Download

Datasheet
ACT20M
Signal Isolation and Conversion
NEW
Weidmuller’s new 8-pole housing, module power can
be distributed through the rail for minimized power
wiring and reduced installation costs. This “Power Rail”
provides the flexibility to add or remove individual
modules quickly and easily without affecting the wiring
or operation of other components on the rail.
The ACT20M range offers D.C. and temperature isolators
and converters for use in industrial and marine applications.
Configuration is simple because the ACT20M modules
require no calibration. Models with selectable temperature,
voltage and current ranges feature DIP switches. For the
Universal input model, Weidmuller provides vendorindependent, FDT-based configuration software available
for download from the Weidmuller website.
High quality signal isolation and conversion in a
slim 6mm wide housing format is now available with
Weidmuller’s ACT20M range. Features include
worldwide approvals for both standard and hazardous
area installations. This series of single- and dual-channel
models extends Weidmuller’s signal conditioning
portfolio with a package of solutions for industrial
process measurement and control applications.
ACT20M is designed to reduce the time and cost
of building control panels. DIN-rail mounted in
Weidmuller, Canada
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (877) 300-5635
Email: [email protected]
Website: www.weidmuller.ca
Weidmuller, Mexico
Blvd. Hermanos Serdán 698,
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: [email protected]
Website: www.weidmuller.com.mx
Features:
• Very high density analog signal isolation
and conversion
• Easy installation with Power Rail cross-connect option
• DIP switches for calibration-free re-ranging
• Universal input model uses FDT configuration software
(and CBX200 interface)
• CE, cULus, cFMus Class 1 Div. 2 and Class 1 Zone 2
ATEX, IECEx Zone 2, DNV, GL approvals
• Ambient temperature range typically -13˚F to 158˚F
(-25˚C to 70˚C) Weidmuller, United States
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: [email protected]
Website: www.weidmuller.com
ACT20M Signal Isolation and Conversion
Universal input converter
ACT20M-UI-AO-S
• Isolating and converting of
temperature signals and DC signals
• Configuration using FDT/DTM
software
• Optional power supply via the DIN-railbus
• 3 way isolation
4
3
I, U, R
IN
2
5
I, U
6
OUT
7
1
82
83
Supply
8
Supply
Technical data
Input
Sensor
Thermocouples: B, E, J, K, L, LR, N, R, S, T, U, W3, W5
RTD: PT100, PT1000, Ni120, Ni100, Ni1000
2/3/4 wire
10 Ω…10 k Ω
0(4)...20 mA
0(2)...10 V, 0(1)...5 V
> 10 MΩ
< 150 Ω
> 15 V DC at 20 mA
Potentiometer/Resistance
Input current
Input voltage
Input resistance, voltage
Input resistance, current input
Sensor supply
Output
Output current
Output voltage
Load resistance, current
Load resistance, voltage
General data
Supply voltage
Power consumption
0(4)…20 mA
0(2)…10 V
< 600 Ω
> 10 k Ω
Temperature coefficient
Insulation coordination
Insulation voltage
Rated voltage
Pollution degree
Overvoltage category
Approvals
Dimensions
Length x width x height
Clamping range (nominal / min. / max.)
Note
mm
mm2
+
–
3
5
U, I, ϧ
6
U, I
2
Power
1
In
+
–
3
7
8
4
5
U, I, ϧ
6
U, I
2
Power
1
7
8
+
–
Out 1
+
Power
24 V
–
+
–
PLC
mA
passive
Out 1
+
PLC
mA
passive
Power
24 V
–
ACT20M-UI-AO-S
+
4-wire
V
active
4
3
In
–
5
U, I, ϧ
6
U, I
2
2.5 kV
300 V
2
II
1
cULus 61010-1, cFMus Div.2, ATEX zone 2, IECEx Zone
2, DNV, GL
3
Power
TC
In
+
–
114.3 x 6.1 x 112.5
2.5 / 0.5 / 2.5
7
8
4
Type
ACT20M-UI-AO-S
Qty.
1
Part No.
1176030000
Note
Accessories
Marker
USB interface
2
In
5
U, I, ϧ
6
U, I
2
Power
1
7
8
+
–
Out 1
+
Power
24 V
–
+
–
PLC
mA
passive
Out 1
+
PLC
mA
passive
Power
24 V
–
ACT20M-UI-AO-S
Ordering data
Note
4-wire
mA
active
2-wire
mA
passive
24 V DC ± 30 %
0.4 W (24 V supply / Passive input / 20 mA input &
output / 100 Ω load)
-25 °C…+70 °C
-40 °C…+85 °C
< 0.1 % span (DC, RTD)
< 0.2 % + CJ error (TC)
< 0.01 % /K
Ambient temperature (operational)
Storage temperature
Accuracy
ACT20M-UI-AO-S
4
Type
MF 5/7.5 MC NEUTRAL
CBX200 USB
Qty.
DIN-rail bus, refer to accessories page
Part No.
1877680000
8978580000
RTD
Sense +
4
R+
3
R–
2
Sense –
1
5
U, I, ϧ
6
U, I
Power
7
8
+
–
+
–
Out 1
PLC
mA
passive
Power
24 V
ACT20M Signal Isolation and Conversion
Signal splitter
ACT20M-CI-2CO-S
ACT20M-AI-2AO-S
• Isolating, converting and splitting
DC signals
• Configured using DIP switch
• Optional power supply via the
DIN-rail bus
• 4 way isolation
I IN
I OUT 2
4
5
3
6
2
1
7
82
83
8
I OUT 1
Supply
I, U
IN
4
5
3
6
I, U
OUT 2
2
1
Supply
7
82
83
I, U
OUT 1
Supply
8
Supply
Technical data
Input
Input current
Input voltage
0(4)…20 mA
–
0(4)…20 mA
0(2)…10 V
0(1)…5 V
< 75 Ω
> 500 k Ω
> 17 V DC at 20 mA
Input resistance, current input
Load resistance, voltage
Sensor supply
Output
Output current
Output voltage
< 75 Ω
–
–
Load resistance, current
Load resistance, voltage
General data
Supply voltage
Power consumption
< 300 Ω / channel
≥ 10 k Ω
0(4)…20 mA
0(2)…10 V
0(1)…5 V
< 300 Ω / channel
> 10k Ω / channel
24 V DC ± 30 %
24 V DC ± 30 %
0.4 W (24 V supply / Passive input / 20 mA input &
output / 100 Ω load)
0.4W (24 V supply / Passive input / 20 mA input &
output / 100 Ω load)
Ambient temperature (operational)
Storage temperature
Accuracy
Temperature coefficient
Cut-off-frequency
Insulation coordination
Insulation voltage
Rated voltage
Pollution degree
Overvoltage category
Approvals
-25 °C…+70 °C
-40 °C…+85 °C
< 0.05 % of measurement range
< 0.01 % /K
100 Hz
-25 °C…+70 °C
-40 °C…+85 °C
< 0.05 % of measurement range
< 0.01 % /K
100 Hz
2.5 kV
300 V
2
II
2.5 kV
300 V
2
II
cULus 61010-1, cFMus Div.2, ATEX zone 2, IECEx Zone
2, DNV, GL
cULus 61010-1, cFMus Div.2, ATEX zone 2, IECEx Zone
2, DNV, GL
114.3 x 6.1 x 112.5
2.5 / 0.5 / 2.5
114.3 x 6.1 x 112.5
2.5 / 0.5 / 2.5
Dimensions
Length x width x height
Clamping range (nominal / min. / max.)
0(4)…20 mA
–
mm
mm2
Note
Ordering data
Note
Accessories
Marker
Note
Type
ACT20M-CI-2CO-S
Qty.
1
Part No.
1175990000
Type
ACT20M-AI-2AO-S
Qty.
1
Part No.
1176020000
Type
MF 5/7.5 MC NEUTRAL
Qty.
Part No.
1877680000
Type
MF 5/7.5 MC NEUTRAL
Qty.
Part No.
1877680000
DIN-rail bus, refer to accessories page
DIN-rail bus, refer to accessories page
3
ACT20M Signal Isolation and Conversion
Converters for DC mA
and Volts
ACT20M-AI-AO-S
ACT20M-AI-AO-E-S
• Isolating and converting DC signals
• DIP switch for range changes
without re-calibration
• Optional power supply via the
DIN-rail-bus
• 3 way isolation
• Choice of active or passive mA input
(“E“ model is not hazardous
location approved)
4
I, U
IN
5
3
I, U
OUT
6
2
82
83
5
3
7
1
Supply
82
8
Supply
I, U
OUT
6
2
7
1
4
I, U
IN
83
Supply
8
Supply
Technical data
Input
Input current
Input voltage
Input resistance, current input
Input resistance, voltage
Sensor supply
Output
Output current
Output voltage
Load resistance, current
Load resistance, voltage
General data
Supply voltage
Power consumption
0(4)…20 mA
0(2)…10 V; 0(1)…5 V
< 75 Ω
> 500 k Ω
–
0(4)…20 mA
0(2)…10 V; 0(1)…5 V
<Input
600 Ω
> 10 k Ω
0(4)…20 mA
0(2)…10 V; 0(1)…5 V
<Input
600 Ω
> 10 k Ω
Switch
1
2
3
4
◼
◼
◼
◼
0 …V20DC
mA± 30 %
24
◼
◼
◼
4 … 20
0.4
W m(24 V supply / Passive
input
/ 20◼mA input
&
◼
◼
◼
◼
0 … 10 V/ 100 Ω load)
output
◼
◼
◼
◼
2 …°C…+70
10 V
-25
°C
◼
◼
◼
◼
0 …°C…+85
5V
-40
°C
◼
◼
…5 V % of measurement◼ range◼
<10.05
◼
◼
◼
◼
... 20 mA
loop
<00.01
% /K
◼
◼
◼
◼
4 ... 20
100
HzmA loop
Ambient temperature (operational)
Storage temperature
Accuracy
Temperature coefficient
Cut-off-frequency
Insulation coordination
Insulation voltage
Rated voltage
Pollution degree
Overvoltage category
Approvals
Dimensions
Length x width x height
Clamping range (nominal / min. / max.)
0(4)…20 mA
0(2)…10 V; 0(1)…5 V
< 75 Ω
> 500 k Ω
> 17 V DC at 20 mA
mm
mm2
2.5 kV
Switch
300
V1
Output
2
5
6
7
II
◼
◼
◼
0 … 20 mA
◼ ATEX
◼ zone ◼
cULus
cFMus Div.2,
2, IECEx Zone
4 … 2061010-1,
m
◼
◼
◼
2,0 DNV,
… 10 VGL
◼
◼
◼
2 … 10 V
◼
◼
◼
114.3
0 … 5 Vx 6.1 x 112.5
◼
◼
◼
2.5
1 …5/ 0.5
V / 2.5
1
2
3
4
◼
◼
◼
◼
0 … 20 mA
24 V DC ± 30 %
◼
◼
◼
◼
4 … 20 m
0.4 W (24 V supply / Passive
input
/ 20◼mA input
&
◼
◼
◼
0 … 10 V
output / 100 Ω load)
◼
◼
◼
◼
2 … 10 V
0 °C…+70 °C
◼
◼
◼
◼
0…5V
-40 °C…+85 °C
◼
◼
◼
◼
1 …5 V
< 0.2 % of measurement ◼range ◼
◼
◼
0 ... 20 mA loop
< 0.015 % /K
◼
◼
◼
◼
4 ... 20 mA loop
100 Hz
2.5 kV
Output
300
V1
2
5
II
◼
0 … 20 mA
◼
4 … 20 m
cULus
DNV, GL◼
0 … 10 61010-1,
V
◼
2 … 10 V
◼
0 … 5 Vx 6.1 x 112.5
114.3
◼
1 …5/ 0.5
V / 2.5
2.5
ACT20M-AI-AO-S
In
+
–
4
3
6
U, I
U, I
Power
1
4-wire
V, mA
active
4
+
–
3
7
8
4
5
6
U, I
1
Marker
Note
In
Type
ACT20M-AI-AO-S 2
Accessories
6
7
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
ACT20M-AI-AO-E-S
5
2
Ordering data
Switch
◼ = on
◼ = off
◼ = on
◼ = off
2-wire
mA
passive
Switch
Type
MF 5/7.5 MC NEUTRAL
U, I
Power
Qty.
71
8
Qty.
DIN-rail bus, refer to accessories page
+
–
Out 1
+
Power
24 V
–
+
–
+
–
PLC
V, mA
passive
Out 1
PLC
V, mA
passive
4-wire
V, mA
active
In
+
–
4
3
5
6
U, I
U, I
2
1
Power
7
8
+
–
+
–
Out 1
PLC
V, mA
passive
Power
24 V
Part No.
1176000000
Power
Type
ACT20M-AI-AO-E-S
Qty.
1
Part No.
1176010000
Part No.
1877680000
Type
MF 5/7.5 MC NEUTRAL
Qty.
Part No.
1877680000
24 V
DIN-rail bus, refer to accessories page
ACT20M Signal Isolation and Conversion
ILP and OLP isolators
ACT20M-CI-CO-ILP-S
ACT20M-CI-CO-OLP-S
• Isolation of DC mA signals
• Takes power from the input loop (ILP)
or output loop (OLP)
• Available as either single-channel or
double-channel version
• 2 way isolation
I IN 1
I IN 2
4
5
3
6
2
7
1
8
I OUT 1
I IN 1
I OUT 2
I IN 2
4
5
3
6
2
7
1
8
I OUT 1
I OUT 2
Technical data
Input
Input current
Input resistance, current input
Output
Output current
Load resistance, current
General data
Power consumption
Ambient temperature (operational)
Storage temperature
Accuracy
Temperature coefficient
Cut-off-frequency
Insulation coordination
Insulation voltage
Rated voltage
Pollution degree
Overvoltage category
Approvals
Dimensions
Length x width x height
Clamping range (nominal / min. / max.)
0(4)…20 mA
< 65 Ω at 25 °C
0(4)…20 mA
typ. < 125 Ω
0(4)…20 mA
< 600 Ω
4 - 20 mA
< 600 Ω
30 mW per channel - from input loop
-25 °C…+70 °C
-40 °C…+85 °C
< 0.1 % of measurement range
< 0.01 % /K
100 Hz
55 mW per channel - from output loop
-25 °C…+70 °C
-40 °C…+85 °C
< 0.1 % of measurement range
< 0.01 % /K
100 Hz
2.5 kV
300 V
2
II
2.5 kV
300 V
2
II
ACT20M-CI-CO-ILP-S
4-wire
cULus
61010-1,+
mA
In
–
2, DNV,
active GL
mm
mm2
4
cFMus
3
5
PLC
Div.2, ATEX zone
+ 2, IECEx Zone
6
I
2
–
Out
mA
passive
7
114.3 x 6.1 x 112.5
2.5 / 0.5 / 2.5 1
I
ACT20M-CI-CO-OLP-S
4
5
2-wire
PLC
cULus
61010-1,+ cFMus
Div.2, ATEX zone
+ 2, IECEx Zone
mA
mA
In
Out
2, DNV,
– 3
passiveGL
active
6 –
I
2
114.3 x 6.1 x 112.5
1
2.5 / 0.5 / 2.5
8
ACT20M-2CI-2CO-ILP-S
4-wire
mA
active
In 1
4-wire
mA
active
In 2
+
–
+
–
4
3
2
I
6
7
I
1
I
8
ACT20M-2CI-2CO-OLP-S
5
I
7
I
8
+
–
+
–
Out 1
Out 2
PLC
mA
passive
2-wire
mA
passive
In 1
PLC
mA
passive
2-wire
mA
passive
In 2
+
–
+
–
4
3
2
5
I
I
7
I
1
6
I
8
+
–
+
–
Out 1
PLC
mA
active
Out 2
PLC
mA
active
Ordering data
Single-channel version
Double-channel version
Type
ACT20M CI-CO-ILP-S
ACT20M 2CI-2CO-ILP-S
Qty.
1
1
Part No.
1176070000
1176080000
Type
ACT20M- CI-CO-OLP-S
ACT20M-2CI-2CO-OLP-S
Qty.
1
1
Part No.
1176040000
1176050000
Marker
Type
MF 5/7.5 MC NEUTRAL
Qty.
Part No.
1877680000
Type
MF 5/7.5 MC NEUTRAL
Qty.
Part No.
1877680000
Accessories
5
ACT20M Signal Isolation and Conversion
DC isolator
ACT20M-CI-CO-S
• Isolating DC signals
• Optional power supply via the
DIN-rail-bus
• 3 way isolation
I IN
4
5
3
I OUT
6
2
7
1
82
83
8
Supply
Supply
Technical data
Input
Input current
Load resistance, current input
Output
Output current
Load resistance, current
General data
Supply voltage
Power consumption
0(4)…20 mA
< 75 Ω
0(4)…20 mA
< 600 Ω
2.5 kV
300 V
2
II
cULus 61010-1, cFMus Div.2, ATEX zone 2, IECEx Zone
2, DNV, GL
mm
mm2
114.3 x 6.1 x 112.5 mm
2.5 / 0.5 / 2.5 mm²
Note
Ordering data
Type
ACT20M-CI-CO-S
Qty.
1
Part No.
1175980000
Type
MF 5/7.5 MC NEUTRAL
Qty.
Part No.
1877680000
Note
Accessories
Marker
Note
6
In
+
–
4
3
5
6
I
I
2
24 V DC ± 30 %
0.4 W (24 V supply / Passive input / 20 mA input &
output / 100 Ω load)
-25 °C…+70 °C
-40 °C…+85 °C
< 0.05 % of measurement range
< 0.01 % span/K
100 Hz
Ambient temperature (operational)
Storage temperature
Accuracy
Temperature coefficient
Cut-off-frequency
Insulation coordination
Insulation voltage
Rated voltage
Pollution degree
Overvoltage category
Approvals
Dimensions
Length x width x height
Clamping range (nominal / min. / max.)
ACT20M-CI-CO-S
4-wire
mA
active
DIN-rail bus, refer to accessories page
1
Power
7
8
+
–
+
–
Out 1
PLC
mA
passive
Power
24 V
ACT20M Signal Isolation and Conversion
Temperature transmitter
ACT20M-RTCI-CO-OLP-S
ACT20M-RTI-CO-EOLP-S
• Choice of isolating or non-isolating
converters for J or K thermocouples
and RTDs.
• Hundreds of min/max range
combinations
• Configuration via DIP switches
• Power supplied from the output loop
• 2-way isolation (OLP-S model only)
• Output is linear with temperature
+
PT 100
TC
+
Optional
external –
CJC
4
5
3
6
I
8 V DC...35 V DC
PLC
PT 100
2
1
4
5
3
6
I
8 V DC...35 V DC
PLC
2
1
Technical data
Input
Sensor
Input measurement range
Temperature input range
Output
Output current
Load Resistance
Wire break detection
General data
Configuration
Supply voltage
Power consumption
Accuracy
Temperature coefficient
Galvanic isolation
Step response time
Ambient temperature (operational)
Insulation coordination
Insulation voltage
Rated voltage
Pollution severity
Surge voltage category
Approvals
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
mm²
mm
PT100 / 2-/3-/4-wire, Thermocouple acc. to IEC 584,
type: J, Thermocouple acc. to IEC 584, type: K
PT100 -200…+850 °C, Thermocouple type J -100…
+1200 °C, Thermocouple type K -200…+1370 °C
(internal or external CJC)
Selectable by DIP Switch
PT100 / 2-/3-/4-wire
4...20 mA, 20…4 mA
<600 Ω
3.5 mA ⁄ 23 mA ⁄ none Selectable by DIP Switch
4...20 mA, 20…4 mA
<600 Ω
3.5 mA ⁄ 23 mA ⁄ none Selectable by DIP Switch
DIP switch
8...35 V DC Loop powered
ca. 1 W
absolute accuracy: < ±0.05 % of the measurement
range, RTD (PT100) Basic accuracy: < ±0.1 °C of the
measurement range, TC (J,K) Basic accuracy: < ±0.5
°C of the measurement range
RTD (PT100) ≤ 0.01 % of the measurement range ⁄ °C
or 0.02 °C ⁄ °C‘, TC (J,K) 0.1 °C ⁄ °C
2-way isolator
≤ 30 ms / ≤ 300 ms Selectable by DIP Switch
-25...+70 °C
DIP switch
8...35 V DC Loop powered
ca. 1 W
absolute accuracy: < ±0.1 % of the measurement
range, Basic accuracy: < ±0.2 °C of the measurement
range
2.5 kVeff
300 Veff
N/A
2
II
2
II
cULus; FMEX; IECEXKEM; KEMAATEX;
DETNORVER; GL
cULus; FMEX; IECEXKEM; KEMAATEX;
DETNORVER; GL
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
PT100 -200…+850 °C
Selectable by DIP Switch
RTD (PT100) ≤ 0.01 % of the measurement range ⁄ °C
or 0.02 °C ⁄ °C
Without isolation
≤ 30 ms / ≤ 300 ms Selectable by DIP Switch
-25...+70 °C
Note
Ordering data
Type
ACT20M-RTCI-CO-OLP-S
Qty.
1
Part No.
1435590000
Type
ACT20M-RTI-CO-EOLP-S
Qty.
1
Part No.
1435610000
Note
7
ACT20M Signal Isolation and Conversion
Temperature transmitter
ACT20M-RTI-AO-S
ACT20M-RTI-AO-E-S
• Choice of isolating or non-isolating
converters for RTDs.
• Hundreds of min/max range
combinations
• Optional Power Rail accessory
simplifies jumpering and saves
wiring time.
• Configuration via DIP switches
• 3-way isolation (AO-S model only)
PT 100
4
5
3
6
2
7
1
82 83
8
I, V
PLC
PT 100
Supply
4
5
3
6
2
7
1
8
I, V
OUT 1
Supply
Supply
Technical data
Input
Sensor
Input measurement range
Temperature input range
Output
Output current
Output voltage
load impedance current
load impedance voltage
Wire break detection
General data
Configuration
Supply voltage
Power consumption
Accuracy
Galvanic isolation
Temperature coefficient
Step response time
Ambient temperature (operational)
Insulation coordination
Insulation voltage
PT100 / 2-/3-/4-wire
PT100 -200…+850 °C
Selectable by DIP Switch
PT100 / 2-/3-/4-wire
PT100 -200…+850 °C
Selectable by DIP Switch
0...20 mA, 4...20 mA Selectable by DIP Switch
0(1)...5 V, 0(2)...10 V Selectable by DIP Switch
≤ 600 Ω
≥ 10 kΩ
3.5 mA ⁄ 23 mA ⁄ none Selectable by DIP Switch
0...20 mA, 4...20 mA Selectable by DIP Switch
0(1)...5 V, 0(2)...10 V Selectable by DIP Switch
≤ 600 Ω
≥ 10 kΩ
3.5 mA ⁄ 23 mA ⁄ none Selectable by DIP Switch
DIP switch
24 V DC ± 30 %
1W
absolute accuracy: < ±0.05 % of the measurement
range, Basic accuracy: < ±0.1 % of the measurement
range
3-way isolator
≤0.01 % of the measurement range °C or 0.02 °C ⁄ °C
≤ 30 ms / ≤ 300 ms Selectable by DIP Switch
-25...+70 °C
DIP switch
24 V DC ± 30 %
1W
absolute accuracy: < ±0.1 % of the measurement
range
2.5 kVeff
N/A
N/A
Without isolation
≤0.01 % of the measurement range °C or 0.02 °C ⁄ °C
≤ 30 ms / ≤ 300 ms Selectable by DIP Switch
-25...+70 °C
Rated voltage
300 Veff
Pollution severity
Surge voltage category
Approvals
2
II
2
II
cULus; FMEX; IECEXKEM; KEMAATEX;
DETNORVER; GL
cULus; FMEX; IECEXKEM; KEMAATEX;
DETNORVER; GL
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
mm²
mm
Note
Ordering data
Type
ACT20M-RTI-AO-S
Note
8
Qty.
1
Part No.
1375510000
Type
ACT20M-RTI-AO-E-S
Qty.
1
Part No.
1375520000
ACT20M Signal Isolation and Conversion
Temperature transmitter
ACT20M-TCI-AO-S
ACT20M-TCI-AO-E-S
• Choice of isolating or non-isolating
converters for J or K thermocouples
• Hundreds of min/max range
combinations
• Optional Power Rail accessory
simplifies jumpering and saves
wiring time.
• Configuration via DIP switches
• 3-way isolation (AO-S model only)
+
TC
+
Optional
external –
CJC
4
5
3
6
2
7
1
82 83
8
I, V
+
PLC
TC
+
Supply
Optional
external –
CJC
4
5
3
6
2
7
1
8
I, V
OUT
Supply
Supply
Technical data
Input
Sensor
Input measurement range
Temperature input range
Output
Output current
Output voltage
load impedance current
load impedance voltage
Wire break detection
General data
Configuration
Supply voltage
Power consumption
Accuracy
Galvanic isolation
Temperature coefficient
Step response time
Ambient temperature (operational)
Insulation coordination
Insulation voltage
Rated voltage
Pollution severity
Surge voltage category
Approvals
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
mm²
mm
Thermocouple (Type J, K)
Thermocouple type J -100…+1200 °C, Thermocouple
type K -200…+1370 °C (internal or external CJC)
Selectable by DIP Switch
Thermocouple (Type J, K)
Thermocouple type J -100…+1200 °C, Thermocouple
type K -200…+1370 °C (internal or external CJC)
Selectable by DIP Switch
0...20 mA, 4...20 mA Selectable by DIP Switch
0(1)...5 V, 0(2)...10 V Selectable by DIP Switch
≤ 600 Ω
≥ 10 kΩ
3.5 mA ⁄ 23 mA ⁄ none Selectable by DIP Switch
0...20 mA, 4...20 mA Selectable by DIP Switch
0(1)...5 V, 0(2)...10 V Selectable by DIP Switch
≤ 600 Ω
≥ 10 kΩ
3.5 mA ⁄ 23 mA ⁄ none Selectable by DIP Switch
DIP switch
24 V DC ± 30 %
ca. 1 W
absolute accuracy: < ±0.05 % of the measurement
range, TC (J,K) Basic accuracy: < ±0.5 °C of the
measurement range
3-way isolator
< 0.1 % / °C
≤ 30 ms / ≤ 300 ms Selectable by DIP Switch
-25...+70 °C
DIP switch
24 V DC ± 30 %
ca. 1 W
absolute accuracy: < ±0.1 % of the measurement
range, Basic accuracy: < ±1 °C
2.5 kVeff
300 Veff
2
II
N/A
N/A
2
II
cULus; FMEX; IECEXKEM; KEMAATEX;
DETNORVER; GL
cULus; FMEX; IECEXKEM; KEMAATEX;
DETNORVER; GL
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
Without isolation
≤ 0.01 % / °C
≤ 30 ms / ≤ 300 ms Selectable by DIP Switch
-25...+70 °C
Note
Ordering data
Type
ACT20M-TCI-AO-S
Qty.
1
Part No.
1375480000
Type
ACT20M-TCI-AO-E-S
Qty.
1
Part No.
1375500000
Note
9
ACT20M Signal Isolation and Conversion
Bipolar converters
ACT20M-BAI-AO-S
ACT20M-BAI-2AO-S
• For use with center-zero sensors,
e.g. actuator position control, or
bi-directional flow monitoring.
• DIP switches simplify configuration
• Conversion choices: bipolar in/unipolar
out, or bipolar in/2x unipolar out.
• Optional Power Rail accessory simplifies
jumpering and saves wiring time.
± I, ± V
IN
4
5
3
82 83
I, V
OUT 1
± I, ± V
IN
4
5
6
3
6
7
2
8
OUT 2
Supply
1
I, V
Supply
7
82 83
8
I, V
OUT 1
Supply
Supply
Technical data
Input
Input current
Input voltage
Input resistance, voltage
Input resistance, current inputs
Output
Cut-off frequency (-3 dB)
load impedance voltage
Number of outputs
load impedance current
Output voltage, note
Output current
General data
Accuracy
Configuration
Galvanic isolation
Mounting rail
Power consumption
Power consumption, max.
Step response time
Supply voltage
Temperature coefficient
Type of connection
Insulation coordination
EMC standards
Galvanic isolation
Insulation voltage
Pollution severity
Rated voltage
Standards
Surge voltage category
Approvals
Approvals
ROHS
Dimensions
Depth x width x height (mm)
-10 mA…0…+10 mA, -20 mA…0…+20 mA
-5 V…0…+5 V, -10 V…0…+10 V
Selectable by DIP Switch
≥ 1 MΩ
50 Ω at 20 mA
-10 mA…0…+10 mA, -20 mA…0…+20 mA
-5 V…0…+5 V, -10 V…0…+10 V
Selectable by DIP Switch
≥ 1MΩ
50 Ω at 20 mA
≥ 100 Hz, 10 Hz Selectable by DIP Switch
≥ 10 kΩ
1
≤ 600 Ω
0(2)...10 V, 0(1)...5 V Selectable by DIP Switch
0...20 mA, 4...20 mA Selectable by DIP Switch
≥ 100 Hz, 10 Hz Selectable by DIP Switch
≥ 10 kΩ
2
2 x 300 Ω
0(2)...10 V, 0(1)...5 V Selectable by DIP Switch
0...20 mA, 4...20 mA Selectable by DIP Switch
< 0.05 % of measuring range
DIP switch
3-way isolator;
TS 35
Typ. 400 mW
0.8 W
≤ 7 ms, ≤ 100 ms, Selectable by DIP Switch
24 V DC ± 30 %
< 0.01% of span/°C (TU)
Screw connection
< 0.05 % of measuring range
DIP switch
4-way isolator;
TS 35
Typ. 400 mW
0.8 W
≤ 7 ms, ≤ 100 ms, Selectable by DIP Switch
24 V DC ± 30 %
< 0.01% of span/°C (TU)
Screw connection
EN 61326-1
3-way isolator;
2.5 kVeff
EN 61326-1
4-way isolator;
2.5 kVeff
2
300 Veff
2
300 Veff
DIN EN 61010-1, DIN EN 60079
II
DIN EN 61010-1, DIN EN 60079
II
cULus, DNV, FM, IECEx, Ex Conform
cULus, DNV, FM, IECEx, Ex Conform
114.3 x 6.1 x 112.5
114.3 x 6.1 x 112.5
Note
Ordering data
Note
10
Type
ACT20M-BAI-AO-S
Qty.
1
Part No.
1375450000
Type
ACT20M-BAI-2AO-S
Qty.
1
Part No.
1375470000
ACT20M Signal Isolation and Conversion
Rail bus accessories
CH20M BUS-PROFIL TS35x7.5/1000
CH20M BUS-PROFIL TS35x15/1000
CH20M BUS 4.50/05 AU/1000
• Support section for TS35 x 7.5
• Length: 250, 500 or 750 mm
• Support section for TS35 x 15
• Length: 250, 500 or 750 mm
• Bus PCB for use on TS35 x 7.5 and TS 35 x 15
• Length: 250, 500 or 750 mm
• Five conductor paths, gold plated
• Electrical rating: 63 V AC, 5 A/conductor path
Support section for bus PCB
Ordering data
Type
CH20M BUS-PROFIL
TS35x7.5/250
CH20M BUS-PROFIL
TS35x7.5/500
CH20M BUS-PROFIL
TS35x7.5/750
Qty.
Part No.
10 1248150000
10 1248160000
5 1248170000
Support section for bus PCB
Ordering data
Type
CH20M BUS-PROFIL
TS35x15/250
CH20M BUS-PROFIL
TS35x15/500
CH20M BUS-PROFIL
TS35x15/750
Qty.
Part No.
5
1248180000
5
1248190000
5
1248210000
Bus PCB
Ordering data
Type
CH20M BUS 4.50/
05 AU/250
CH20M BUS 4.50/
05 AU/500
CH20M BUS 4.50/
05 AU/750
Qty.
Part No.
10
1248220000
10
1248230000
5
1248240000
CH20M BUS-ADP TS35/1000
CH20M BUS-AP LI TS35x7.5 & 15
CH20M BUS-AP RE TS35x7.5 & 15
• Cover plate for rail bus
• Length: 250, 500 or 750 mm
• End plate for rail bus
• Fits on TS35 x 7.5 and TS 35 x 15
• Left
• End plate for rail bus
• Fits on TS35 x 7.5 and TS 35 x 15
• Right
Cover plate
Ordering data
Type
Qty.
End plate
Part No.
CH20M BUS-ADP TS35/250
10 1248250000
CH20M BUS-ADP TS35/500
10 1248260000
CH20M BUS-ADP TS35/750
5 1248270000
Ordering data
Type
CH20M BUS-AP LI TS35x7.5
& 15
Ordering data
Qty.
Part No.
50
1193160000
SET CH20M BUS 250MM TS 35X15
SET CH20M BUS 250MM TS 35X7.5
• S
ET consists of one each of
• S
ET consists of one each of
Set
CH20M BUS 4.50/05 AU/250
CH20M BUS-ADP TS 35/250
CH20M BUS-ADP TS 35/250
CH20M BUS-AP LI TS 35X7.5 & 15
CH20M BUS-AP LI TS 35X7.5 & 15
CH20M BUS-AP RE TS 35X7.5 & 15
CH20M BUS-AP RE TS 35X7.5 & 15
CH20M BUS-PROFIL TS 35X15/250
CH20M BUS-PROFIL TS 35X7.5/250
Type
Qty.
SET CH20M BUS 250MM TS
1
35X15
Part No.
1335150000
Type
CH20M BUS-AP RE
TS35x7.5 & 15
Qty.
Part No.
50
1193170000
Set
CH20M BUS 4.50/05 AU/250
Ordering data
End plate
Ordering data
Type
Qty.
SET CH20M BUS 250MM TS
1
35X7.5
Part No.
1335140000
11
ACT20M Signal Isolation and Conversion
Output-current loop-powered
• Galvanic isolation
• Very low power consumption
• Input range selected via DIP switch
• No calibration necessary
OLP
UL Class I, Div. 2
U/I
I
Technical data
Input
Input voltage
Input resistance, voltage/current
Input current
Rated current
Output
Output current
Output signal limit
Load impedance, voltage/current
Cut-off frequency (-3 dB)
General data
Configuration
Supply voltage
Ambient temperature
Default setting
Accuracy
Temperature coefficient
Step response time
Approvals
Insulation coordination
Standards
EMC standards
Rated voltage
Impulse withstand voltage
Insulation voltage
Setting options/switch position
0...5V: 210 kΩ; 0...10V: 430 kΩ / 51 Ω
0(4)...20 mA
40 mA
4...20 mA (current loop)
Approx. 31 mA
/ RL = (UB-12 V) / 20 mA z.B. 600 Ω at 24 V
10 Hz/ 100 Hz switchable
DIP switch
min. 12 V DC/ max. 30 V DC
0 °C...+55 °C
0...20mA, 10 Hz
0.2% of measuring range final value
≤ 150 ppm/K
< 10 Hz: 80 ms; 100 Hz: 50 ms
CE; cULus
n
0 … 20 mA
◼
4 … 20 mA
◼
0…5V
0 … 10 V
n
Transmission frequency
10 Hz
n
100 Hz
n
◼
n
mm²
mm
4
n
n
n
n
n
◼
◼
n
◼
n
n
n
n
◼
n
n
n
24V DC
24 V DC
230 V AC
1
3
WAVE ANALOGUE
OLP
8543720000/8543730000
Sensor
Part No.
8543720000
~
7
8
9
4 ... 20mA
0...10V
Ordering data
Screw connection
n
230 V AC
2
Qty.
1
SW 1
3
= on
= off
~
2.5 / 0.5 / 2.5
92.4 / 17.5 / 112.4
Type
WAS5 OLP
2
Example of application
III
2
≥ 5.5 mm
Dimensions
Clamping range (nominal / min. / max.)
Length x width x height
Note
12
1
DIN EN 50178, DIN EN 61000-4-2
EN 55011, EN 61000-6
300 V
4 kV
4 kVeff / 5 s
Surge voltage category
Pollution severity
Clearance & creepage distances
Note
Input
RL
SPS
ACT20M Signal Isolation and Conversion
Thermal converter type:
K,J,T,E,N,R,S,B
PRO Thermo
Select of
thermocoupler
SW1
Typ
1
2
3
UL Class I, Div. 2
• 3-way isolation
• Internal cold-junction compensation
• Power supply can be cross-connected
using plug-in jumpers
• Suitable for insulated and uninsulated
thermocouples
• W AVETOOL software helps with
configuration, download at
www.weidmuller.com
K
J
T
E
N
R
S
B
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
U/I
J
Selection of
temperature span
SW2
Span 1 2 3 4 5
VC
Technical data
Input
Sensor
Temperature input range
Output
Output voltage / Output current
Load impedance, voltage/current
Offset current / Offset voltage
Line resistance in measuring circuit
Wire break detection
Fine adjustment
Status indicator
Thermo element (IEC 584) type: K,J,T,E,N,R,S,B
-200...+1820 °C
0...10 V / 0(4)...20 mA
≥ 1 kΩ / ≤ 600 Ω
max. 100 µA / max. 0.05 V
50 Ω
LED flashing (output value: > 20 mA, >10 V)
± 5% (switchable)
Module active: LED on/ wire breakage: LED flashing/
Error: LED off
General data
Configuration
Supply voltage
Power consumption
Step response time
Current-carrying capacity of cross-connect.
Ambient temperature
Storage temperature
Default setting
DIP switch
24 V DC ± 25 %
800...850...950 mW at IOUT = 20 mA
without filter: max. 1.4 s; with filter: max. 7.5 s
≤2A
0 °C...+55 °C
-20 °C...+85 °C
Type K; 0...1000°C; 4...20mA; filter: off; man.
calibration: off
CE; cULusEX; GL
Approvals
Insulation coordination
Standards
EMC standards
Rated voltage
Impulse withstand voltage
Insulation voltage
DIN EN 50178, DIN EN 61000-4-2
EN 55011, EN 61000-6
300
4 kV
2 kVeff / 5 s
Surge voltage category
Pollution severity
Clearance & creepage distances
mm²
mm
2.5 / 0.5 / 2.5
92.4 / 17.5 / 112.4
Ordering data
Screw connection
Type
WAS5 PRO Thermo
Qty.
1
100 °C
150 °C
200 °C
250 °C
300 °C
350 °C
400 °C
450 °C
500 °C
550 °C
600 °C
650 °C
700 °C
750 °C
800 °C
850 °C
900 °C
950 °C
1000 °C
1050 °C
1100 °C
1150 °C
1200 °C
1250 °C
1300 °C
1350 °C
1400 °C
1450 °C
1500 °C
1600 °C
1700 °C
1800 °C
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
Accuracy
III
2
≥ 3 mm
Dimensions
Clamping range (nominal / min. / max.)
Length x width x height
Note
Note
◼
Part No.
8560720000
K -200 °C …-150 °C
-150 °C …1200 °C
1200 °C …1372 °C
J -200 °C …-150 °C
-150 °C …1200 °C
T -200 °C …-150 °C
-150 °C … 400 °C
E -200 °C …-150 °C
-150 °C …1000 °C
N -200 °C …-150 °C
-150 °C …1300 °C
R -50 °C … 200 °C
200 °C …1760 °C
S -50 °C … 200 °C
200 °C …1760 °C
B 50 °C … 250 °C
250 °C … 500 °C
500 °C …1820 °C
Selection of minimum
temperature
SW1
ϑ min
1 2 3 4
0 °C
– 10 °C
– 20 °C
– 30 °C
– 40 °C
– 50 °C
– 100 °C
– 150 °C
– 200 °C
+ 50 °C
+ 100 °C
+ 150 °C
+ 200 °C
+ 250 °C
+ 500 °C
Special range
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
◼
Selection of output
Switch 2
Output
6
7
◼
◼
0 ... 10 V
◼
◼
0 ... 20 V
◼
◼
4 ... 20 V
Switching on the
manual fine adjustment
SW 2
man.
adjust.
6
◼
off
◼
on
Switching on the
filter function
SW 2
Filter
off
on
◼
◼
8
◼
◼
= on
= off
± (5K + 0.1 % of set range)
± (3K + 0.1 % of set range)
± (4K + 0.1 % of set range)
± (4K + 0.1 % of set range)
± (3K + 0.1 % of set range)
± (5K + 0.1 % of set range)
± (3K + 0.1 % of set range)
± (4K + 0.1 % of set range)
± (3K + 0.1 % of set range)
± (6K + 0.1 % of set range)
± (3K + 0.1 % of set range)
± (10K + 0.1 % of set range)
± (6K + 0.1 % of set range)
± (10K + 0.1 % of set range)
± (6K + 0.1 % of set range)
± (25K + 0.1 % of set range)
± (10K + 0.1 % of set range)
± (6K + 0.1 % of set range)
13
ACT20M Signal Isolation and Conversion
RTD signal isolator/converter
• Universally adjustable via DIP switch
• 3-way isolation
• Linearisation
• Power supply can be cross-connected
using plug-in jumpers
• W AVETOOL software helps with
configuration,download at
www.weidmuller.com
RTD
J,R
PRO RTD
UL Class I, Div. 2
U/I
VC
Technical data
Input
Sensor
PT100/2-/3-/4-wire, Ni100/2-/3-/4-wire, potentiometer: min. 0–100 Ω, max. 0–100 kΩ,
Resistance: 0–450 Ω
configurable
Temperature input range
Output
Output current / Output voltage
Offset current / Offset voltage
Load impedance, voltage/current
Wire break detection
Fine adjustment
0(4)...20 mA / 0...10 V
max. 100 µA / max. 0.05 V
≥ 1 kΩ / ≤ 600 Ω
LED flashing (output value: > 20 mA, >10 V)
≥ ± 5 %, Version 1 and later: ≥ 12.5 % /
potentiometer: 12.5%...25%
Module active: LED on/ wire breakage: LED flashing/
Error: LED off
Status indicator
General data
Configuration
Supply voltage
Power consumption
Step response time
DIP switch, Potentiometer
24 V DC ± 25 %
830...880...980mW at IOUT = 20 mA
fast/slow: 2-/3-/4-conductor: 1.2 s/2.2 s;
potentiometer: 0.5 s/1.1 s
0 °C...+55 °C
CE; cULus; GL
Ambient temperature
Approvals
Insulation coordination
Standards
EMC standards
Rated voltage
Impulse withstand voltage
Insulation voltage
DIN EN 50178, DIN EN 61000-4-2
EN 55011, EN 61000-6
300 V
4 kV
2 kVeff / 5 s
Surge voltage category
Pollution severity
Clearance & creepage distances
Dimensions
Clamping range (nominal / min. / max.)
Length x width x height
Note
III
2
≥ 3 mm
mm²
mm
2.5 / 0.5 / 2.5
92.4 / 17.5 / 112.4
Ordering data
Screw connection
Note
14
Type
WAS5 PRO RTD
Qty.
1
Part No.
8560700000
ACT20M Signal Isolation and Conversion
PRO RTD
Switch position / setting options
Choice of inputs
Switch 1
Input
1
2
3
PT100 2-wire
■
■
■
PT100 3-wire
□
■
■
PT100 4-wire
■
□
■
R
2-wire
□
□
■
NI100 2-wire
■
■
□
NI100 3-wire
□
■
□
NI100 4-wire
■
□
□
Potentiometer
□
□
□
■ = on
□ = off
Choice of outputs
Switch 2
Output
6
7
0...10 V
■
□
0...5 V
■
■
0...20 mA
□
□
4...20 mA
□
■
Choice of step
response time
Step response time
slow
fast
ϑmin
0 °C
-10 °C
-20 °C
-25 °C
-30 °C
-40 °C
-50 °C
-60 °C
-70 °C
-80 °C
-90 °C
-100 °C
-150 °C
-200 °C
Choice of minimum input size
Switch 1
Rmin
Potimin
4
5
6
0Ω
0%
■
■
■
10 Ω
10 %
■
■
■
20 Ω
20 %
■
■
□
20 Ω
25 %
■
■
□
30 Ω
30 %
■
□
■
40 Ω
40 %
■
□
■
50 Ω
50 %
■
□
□
60 Ω
60 %
■
□
□
70 Ω
70 %
□
■
■
80 Ω
80 %
□
■
■
90 Ω
□
■
□
100 Ω
□
■
□
150 Ω
□
□
■
200 Ω
□
□
■
Special area
T
40 K
50 K
60 K
70 K
80 K
90 K
100 K
110 K
120 K
125 K
130 K
140 K
150 K
160 K
170 K
180 K
190 K
200 K
250 K
300 K
350 K
400 K
450 K
500 K
550 K
600 K
650 K
700 K
750 K
800 K
850 K
900 K
□
□
□
Choice of measuring range
Switch 2
Poti
R
1 2 3 4
20 Ω
20 %
■ ■ ■ ■
25 Ω
25 %
■ ■ ■ ■
30 Ω
30 %
■ ■ ■ □
35 Ω
35 %
■ ■ ■ □
40 Ω
40 %
■ ■ □ ■
45 Ω
45 %
■ ■ □ ■
50 Ω
50 %
■ ■ □ □
55 Ω
55 %
■ ■ □ □
60 Ω
60 %
■ □ ■ ■
62,5 Ω 62,5 %
■ □ ■ ■
65 Ω
65 %
■ □ ■ □
70 Ω
70 %
■ □ ■ □
75 Ω
75 %
■ □ □ ■
80 Ω
80 %
■ □ □ ■
85 Ω
85 %
■ □ □ □
90 Ω
90 %
■ □ □ □
95 Ω
95 %
□ ■ ■ ■
100 Ω 100 %
□ ■ ■ ■
125 Ω
--□ ■ ■ □
150 Ω
--□ ■ ■ □
175 Ω
--□ ■ □ ■
200 Ω
--□ ■ □ ■
225 Ω
--□ ■ □ □
250 Ω
--□ ■ □ □
275 Ω
--□ □ ■ ■
300 Ω
--□ □ ■ ■
325 Ω
--□ □ ■ □
350 Ω
--□ □ ■ □
375 Ω
--□ □ □ ■
400 Ω
--□ □ □ ■
425 Ω
--□ □ □ □
450 Ω
--□ □ □ □
7
■
□
■
□
■
□
■
□
■
□
■
□
■
□
■
5
■
□
■
□
■
□
■
□
■
□
■
□
■
□
■
□
■
□
■
□
■
□
■
□
■
□
■
□
■
□
■
□
Switch on the manual fine
adjustments
S. 1
Man. adjustment
8
off
□
on
■
S. 2
8
■
□
Accuracy, slow/fast step response time
PT 100,Ni 100: 0,3 % from measuring range 0,8 %
from measuring range < 100 K / 0,3 K / 0,8 K
Potentiometer: 0.2 % from end value / 0.3 %
Resistance: 0.2 % from end value / 0.3 %
Temperature coefficient
Measuring range ≥ 200 K
100 K ≤ Measuring range < 200 K
40 K ≤ Measuring range < 100 K
≤ 200 ppm / °C
≤ 250 ppm / °C
≤ 400 ppm / °C
Adjustment example for zero and span
Temperature adjustment:
Output
4…20 mA
DIP switch
-10 °C…+110 °C
Span
75…110 °C
Range
120 °C
Adjustment range
± 12.5 %
Zero
–25° C
–10° C
95° C
110° C
125° C
–5° C
Span
5° C
110° C
125° C
140° C
Wavetool adjustment tool
This service tool enables quick and
straightforward configuration of the
WAVEANALOG PRO.
Internet download:
http://www.weidmuller.com
15
ACT20M Signal Isolation and Conversion
ACT20 power feed module
ACT20M-FEED-IN-PRO-S
ACT20-FEED-IN-BASIC-S
• Distributes the voltage supply on the
busbar
• Compatible with Weidmuller‘s CH20
rail bus
• Optional backup supply connection
• Approved for installation in Ex Zone 2
/Div. 2
• Monitors the supply voltage
• Alarm alerts via the status relay
Alarm
Power supply, 0 V 51
44 NC
Power supply, +24 V 52
Power supply, +24 V
43 Status relay, N.C.
Backup, +24 V 53
42 Status relay, shared
Backup, 0 V 54
41 Status relay, N.O.
NC
0V
NC
+24 V
81
NC
82
Status
0V
83
+24 V
NC
84
NC
85
Power supply, 0 V
Technical data
Input
Power supply
Max. input current
Backup power supply
Trigger level for the power supply
Output, power supply
Output voltage
Output power
Output current
Output, status relay in safe zone
Max. voltage
Max. current
Max. AC power
General data
Efficiency degree
Ambient temperature
Storage temperature
Power consumption
Protection degree
Weight
Humidity
Approvals
Dimensions
Clamping range (nominal / min. / max.)
Length x width x height
21.6...26.4 V DC
4A
21.6...26.4 V DC
Fault < 21 V DC
16.8...31.2 V DC
2.5A
Input voltage -0.5 V DC @ 4 A
max. 96 W
max. 4 A
= U input
= P input
= I input
250 AC / 30 V DC
2 A AC / 2 A DC
500 VA / 60 W
mm
mm2
> 97.9 %
-20...+60 °C
-20...+85 °C
<2W
IP20
140 g
< 95 %, no condensation
cULus, cFMus, ATEX, IECEx Zone 2, DNV, GOST
Screw connection
2.5 / 0.5 / 2.5
119.2 / 22.5 / 113.6
100 %
-25...+70 °C
-40...+85 °C
<2W
IP20
70 g
< 95 %, no condensation
cULus, ATEX, IECEx Zone 2, GL, DNV, cFMus, GOST
Screw connection
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
Type
ACT20-Feed-In-PRO-S
Type
ACT20-FEED-IN-BASIC-S
Note
Ordering data
Qty.
1
Part No.
8965500000
Qty.
1
Part No.
12824900000
Note
16
Subject to technical changes • 03/14 • 2.15M • LIT1126