IN-SITU DATA SHEET ZIRCONIA OXYGEN ANALYZER FOR HAZARDOUS LOCATION ZFKE, ZKME This oxygen analyzer is used to continuously measure oxygen concentration in noncombustible exhaust gas of industrial boilers or furnaces, and is ideally suited for combustion management and control. The analyzer system is comprised of the detector and converter coupled together as a complete system. Detector setting configuration includes the flow guide tube and detector sensor. The flow guide tube is inserted directly into the gas and directs gas to the sensor for measurement. The converter (ZKME) is comprised of the signal processor, input/output and communications, display and system controls. The converter is equipped with advanced functionality such as performing the sensor diagnostics and sensor recovery function, so the detector can be used within long term stability. Detector (ZFKE) FEATURES 1. Gas sampling device is unnecessary For quick response, insert the detector directly into the staek. Gas sampling functions such as a gas aspirator and a dehumidifier are not required. 2. Easy maintenance The sensor equipped with the detector, has unit construction, it is easy to replace. By separating the detector and the flow guide tube, filter replacement is easy. 3. More reliable than sensor diagnosis, sensor recoverable function Depending on the components in the measurement gas, the characteristics of the sensor might deteriorate. The equipment includes sensor recovery function electronically, checking the deterioration status of the sensor depletion. Therefore, it has high reliability and long-lasting stability. 4. Safe and secure System detects thermocouple break for heater control on the sensor side. Safety functions of isolating power supply to the detector or isoralting power via external contact input are also. 5. Easy operation The operation and setting for the converter can be performed interactively, and available as English, Japanese or Chinese for language display. Converter (ZKME) SPECIFICATIONS General Specifications Measuring object: Oxygen in noncombustible gas Measuring method: Directly insert type zirconia system Measuring range: 0 to 2 ··· 0 to 50 vol% O2 2 ranges available in 1 vol% O2 steps Repeatability: Within ±0.5%FS Linearity: Within ±2%FS Response time: Within 4 to 7 sec, for 90% (from calibration gas inlet) approx. 10 min Warmup time: Analog output: 4 to 20mA DC (allowable load resistance less than 500Ω) or 0 to 1V DC (output resistance more than 100Ω) Power supply: Rated voltage; 100 to 120V AC (operating voltage 90 to 132V AC) 200 to 240V AC (operating voltage 190 to 264V AC) Rated frequency; 50/60Hz Power consumption: Maximum 240VA (Detector: approx. 200VA, Converter: approx. 40VA) Normal 70VA (Detector: approx. 50VA, Converter: approx. 20VA EDS3-139b Date Apr. 1, 2011 ZFKE, ZKME Detector Specifications (ZFKE) Measured gas temperature: Flow guide tube system; −10 to +600ºC (for general-use, corrosive gas) Measured gas pressure: −3 to +3kPa (−306 to +306mmH2O) Flow guide tube: With or without blow-down nozzle Flange; JIS5K 65A FF (JIS5K-80AFF for high particulate gas) Insertion length; 0.3, 0.5, 0.75, 1m Other: See. Code Symbols Ejector (general-use): Probe for vacumming up measured gas to detector (option) Operating temperature: −10 to +60ºC for Primary detecting element 125ºC or less at detector flange surface with power applied Storage temperature: Sensing element: −20 to +70ºC Structure: Dust/rain-proof structure(IEC IP66 equivalent) Flame proof: See Table 1. SUS316 (filtering accuracy 60µm) Filter: Main materials of gas-contacting parts: Detector; Zirconia, SUS316, platinum Flow guide tube; SUS316 Calibration gas inlet: ø6mm tube join or ø1/4-inch tube join (as specified) Reference gas inlet (option): ø6mm tube join or ø1/4-inch tube join (as specified) Detector mounting: Horizontal plane ±45º, ambient surrounding air should be clean. Outer dimensions: (L × max. dia.) 215mm × 164mm (detector) Mass (approx.) {weight}: Detector; 3.0kg Flow guide tube (for corrosive gas, 1m); 6kg Finish color: Case: Silver and SUS metallic color Cover: Blue Ejector air inlet flow rate: 5 to 10 L/min Calibration gas flow: 1.5 to 2 L/min Blowdown air inlet pressure: 200 to 300kPa {2 to 3 kgf/cm2} Table 1 Detector TIIS (pending) NEPSI 2 Exd IIB T4 EExd IIC T5 Ex II2G Converter specification (ZKME) Concentration value indication: Digital indication in 4 digits Contact output signal: (1) Contact specification; 6 points, 1a 250V AC/3A or 30V DC/3A (2) Contact function; • Under maintenance • Under blowdown Note3) • Span calibrating gas • Zero calibration gas • Instrument anomalies Note1) • Alarm Note2) Note1) The following Instrument errors (1) Thermocouples break (2) Sensor break (3) Temperature fault (4) Calibration fault (5) Zero/span adjustment fault (6) Output error turn the contact-ON Note2) Alarm selects just one as mentioned below (1) High (2) Low (3) Upper and Lower (4) High-high (5) Low-low, it turns ON while operating. Note3) Under blow down is available in case of option, and it turns ON while operating. Contact input signal: (1) Contact specification; 3points (the following option) ON; 0V (10mA or less), OFF; 5V (2) Contact function; • External hold • Calculation reset • Heater OFF • Blow down (option) • Inhibition of calibration • Calibration start • Range change Calibration method: (a) Manual calibration with key operation (b)Auto. calibration (option) Calibration cycle; 00 day 00 hour to 99 days 23 hours (c) All calibration Calibration gas: • Range settings Zero gas; 0.010 to 25.00% O2 Span gas: 0.010 to 50.00% O2 • Recommended calibration gas concentration Zero gas; 0.25 to 2.0% O2 Span gas; 20.6 to 21.0% O2 (oxygen concentration in the air) Blowdown: A function for blowing out with compressed air dust that has deposited in the flow guide tube. Blowdown can (option) be performed for a predetermined time and at predetermined intervals. Blowdown cycle;00 hour 00 minute to 99 hours 59 minutes Blowdown time; 0 minute 00 second to 0 minutes 999 seconds Output signal hold: Output signal is held during calibration, processing recoverable sensor,processing diagnosis of sensor, warm-up, PID auto tuning, under set up maintenance mode " available" and blowdown. The hold function can also be released. Valve and flow Selects zero or span gas during manual meter (option): zero or span calibration. Communication function: RS232C (MODBUS) standard specification RS485 (MODBUS) (option) Combustion efficiency display (option): When you select this display, "rich mode display" will be an simultaneous display. This function calculates and displays combustion efficiency from oxygen concentration and measured gas temperature. Thermocouple (R) is required for temperature measurement. Operating temperature: −20 to +55ºC Operating humidity: 95% RH or less, non condensing Storage temperature: −30 to +70ºC Storage humidity: 95% RH or less, non condensing Construction: Dust-proof, rainproof construction (corresponding to IP65) Explosion proof: See Table 2 Aluminum case Material: Outer dimensions (H x W x D): 470 X 326 X 211mm (IP65) Mass {weight}: IP65:Approx.22kg (excluding cable and detector) Finish color: Case: Silver Cover: blue Mounting method:Mounted flush on panel Electrical Safety: Overvoltage category ; II power supply input ; I relay interfaces (IEC1010-1) External overcurrent protective device ; 10A Equipment interfaces are safety separated (SELV) ZFKE, ZKME Table 2 Converter TIIS (pending) NEPSI Exd IIB T6 EExd IIC T6 Ex II2G 3 ZFKE, ZKME CODE SYMBOLS (Detector) 1 2 3 4 5 6 7 8 Z F K ER (Converter) 9 10 11 12 13 5 - Y 14 15 16 17 - 1 2 3 4 5 6 7 8 Description 1 Cal. gas inlet Non (G3/8 female screw) For φ6mm tube For φ1/4 inch tube Ejector for φ6mm tube Ejector for φ1/4 inch tube Y 1 2 A B Power supply 100 to 120VAC 50/60Hz 200 to 240VAC 50/60Hz 1 3 Z K ME 9 10 11 12 13 1 1 - 1 B E 1 2 Y 1 2 3 4 14 Description - Output signal 4 to 20mA DC 0 to 1V DC Communication function RS-232C RS-485 Optional Functions None Combustion efficiency display function Note1) Blowdown Auto calibration Combustion efficiency indication + Blowdown Note1) Combustion efficiency indication + Auto calibration Note1) Blowdown + Auto calibration Combustion efficiency indication + Blowdown + Auto calibration Note1) Instruction manual language Japanese English Chinese Mounting Option None (Mounting on panel surface) With valve With valve + flowmeter Specification name plate Standard Number of Cable Gland 3 4 5 6 7 Ex Standard NEPSI TIIS (pending) Flow guide tube None <Flange size> JIS 5K 65A 7 5 JIS 5K 80A 8 6 JIS 5K100A 9 7 JIS 10K 65A A JIS 10K 80A B JIS 10K 100A C J ANSI 150LB 2B E D C ANSI 150LB 3B E ANSI 150LB 4B F Y DIN DN50 PN10 G 1 DIN DN80 PN10 H 2 <Application / meterial> For corrosive gas / SUS316 F 1 With blow-down nozzle / SUS316 G For high particular / SUS316 H 3 For high particular with cover / SUS316 J 4 For high particular / SUS310S K 5 For high particular with cover / SUS310S L 6 For high particular / titanium M 7 For high particular with cover / titanium N <Length> N 3 300mm T 5 500mm 7 Note1) When you select this display, rich mode 750mm will be a simultaneous display. 1 1000mm Reference gas inlet Y Non (G1/8 female screw) A for φ6mm tube (Exclusive-special cable) B For φ1/4 inch tube 1 2 3 4 5 6 7 8 9 Filter Description Z R Z E R 1 Standard 5 For high particular 7 Connectable devices Instruction manual language E For ZKME J Japanese Types E English R For R thermocouple C Chinese Cable length Specification name plate YA 6m 1 Standard YB 10m Ex. Standard YC 15m N NEPSI YD 20m T TIIS (pending) YE 30m YF 40m YG 50m YH 60m YJ 70m (Replacement Detector element) YK 80m YL 90m Power supply Code symbols YM 100m 0Y 0 4 100 to 120V AC ZFK8YY15-0Y0YY-0YY 200 to 240V AC ZFK8YY35-0Y0YY-0YY 0 1 2 Cable end treatment None One side (detector side) Both sides SCOPE OF DELIVERY CAUTIONS Detector: Detector main unit × 1, Viton Packing × 1, thermo seal × 1, mounting screw (M5mm × 25) × 6, flow guide tube (as specified) × 1, Wrench × 1, Instruction manual × 1 Converter: Converter main unit × 1, mounting screw (M12 × 50) × 4, Cock (option) × 1, flowmeter (option) × 1, Accessories (AC250V 500mA T fuse × 2, AC250V 2.5A T fuse × 2), Wrench × 1, Instruction manual × 1 Ejector: With detector main unit (option) Items to be prepared separately: (1)Standard gas for calibration Type ZBM NSH4-01 (up to 5% O2 range) Type ZBM NSJ4-01 (over 5% O2 range) (2)Reduction valve for standard gas (type ZBD61003) (3)Flowmeter Type; ZBD42203, 0.2 to 2L/min (for calibrating gas) (unnecessary when the code 11th of ZKME is 2) Type; ZBD42403, 1 to 10L/min (for ejector) (4)Opner Type; ZZP*TK7N9329P2 (for detector; ZFKE) Type; ZZP*TK7N9329P1 (for converter; ZKME) • If combustible gas (CO, H2 etc.) exists in the measured gas, error will occur due to burning at the sensor section. The inclusion of corrosive gas (Si vapor, alkaline metal, P, Pb etc.) will shorten the life of the sensor. • When the measured gas temperature is high (+300°C or higher), the flange should be separated from the furnace wall in order to bring the detector flange surface temperature below the specified value +125°C). The flow guide should be attached in the direction in which the gas flow to the detector decreases. • When much dust is included in the gas, the flow guide tube should be attached at an inclination so that the flow goes from below to above. And the flow guide should be attached in the direction in which the gas flow to the detector decreases. • In the case of a refuse incinerator, automatic blow down of the flow guide should not be performed (to prevent corrosion of the flow guide tube due to drainage). Blowdown should be performed manually when change in the indication has become very little with the furnace stopped. DEVICE CONFIGURATION The device to be combined differ according to the conditions of the gas to be measured. Select the devices to be combined with reference to the following table. Measured gas Application Temperature Gas Flow General-use 600ºC or (boiler) less For corrosive 600ºC or gas (refuse less Device configuration Note Detector type Fuel; gas, oil ZFKER 5- F Y - Fuel: coal ZFKER 5- G Y - with blow down Included low moisture ZFKER 5- F Y - Less than 10g/Nm3 Included low moisture ZFKER 5- G Y - Less than 25g/Nm3 with blow down Included low moisture DUST 5 to 20m/s Less than 0.2g/Nm3 Less than 10g/Nm3 5 to 20m/s Less than 1g/Nm3 incinerator) with blow down Less than 25g/Nm3 Included high moisture with blow down ZFKER ZFKER H 5- K Y M J 5- L Y N Converter type ZKME ZKME ZKME ZKME ZKME ZKME Note (1) Dust volume is approximate value. (2) Instrument quality air or bottled air is available as reference air by selecting detector with reference air inlet. 5 ZFKE, ZKME CONFIGURATION Flow guide tube system Rc1/4 (upper side blow port should be selected) Blow-down, 200 to 300kPa Reduction valve (unnecessary when supply air pressure is 200 to 300kPa Solenoid valve (not supplied) Supply air 15ASGP tube equivalent (not supplied) Flow guide tube 15ASGP tube equivalent (not supplied) Detector (ZFKE) from (1) Gas temperature. 600ºC max. exhaust 6 Sample gas outlet 1 5 2 3 AC power supply 4 Black Black Red Blue White Yellow Gas temperature. 600ºC max. Flow guide tube for high particulate Converter (ZKME) Sample gas outlet 1 2 + O2 − O2 sensor input *4 Gas temperature. 600ºC max. Flow guide for high particulate with cover 3 4 5 + TC1 − + AO 6 7 8 9 4 to 20mA DC or 0 to 1V DC 12 13 DI1 DI2 DI3 DICOM 15 17 18 19 20 Calibrating gas contact output Maintenance contact output ALARM Contact input Calibrating gas contact output SPAN GAS MAINTE COM 21 22 23 TM-1 14 O2 sensor heater power input ZERO GAS Blow contact output Alarm contact output + TC2 − 16 11 ZV O2 sensor or Fault contact thermocouple output input Analog output Thermocouple for combustion control 10 − 24 25 SV 26 AC power supply PE *3 N AC L 27 28 1 2 TM-2 3 RS232C or RS485 (option) AC power supply φ 6mm or φ 1/4 inch tube for calibration gas (not supplied) Joint *2 Ref. gas Solenoid valve (not supplied) AC power supply Reduction valve (ZBD6) Standrad gas for zero point (ZBM) Flowmeter (ZBD4) (1.5 to 2.0L/min) Reduction valve (unnecessary when supply air pressure is 50 to 100kPa) (1) to Detector *1 Air supply φ 6mm or φ 1/4 inch tube for calibration gas (1.5 to 2.0L/min) (not supplied) Solenoid valve (not supplied) Reduction vale (ZBD6) Span point *1 Standard gas for span point (ZBM) Note: *1 *2 *3 *4 6 Standard gas or instrumentation air can be used in place of span gas. Instrument quality air or bottled air is available as reference gas instead of ambient air. Protective earth. Connect the shield of a exclusive cable with the ground terminal in the converter. Flow guide tube system (with valve) Rc1/4 (upper side blow port should be selected) Blow-down, 200 to 300kPa Reduction valve (unnecessary when supply air pressure is 200 to 300kPa Solenoid valve (not supplied) Supply air 15ASGP tube equivalent (not supplied) Flow guide tube 15ASGP tube equivalent (not supplied) Detector (ZFKE) from (1) Gas temperature. 600ºC max. exhaust 6 Sample gas outlet 1 5 2 3 AC power supply 4 Black Black Red Blue White Yellow Gas temperature. 600ºC max. Flow guide tube for high particulate Converter (ZKME) Sample gas outlet 1 2 + O2 − O2 sensor input *4 Gas temperature. 600ºC max. Flow guide for high particulate with cover 3 4 + TC1 − 5 + AO 6 7 8 9 4 to 20mA DC or 0 to 1V DC 12 13 DI1 DI2 DI3 DICOM 15 17 18 19 20 Calibrating gas contact output Maintenance contact output ALARM Contact input Calibrating gas contact output SPAN GAS MAINTE COM 21 22 23 TM-1 14 O2 sensor heater power input ZERO GAS Blow contact output Alarm contact output + TC2 − 16 11 ZV O2 sensor or Fault contact thermocouple output input Analog output Thermocouple for combustion control 10 − 24 25 SV 26 AC power supply PE *3 N AC L 27 28 1 2 TM-2 3 RS232C or RS485 (option) AC power supply φ 6mm or φ 1/4 inch tube for calibration gas (not supplied) Flowmeter (option) Valve (option) MEASURE Reduction valve (ZBD6) ZERO SPAN *2 Ref. gas Flowmeter (ZBD4) (1.5 to 2.0L/min) Standrad gas for zero point (ZBM) (1) to Detector *1 Air supply φ 6mm or φ 1/4 inch tube for calibration gas (1.5 to 2.0L/min) (not supplied) Note: *1 *2 *3 *4 Standard gas or instrumentation air can be used in place of span gas. Instrument quality air or bottled air is available as reference gas instead of ambient air. Protective earth. Connect the shield of a exclusive cable with the ground terminal in the converter. Reduction vale (ZBD6) Span point *1 Standard gas for span point (ZBM) 7 ZFKE, ZKME Flow guide tube system (with ejector) Rc1/4 (upper side blow port should be selected) Blow-down, 200 to 300kPa Reduction valve (unnecessary when supply air pressure is 200 to 300kPa Solenoid valve (not supplied) Supply air 15ASGP tube equivalent (not supplied) Flow guide tube 15ASGP tube equivalent (not supplied) Detector (ZFKE) from (1) Gas temperature. 600ºC max. exhaust Calibrating gas Flowmeter (ZBD4) (5 to 10L/min) exhaust 6 Sample gas outlet 1 5 2 3 from (2) AC power supply 4 Black Black Red Blue White Yellow Gas temperature. 600ºC max. Flow guide tube for high particulate Converter (ZKME) Sample gas outlet 1 2 + O2 − O2 sensor input *4 Gas temperature. 600ºC max. Flow guide for high particulate with cover 3 4 5 + + TC1 − AO 6 7 8 9 4 to 20mA DC or 0 to 1V DC Blow contact output Alarm contact output ALARM Contact input + TC2 − DI1 DI2 DI3 DICOM 15 17 18 19 16 11 12 13 ZV O2 sensor or Fault contact thermocouple output input Analog output Thermocouple for combustion control 10 − 20 Maintenance contact output O2 sensor heater power input ZERO GAS Calibrating gas contact output Calibrating gas contact output SPAN GAS MAINTE COM 21 22 23 TM-1 14 24 25 SV 26 AC power supply PE N AC L 27 28 1 2 TM-2 3 RS232C or RS485 (option) Joint φ 6mm or φ 1/4 inch tube for calibration gas (not supplied) *2 Ref. gas Flowmeter (ZBD4) (1.5 to 2.0L/min) Solenoid valve (not supplied) AC power supply AC power supply Standrad gas for zero point (ZBM) Reduction valve (unnecessary when supply air pressure is 50 to 100kPa) (2) to ejector (1) to Detector φ 6mm or φ 1/4 inch tube for calibration gas (0.2 to 0.5L/min) (not supplied) Reduction valve (ZBD6) *1 Air supply Joint Solenoid valve (not supplied) Reduction vale (ZBD6) Span point *1 Standard gas for span point (ZBM) Note: *1 *2 *3 *4 8 Standard gas or instrumentation air can be used in place of span gas. Instrument quality air or bottled air is available as reference gas instead of ambient air. Protective earth. Connect the shield of a exclusive cable with the ground terminal in the converter. *3 Flow guide tube system (with ejector+valve) Rc1/4 (upper side blow port should be selected) Blow-down, 200 to 300kPa Reduction valve (unnecessary when supply air pressure is 200 to 300kPa Solenoid valve (not supplied) Supply air 15ASGP tube equivalent (not supplied) Flow guide tube 15ASGP tube equivalent (not supplied) Detector (ZFKE) from (1) Gas temperature. 600ºC max. exhaust Calibrating gas Flowmeter (ZBD4) (5 to 10L/min) exhaust 6 Sample gas outlet 1 5 2 3 from (2) AC power supply 4 Black Black Red Blue White Yellow Gas temperature. 600ºC max. Flow guide tube for high particulate Converter (ZKME) Sample gas outlet 1 2 + O2 − O2 sensor input *4 Gas temperature. 600ºC max. Flow guide for high particulate with cover 3 4 + TC1 − 5 + 6 AO 7 8 4 to 20mA DC or 0 to 1V DC 11 12 13 DI1 DI2 DI3 DICOM 15 17 18 19 20 Calibrating gas contact output Maintenance contact output ALARM Contact input Calibrating gas contact output SPAN GAS MAINTE COM 21 22 23 TM-1 14 O2 sensor heater power input ZERO GAS Blow contact output Alarm contact output + TC2 − 16 10 ZV O2 sensor or Fault contact thermocouple output input Analog output Thermocouple for combustion control 9 − 24 25 SV 26 AC power supply PE *3 N AC L 27 28 1 2 TM-2 3 RS232C or RS485 (option) Flowmeter (option) φ 6mm or φ 1/4 inch tube for calibration gas (not supplied) *2 Ref. gas Valve (option) MEASURE AC power supply Reduction valve (ZBD6) ZERO Flowmeter (ZBD4) (1.5 to 2.0L/min) SPAN Standrad gas for zero point (ZBM) (1) to Detector *1 Air supply φ 6mm or φ 1/4 inch tube for calibration gas (0.2 to 0.5L/min) (not supplied) Reduction vale (ZBD6) Span point *1 Standard gas for span point (ZBM) Note: *1 *2 *3 *4 Standard gas or instrumentation air can be used in place of span gas. Instrument quality air or bottled air is available as reference gas instead of ambient air. Protective earth. Connect the shield of a exclusive cable with the ground terminal in the converter. 9 ZFKE, ZKME OUTLINE DIAGRAM (Unit:mm) Y Detector (ZFKER 1 ) 2 Ref. gas inlet (to order) SUS316, for φ 6mm tube (the 13th digit is “A”) or 1/4 inch tube Approx. 152 (the 13th digit is “B”) Approx. 140 Approx. 215 77 17.5 Approx. φ 100 Lock screw M6 View A External ground terminal M4 Explotion-proof name plate Exclusive Cable gland (For power supply) Approx. 32 Filter Approx. 162 View B Approx. 126 P Calibration gas inlet (To order) SUS316, for φ 6mm tube (the 6th digit is “1”) Or 1/4 inch tube (the 6th digit is “2”) (Not provided if the 6th digit is “Y”) Exclusive Cable gland (For signal) Approx. 242 Approx. 180 7 φ6 6 φ 6- (13th digt code A, B) (14th digt code 7) VIEW A VIEW B EXTERNAL CONNECTION DIAGRAM Heater Thermocouple Element output 1 3 2 4 5 Black Black Red White Yellow 2-core wire 4-core wire Exclusive-special cable VIEW FROM P Sensor unit (ZFK8YY) (132.7) 3.5 20 (φ 17.5) (88.4) 4-φ 3.5(Mount for detector) S- H 2 T- 4 45° TK4J4664R0 3 made in japan 40 5 10 T+ S+ H 6 1 45° φ 35 6 Blue Detector (ZFKER A ) B Ref. gas inlet (to order) SUS316, for φ 6mm tube (the 13th digit is “A”) Or 1/4inch tube (the 13th digit is “B”) Approx. 215 Approx. 155 17.5 77 Approx. 140 Approx. 100 Lock screw M6 P View B Approx. 126 External ground terminal M4 Approx. 47 Approx. 57 Approx. 185 Filter View A Exclusive Cable gland (For power supply) Calibration Air out Calibration gas inlet SUS316, for φ 6mm tube (the 6th digit is “A.”) 1/4 inch tube (the 6th digit is “B.”) Air in Approx. 37 Approx. 21 Approx. 78 Exclusive Cable gland (For signal) Ejector gas inlet SUS316, for φ 6mm tube (the 6th digit is “A.”) 1/4 inch tube (the 6th digit is “B.”) Ejector gas outlet SUS316, for φ 6mm tube (the 6th digit is “A.”) 1/4 inch tube (the 6th digit is “B.”) Approx. 242 Approx. 180 (13th digt code A, B) 7 φ6 (14th digt code 7) VIEW A 6 VIEW B φ 6- Explotion-proof name plate EXTERNAL CONNECTION DIAGRAM Heater Thermocouple Element output 1 3 2 4 5 Black Black Red White Yellow 2-core wire 6 Blue 4-core wire Exclusive-special cable VIEW FROM P Flow guide tube (with blow-down nozzle) (ZFKE: 10th digit code. G) Approx. L D C 67 Approx. 20 f 60.5 t Gas inlet 6-M5 detector side Gas outlet ZFKE MTG. position Code 11th 3 L (m) 0.3 Mass 3.0 Approx.(kg) 5 7 1 0.5 0.75 1.0 3.8 4.8 5.7 Z L= (to order) Blow down N– h air inlet MTG. holes 4-Rc1/4 with plug int.thd. Flange size JIS 5K 65A JIS 5K 80A JIS 5K 100A JIS 10K 65A JIS 10K 80A JIS 10K 100A ANSI 150LB 2B ANSI 150LB 3B ANSI 150LB 4B DIN DN50 PN10 DIN DN80 PN10 Code 9th 7 8 9 A B C D E F G H D C t f 155 180 200 175 185 210 150 190 230 165 200 130 145 165 140 150 175 120.7 152.4 190.5 125 160 14 14 16 18 18 18 17.5 22.3 22.3 18 20 2 2 2 2 2 2 2 2 2 0 0 110 121 141 116 126 151 92.1 127 157.2 0 0 N h 4 4 8 4 8 8 4 4 8 4 4 15 19 19 19 19 19 19.1 19.1 19.1 18 18 11 ZFKE, ZKME Blow down air inlet Select an upper port to avoid the condensation in the piping C 4 - Rc 1/4 with plug int thd. D Flow guide tube (for high particulate) (ZFKE: 10th dight code. H, K, M) N- h MTG. hole 67 38. 5 ZFKE MTG. position t Packing 188 Code 11th 3 0.3 50 Mass 4.5 Approx.(kg) 5 1 7 0.5 0.75 1.0 5.6 8.3 7.0 Z L= (to order) L Gas outlet L (m) 30 Gas flow Flange size JIS 5K 65A JIS 5K 80A JIS 5K 100A JIS 10K 65A JIS 10K 80A JIS 10K 100A ANSI 150LB 2B ANSI 150LB 3B ANSI 150LB 4B DIN DN50 PN10 DIN DN80 PN10 Code 9th 7 8 9 A B C D E F G H D C t f 155 180 200 175 185 210 150 190 230 165 200 130 145 165 140 150 175 120.7 152.4 190.5 125 160 14 14 16 18 18 18 17.5 22.3 22.3 18 20 2 2 2 2 2 2 2 2 2 0 0 110 121 141 116 126 151 92.1 127 157.2 0 0 N h 4 4 8 4 8 8 4 4 8 4 4 15 19 19 19 19 19 19.1 19.1 19.1 18 18 Blow down air inlet Select an upper port to avoid the condensation in the piping C 4 - Rc 1/4 with plug int thd. D Flow guide tube (for high particulate with cover) (ZFKE: 10th dight code. J, L, N) N- h MTG. hole 67 38. 5 ZFKE MTG. position (178) t L (L-10) Gas outlet 50 Packing Gas flow Production tube 12 (38) 30 Code 11th 3 L (m) 0.3 Mass 7.1 Approx.(kg) 5 7 1 0.5 0.75 1.0 Z L= 9.0 11.4 13.6 (to order) Flow guide tube (ZFKE: 10th dight code. F) f D C 67 Approx. 40 Approx. L Gas inlet 60.5 t 6-M5 detector side Gas outlet N- h MTG. holes ZFKE MTG. position 3 Code 11th 5 7 0.3 0.5 0.75 MASS 3.3 Approx.(kg) 4.5 6.1 7.6 L (m) Z 1 1.0 Flange size L= (to order) JIS 5K 65A JIS 5K 80A JIS 5K 100A JIS 10K 65A JIS 10K 80A JIS 10K 100A ANSI 150LB 2B ANSI 150LB 3B ANSI 150LB 4B DIN DN50 PN10 DIN DN80 PN10 Code 9th 7 8 9 A B C D E F G H D C t f 155 180 200 175 185 210 150 190 230 165 200 130 145 165 140 150 175 120.7 152.4 190.5 125 160 14 14 16 18 18 18 17.5 22.3 22.3 18 20 2 2 2 2 2 2 2 2 2 0 0 110 121 141 116 126 151 92.1 127 157.2 0 0 N h 4 4 8 4 8 8 4 4 8 4 4 15 19 19 19 19 19 19.1 19.1 19.1 18 18 Coverter (ZKME) Mounting hole 4-ø14 Lock screw M6 326 211 286 17 ZKM Oxygen Analyzer Oxygen Ana MODE ESC ENTER POWER 注 意 POWER 変換器へ供給する電源電圧は、接続される 検出器の電源電圧に合わせてください。 362 HEATER FUSE T 2.5A CAUTION Power supply must be selected the same voltage of detector. 442 402 FUSE T 0.5A ON POWER OFF +O 2 - +TC1 - +AO - FAULT 1 2 15 3 16 4 17 5 18 6 19 7 20 +TC2 - DI1 DI2 DI3 DI- COM ZV HEATER BLOW 9 10 11 12 13 14 21 22 23 24 25 26 27 28 MAINALARM AC COM SV N L TENANCE 8 CAUTIO WHEN POWER OPEN THIS EXPLOSIVEOFF AND COVER, KEEP ATMOSPHERE OUT N Fuji Electr ic Fuji Electric Co.,Ltd. ESC ENT 68 MODE Fuji Electric Co.,Ltd. Co.,Ltd. Cable gland for flame proof ø9 - ø12 / closeup plug (To order) Ground terminal M4 For communication For contact In/Out For Other 60 60 60 40 60 52 186 60 For sensor signal For sensor power For output For power supply 13 ZFKE, ZKME EXTERNAL TERMINAL (TM1) /M3 Exclusive cable O2 sensor input O2 sensor thermocouple input Analog output 4-20mA DC or 0-1V DC 1 2 3 4 + O2 − + TC1 − 5 + AO 6 Fault contact output 250V AC/3A 30V DC/3A 7 8 9 + 15 FAULT TC2 − DI1 DI2 DI3 DICOM 16 17 18 19 Thermocouple input type R (not supplied) 11 12 BLOW ZERO GAS SPAN GAS 22 Alarm contact output 250V AC/3A 30V DC/3A 23 COM 24 25 Maintenance contact output 250V AC/3A 30V DC/3A Terminal number 2 3 Remarks RS232C TXD RXD GND Standard RS485 TRX+ TRX– GND Option SV 26 Calibrating gas contact output 250V AC/3A 30V DC/3A COMMUNICATION TERMINAL (TM2) /INSERTION TERMINAL 14 14 HEATER MAINTE 21 20 Contact input Short circuit : on (Current 5mA) Open : off (Voltage 5V) 1 13 ZV ALARM Ground terminal M4 COM 10 − or O2 sensor heater power output Blow contact output 250V AC/3A 30V DC/3A N 27 AC L 28 AC Power supply input 100 to120V AC 200 to 240V AC OUTLINE DIAGRAM (Unit:mm) <Option> SELECTOR VALVES + FLOWMETER (IN CASE OF 11TH DIGIT CODE “2” ) 114 102 MEA RE ZERO CALIB. SPAN 6 2-φ 5.5 Mounting hole Zero gas inlet (NPT1/8) 20 ZERO SPAN 293 126 20 20 15 30 83 Span gas inlet (NPT1/8) 65 Calibration gas outlet (NPT1/8) SELECTOR VALVES (IN CASE OF 11TH DIGIT CODE “1” ) 6 2-φ 5.5 Mounting hole ZERO CALIB. SPAN 15 30 Zero gas inlet (NPT1/8) 20 20 65 83 Span gas inlet (NPT1/8) Calibration gas outlet (NPT1/8) 65 114 102 MEA RE 20 ZERO SPAN 101 15 ZFKE, ZKME Caution on Safety *Before using this product, be sure to read its instruction manual in advance. International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice. Printed in Japan