Technical Data

FlexTemp 2301 Temperature Transmitter
4...20 mA transmitter for Pt100 sensors
2-, 3- or 4-wire sensors
Accuracy better than 0.25°C
Sensor offset correction
Automatic/configurable cable resistance
compensation (2-wire)
Sensor error detection
2-way configuration (Windows)
Configurable damping and status indication
Engineering unit °C or °F
PC datalogging
Description
FlexTemp 2301 is a 4...20 mA loop-powered transmitter for Pt100
sensors.
Either 2-, 3- or 4-wire sensors can be used. For 2-wire sensors an
automatic balancing of the sensor cable resistance is possible with
shorted sensor cable. The cable resistance can be manually configured as well.
www.baumerprocess.com
Design and specifications subject to change without notice
Using a PC, the Windows-based FlexProgram software and a FlexProgrammer configuring unit, the following parameters can be configured
via the output connectors: TAG no., number of wires, cable resistance,
error detection level, measuring range/unit, damping, offset and status
indication.
The FlexProgram has a datalogging facility enabling the user to monitor measuring results or calibrate the measuring setup.
Data Sheet 2301-1
Page 1
Technical Data
Input
Environmental conditions
Accuracy
Operating temperature
-40...85°C
Span < 250°C:
Span > 250°C:
< 0.25°C {2}
0.25% of span
Storage temperature
-55...90°C
Humidity
< 90% RH (IEC 68-2-38)
Sample time
< 0.7 sec.
Vibrations
GL, test 2 (IEC 68-2-6)
Pt100 Standard
IEC/DIN/EN 60 751-2
Long-term test
IEC 770 6.3.2
RTD measuring current
0.3 mA, continuously
Sensor type
2-, 3- or 4-wires {1}
Sensor short detection
< -225°C
Sensor break detection
> 875°C
Error detection delay
< 10 sec.
Compensation for
cable error
< 0.02°C/Ohm (3-wire)
Dimensions
62 x 88 x 24 mm
Cable resistance
Max. 20 Ohm /wire {1}
Protection class
Housing: IP 30; Terminals: IP10
Measuring range
-200...850°C {1}
Measuring unit
°C or °F {1}
Minimum span
25°C
EMC data
Generic standards
EN 61000-6-3, EN61000-6-2
Product standards
EN 61326
Namur
NE21
Mechanical data
Other data
Temperature drift
Typ. 0.003% per °C
Max. 0.01% per °C
Protection
+/- 35 Vdc
Power-on time
10 sec.
Suppression
50 and 60 Hz
Failure information
Namur NE43
Resolution
14 bit
Repeatability
< 0.1°C
Ripple immunity
IEC 770 6.2.4.2
Offset Adjustment
Max. + 10°C {1}
Output
Test conditions
Configuration
0...100°C
Amb. temperature
23°C +/- 2°C
Power supply
24 Vdc
Disposal of product and packing
Signal span
4...20 mA, 2-wire
Accuracy
< 0.1% of signal span
Supply range
8...35 Vdc
Notes
Ripple immunity
3 Vrms
{1}
Configurable
Load equation
RL < (Vcc - 8)/23 [kOhm]
{2}
Lower range limit < 100°C
Up/Down scaling limits
23 mA/3.5 mA {1}
Damping
0...30 sec. {1}
Protection
Reversed polarity protection
Resolution
12 bit
According to national laws or by returning to Baumer
Effect of variations in supply voltage:
Output current
0.01% per volt
TAG No.
15 characters {1}
Ordering details - FlexTemp 2301
2301 000x (x)
Type
Not configured, standard safety
8´ Digit
Configuration
Configuration according to customer specifications (default is 0...120°C, 3-wire)
9´ Digit
www.baumerprocess.com
Design and specifications subject to change without notice
1
C
Data Sheet 2301-1
Page 2
Application Example
Pt100
230 Vac
3
7
4
8
3
4
1
2
1
2
+
24 Vdc
-
4...20 mA
FlexTemp 2301
Power supply
Configuration
FlexProgrammer
Note:
Disconnect loop supply before
connecting the FlexProgrammer
to FlexTemp 2301.
1
FlexProgrammer
2
1 2
FlexProgrammer 9701
1
2
Red clip
1
2
Black clip
Note: Ambient temperature range 0...50°C
www.baumerprocess.com
Design and specifications subject to change without notice
Data Sheet 2301-1
Page 3
Electrical Installation
RTD
Pt100
Pt100
Pt100
3
7
3
7
3
7
4
8
2-wire sensor
4
8
3-wire sensor
4
8
4-wire sensor
Accessories
Dimensional drawings
[mm]
65.5
Type No. 9701-0001 complies:
FlexProgrammer interface unit
CD with the FlexProgram software and product drivers (DTM)
USB cable
Cable with 2 alligator clips
www.baumerprocess.com
Design and specifications subject to change without notice
88
62
UK/2007-03-14 This data sheet may only be reproduced in full.
The FlexProgrammer 9701 is a dedicated tool to configure all
Baumer configurable products.
24
Data Sheet 2301-1
Page 4