IN-SITU ZIRCONIA OXYGEN ANALYZER < ZIRCOMAT-C > DATA SHEET This oxygen analyzer is used to continuously measure oxygen concentration in combustion exhaust gas of industrial boilers or furnaces, and is ideally suited for combustion monitoring and control. The detector (ZFK) used with the analyzer is directly inserted into the objects measured, eliminating the need for a sampling device and provides quick response. The converter (ZRY) features 3 measuring ranges, one touch calibration and NEMA4 housing. Comparing to the current converter (ZRM) , this ZRY is recognized as economical type with simple functions. ZFK, ZRY General-use detector FEATURES 1. Sampling device is unnecessary Gas sampling devices such as a gas aspirator, a dehumidifier, etc. are unnecessary because of use of directinsertion type detector. 2. High speed response The adoption of a flow guide tube utilizing the flow of the measured gas assures quick response (less than 7sec). 3. Dust-tight and water-proof housing Aluminum die casting housing of converter satisfies NEMA4 and IP65 standard. 4. 3-measuring ranges and one touch calibration The converter has 0-5, 10, 25 vol% 3 ranges easily changed by pin connection and zero and span are simply calibrated by key operation. SPECIFICATIONS General Measuring object: Oxygen contained in noncombustible gas Measuring principle: Direct-insertion zirconia system Measuring range: 0 to 5, 10 or 25 vol% O2 (Changed by internal set pin) Repeatability: Within ± 1.0% of full scale Linearity: ± 2% of full scale Response time: Within 7sec for 90% response (from calibration gas inlet) Power supply: 100, 115, 220 or 230V AC, 50/60Hz Power consumption: (approx.) 15 + 50VA (at steady state) 15 + 200VA (at start) Warmup time: Approx. 15min Converter Oxygen detector (ZFK2, 5) Measuring detector: For general-use: ZFK2 For corrosive gas: ZFK5 Measured gas temperature: Flow guide tube system; –20 to +600°C Measured gas pressure: –3 to +3kPa Flow guide tube: Flange; JIS5K 65A FF (JIS5K-80AFF for high particulate gas) Insertion length; 0.3, 0.5, 0.75, 1m (0.8m for high particulate gas) Ambient temperature: –20 to +60°C for cable section 125°C or less at detector flange surface with power applied Structure: Dust/rain-proof structure(IEC IP55 equivalent) Filter: Alumina(filtering accuracy 50µm) and quartz paper Main materials of gas-contacting parts: General-use detector(ZFK 2); Zirconia, SUS316, platinum, SUS304 Anticorrosive detector(ZFK 5); Zirconia, tita-nium, platinum, SUS316 Flow guide tube; SUS304 or SUS316 EDSX3-119b Date Mer. 6, 2007 ZFK, ZRY Calibration gas inlet: Brass joint for φ1/4 inch tube. Reference air inlet (option): Rc1/8 or NPT1/8 Detector mounting: Horizontal plane ± 45°, ambient surrounding air should be clean. Outer dimensions: (L x max. dia.) 210mm x 100mm (detector) Mass (approx.) {weight}: Detector; 1.6kg Flow guide tube (general-use, 1m); 5kg Finish color: Silver and SUS metallic color Oxygen converter (ZRY) Measuring range: 0-5, 10, 25 vol% O2 Changeable by internal set pin. Repeatability: ± 1.0% of full scale Lineality: ± 2.0% of full scale Indication: Oxygen concentration; 3-digit LED Oxygen concentration output signal: 4 to 20mA DC (allowable load resistance: 500 Ω or less) Isolated output, linear Fault contact output: 250V AC, 2A rating (close contact or open contact for fault should be specified when you place an order.) Self-diagnoses: Fault of sensor temperature, zero calibration error, span calibration error Calibration method: Manual calibration with key operation Calibration gas: • Recommended calibration gas concentration Zero gas; 1.0 to 2.0% O2 Span gas; 20.6 to 21.0% O2 (oxygen concentration in the air) Ambient temperature: –10 to +50°C Ambient humidity: 90% RH or less Power supply: 90 to 220 or 230 V AC, 50/60Hz Construction: Dust-tight, waterproof construction, NEMA4 (corresponding to IP65 of IEC) Material: Aluminum die casting Outer dimensions (H x W x D): 220 X 230 X 95mm Mass {weight}: Approx. 4.5kg (excluding cable and detector) Finish color: Munsell 6PB 3.5/10.5 (blue): cover, silver; case Mounting method: Mounted flush on panel The product conforms to the requirements of the Electromagnetic compatibility Directive 89/336/EEC as detailed within the technical construction file number TZ737041. The applicable standards used to demonstrate compliance are : EN 55011 : 1992 CLASSA Conducted and Radiated emissions EN 50082-1 : 1992 Radiated immunity, ESD and FBT ZFK, ZRY 2 Exclusine cable (ZRZP) Cable: Cable conduit: Length: 4-cores sealed wire (O2 signal and Rthemo couple signal) and 2-cores cable (power) Flexible type Refer to code symbols SCOPE OF DELIVERY Detector: Detector main unit x 1, Viton O ring x 1, mounting screw (M5mm x 12) x 6, thermal sticker x 1, flow guide tube (as specified) x 1, ceramic filter x 1, cover (as specified) x 1, reference air inlet (as specified) x 1 Converter: Converter main unit x 1 Accessories (AC250V 500mA T fuse x 1, AC250V 3.15A T fuse x 1) Items to be prepared separately: (1) Standard gas for calibration Type ZBMMNSK4-01 (2) Reduction valve for standard gas (type ZBD61003) (3) Flowmeter Type; ZBD52203, 0.2 to 2L/min (for calibrating gas) CAUTIONS • If combustible gas (CO, H2 etc.) exists in the measured gas, error will occur due to burning at the sensor section. The inclusion of corrosive gas (Si vapor, alkaline metal, P, Pb etc.) will shorten the life of the sensor. • When the measured gas temperature is high (+300°C or higher), the flange should be separated from the furnace wall in order to bring the detector flange surface temperature below the specified value +125°C). The flow guide should be attached in the direction in which the gas flow to the detector decreases. • When dust more than 1g/Nm 3 is included in the gas, manual blow down is necessary. DEVICE CONFIGURATION The device to be combined differ according to the conditions of the gas to be measured. Please select the devices to be combined with reference to the following table. Measured gas Application Temperature Gas Flow General-use 600°C or (boiler) less Device configuration Protection Note cover DUST 5 to 20m/s Less than 0.2g/m3 [nor] — Less than 10g/m3 [nor] no Detector type Converter Ejector type type Fuel; gas, oil ZFK R 4- 5 ZRY — Fuel: coal ZFK R 4- 6 D 8 ZRY — ZFK R 4- 6 E 8 ZRY — with manual blow down Anti-corrosive use Less than 25g/m3 [nor] yes Included high moisture with manual blow down (incinerator) Note (1) Dust volume is approximate value. (2) Instrument quality air or bottled air is available as reference air by selecting detector with reference air inlet, when oxygen concentration in air around sensor changes. CODE SYMBOLS (Converter) (Detector) 4 5 6 7 8 ZFK R 2 9 10 11 12 13 1 2 3 4 5 6 7 8 Description 4 Z RY 1 Application General use. For corrosive gas (refuse incinerator) 2 5 Flow guide tube flange application None SUS304 general use SUS304 general use SUS304 general use SUS304 general use SUS316 for corrosive gas SUS316 for corrosive gas SUS316 for corrosive gas SUS316 for corrosive gas SUS316 for high particulate SUS316 for high particulate with cover 0Y0 5A3 5A5 5A7 5A1 5B3 5B5 5B7 5B1 6D8 6E8 Y A B 4 5 6 7 8 4 300mm 500mm 750mm 1000mm 300mm 500mm 750mm 1000mm 800mm 800mm Reference air inlet Non Rc1/8 NPT1/8 9 10 11 12 13 Description Application General use. For corrosive gas (refuse in cinerator) 2 5 Cal. gas inlet For φ1/4 inch tube 2 1 3 5 Power supply 100/115VAC 50/60Hz 200/220VAC 50/60Hz 230VAC 50/60Hz Mounting method Panel mounting 1 Y E length ( Replacement Detector element) R 2 Power supply 90 to 230V AC 50/60Hz (CE marking approved) 1 Protection cover Without With Y A ZFK B C Power supply 100/115VAC 50/60Hz 200/220VAC 50/60Hz 230VAC 50/60Hz (CE-marking approved) 1 3 5 Description 0 Output signal and fault output 4 to 20mA DC, close contact 4 to 20mA DC, open contact Cal. gas inlet For φ1/4 inch tube 2 9 10 11 12 Y 1 2 - 1 R Instruction manual NO YES (English) (Exclusive-special cable) 1 2 3 4 5 6 7 8 Z R Z PR 9 Description 1 - Connectable devices For ZRY P Types For R thermocouple R Conduit length None None None None None None None None None None None None 6m 10m 15m 20m YA YB YC YD YE YF YG YH YJ YK YL YM AA BB CC DD 0 1 2 Cable length 6m 10m 15m 20m 30m 40m 50m 60m 70m 80m 90m 100m 6m 10m 15m 20m Cable end treatment None One side (detector side) Both sides Note: For connection between detector and converter, the conduit to be used should be rainproof flexible type. 3 ZFK, ZRY CONFIGURATION Flow guide tube system Cover for retaining warmth Flow guide tube Status of fault contact output Detector ZFK2 5 digit of model Power off B C Gas temperature. 600°C max. *3 Ball valve 1 2 3 4 5 Power on and fault open open close open close open 6 Rainproof flexible conduit. 20m max. Bule Red Yellow Black White White Sample gas outlet Power on and normal 4-core cable Converter (ZRY) 2-core cable Thermocouple Zirconia signal signal Gas temperature. 600°C max. 1 2 3 4 Analog output 5 6 Fault contact output 7 8 Sensor heater 9 10 11 12 13 14 Flow guide tube for high particulate Red White Blue Yellow 6mm or 4 inch tube for calibration gas (not supplied) *3 Ball valve Black White DC4 to 20mA AC power supply Cell/thermocouple output Heater power supply Sample gas outlet Gas temperature. 600°C max. Flow guide for high particulate with cover Change valve Reduction valve (ZBD6) Standrad gas for zero point (ZBM) *2 Ref. air Flowmeter (ZBD4) (1 to 1.5L/min) Reduction valve (unnecessary when supply air pressure is 50 to 100kPa *1 Air supply to Detector (0.2 to 0.5L/min) Reduction vale (ZBD6) *1 Standard gas for span point (ZBM) Note 4 *1 Sandard gas or instrumentation air can be used in place of span gas. *2 Instrument quality air or bottled air is available as reference air instead of ambient air, when oxygen concentration in air around sensor changes. *3 Blow down air inlet pressure in 200 to 300kpa. OUTLINE DIAGRAM (Unit:mm) Detector (ZFK2) 80 Proof cover (to order) Approx. 130 67 Approx. 65 45.4 Approx. 118 36 5 26 Filter EXTERNAL CONNECTION DIAGRAM 85 Heater Thermocouple Element output 60 ° A Approx. 25 1 3 2 4 5 6 Black / White/ Red / White/ Yellow / Blue 2-core wire 6- 6 4-core wire Exclusive-special cable Ref. air inlet (to order) NPT1/8 or Rc1/8 Calibration gas inlet for 1/4 inch tube. Exclusive cable gland Flow guide tube 155 Approx. L 12 Approx. 20 130 67 34 Gas inlet 20 ZFK2R 6-M5 detector side Gas outlet Cord 11th Oxygen detector L (m) 3 5 0.3 0.5 MASS 2.7 Approx (kg) 3.3 4-5A3 5 7 1 7 1 Z 0.75 1.0 4.1 4.8 L= (to order) 8–15 MTG. holes 5 ZFK, ZRY Detector (ZFK5) 80 67 Proof cover (to order) Approx. 130 Approx. 65 45.4 Approx. 118 36 5 26 Filter EXTERNAL CONNECTION DIAGRAM Thermocouple Element output 60 ° 85 Heater Approx. 35 1 3 2 4 5 6 Black / White/ Red / White/ Yellow / Blue 2-core wire 4-core wire Exclusive-special cable Ref. air inlet (to order) NPT1/8 or Rc1/8 6- 6 Calibration gas inlet for 1/4 inch tube. Exclusive cable gland Flow guide tube 155 12 Approx. 40 Approx. L 130 3 67 60.5 67 Gas inlet ZFK5R 6-M5 detctor side Gas outlet Cord 11th Oxygen detector L (m) 3 0.3 MASS 3.3 Approx (kg) 6 5 7 0.5 0.75 4.5 6.1 1 Z 1.0 7.6 L= (to order) 8- 15 MTG. holes 4-5B3 5 7 1 14 5 4 - Rc 1/4 with plug int thd. 180 Flow guide tube (for high particulate) Blow down air inlet Select an upper port to avoid the condensation in the piping 8 - 19 MTG. hole 67 29. 5 Flange: JIS 5K80A FF ZFK MTG. position 185 Packing R 4 - 6 D8 Gas outlet 800 50 ZFK 30 Gas flow Tube (50A SCH40) 5 14 180 Flow guide tube (for high particulate with cover) 4 - Rc 1/4 with plug int thd. Blow down air inlet 8 - 19 MTG. holes Select an upper port to avoid the condensation in the piping 67 29 .5 Flange: JIS 5K80A FF (175) ZFK MTG. position 50 Packing ZFK R 4 - 6 E8 800 (790) Gas outlet 30 Gas flow Protection tube (65A SCH40) (38) Tube (50A SCH40) 7 ZFK, ZRY Converter (ZRY) Panel flush mounted 2- 312 220 20 φ9 72 3.2 95 14 230 5 φ1 39 CABLE GRAND 5-G1/2 40 40 40 40 CONNECTION DIAGRAM 1 2 + 3 – THERMOCOUPLE + 4 5 6 7 – + – 8 ELEMENT OUTPUT FAULT INPUT SIGNAL CONTACT OUTPUT 9 10 11 12 13 14 L HEATER POWER FOR SENSOR N POWER SUPPLY Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan