {4}
4-wire cable
compensation
RTD
4-wire cable
compensation
Notes
{3} Configurable compensation for cable resistance
{4} Transfer resistance between element and wiper
Accessories
Dimensional drawing
ø44
ø6
26.3
33
ø4 mounting hole.
Spring loaded
mounting screws.
www.baumerprocess.com
Design and specifications subject to change without notice
[mm] The FlexProgrammer 9701 is a dedicated tool to configure all
Baumer configurable products.
Type No. 9701-0001 comprises:
FlexProgrammer interface unit
CD with the FlexProgram software and product drivers (DTM)
USB cable
Cable with 2 alligator clips
Data Sheet 2202-1
Page 4