IN-SITU ZIRCONIA OXYGEN ANALYZER <ZIRCOMAT-P> DATA SHEET This oxygen analyzer is used to continuously measure oxygen concentration in combustible exhaust gas of industrial boilers or furnaces, and is ideally suited for combustion monitoring and control. The detector (ZFK) used with the analyzer is directly inserted into the objects measured, eliminating the need for a sampling device and provides quick response. The converter (ZRM) features automatic calibration and blowdown functions. The adoption of liquid crystal display facilitates operation and setting in interactive mode. Besides the general-use type detector, corrosion resisting type and high temperature type are available for selection according to applications. ZFK, ZRM General-use detector High-temperature detector FEATURES 1. Output range easily set Output range can be easily set in 0.5% increments within the scope of 2 to 50%. When oxygen decreases, incomplete combustion level appears on the display (rich mode; output voltage of oxygen detector), instead of oxygen concentration. 2. Automatic calibration/blowdown function Automatic calibration and manual/auto blowdown functions are provided as standard functions. An external solenoid valve is required. 3. Easily operated in interactive mode Interactive mode is adopted to the liquid crystal display for operation and parameter setting, facilitating use even for beginners. 4. Combustion efficiency display function Combustion efficiency calculated from oxygen concentration and temperature of exhaust gas can be displayed as an optional function, which is useful to improve combustion efficiency. 5. Sampling device is unnecessary Gas sampling devices such as a gas aspirator, a dehumidifier, etc. are unnecessary because of use of directinsertion type detector. The adoption of a flow guide tube utilizing the flow of the measured gas assures quick response (less than 7sec). 6. Selection of detector type according to applications Besides the general-use type detector used under temperatures of less than 600°C, a corrosion-proof detector for measuring incinerator exhaust gas, and a high temperature type detector using heat insulator for the ejector and insertion tube, capable of measuring temperatures up to 1590°C, are available for selection according to applications. Converter SPECIFICATIONS General Measuring object: Oxygen contained in noncombustible gas Measuring principle: Direct-insertion zirconia system Measuring range: 0 to 2 ……50 vol% O2 freely settable (in 0.5% steps) Repeatability: Within ± 0.5% of max. output signal Linearity: ± 2% of full scale Response time: Within 7sec for 90% response (from calibration gas inlet) Power supply: 100, 115, 220 or 230V AC, 50/60Hz Power consumption: (approx.) 15 + 50VA (at steady state of general-use detector) 15 + 200VA (at start of general-use detector) Warmup time: Approx. 15min Oxygen detector (ZFK2,5), ejector (ZTA) Measuring detector: For general-use: ZFK2 For corrosive gas: ZFK5 EDSX3-113c Date Nov. 30, 2001 ZFK, ZRM Measured gas temperature: Flow guide tube system; –20 to +600°C (for general-use, corrosive gas) Ejector system; –20 to +1590 °C (for high-temperature gas) –20 to +800°C (for general-use) Measured gas pressure: –3 to +3kPa (–306 to +306mmH2O) Flow guide tube: With or without blow-down nozzle Flange; JIS5K 65A FF (JIS5K-80AFF for high particulate gas) Insertion length; 0.3, 0.5, 0.75, 1m (0.8m for high particulate gas) Ejector (general-use): Probe for guiding measured gas to detector Flange; JIS10K 65A RF Insertion length; 0.5, 0.75, 1, 1.5m (according to customer's specification) Ambient temperature: –20 to +60°C for cable section –5 to +100°C for ejector section 125°C or less at detector flange surface with power applied Structure: Dust/rain-proof structure(IEC IP55 equivalent) Filter: Alumina(filtering accuracy 50µm) and quartz paper Main materials of gas-contacting parts: General-use detector; Zirconia, SUS316, platinum Anticorrosive detector; Zirconia, titanium, platinum Flow guide tube; SUS304 or SUS316 Ejector (general use);SUS316, SUS304 Ejector; (for high temperature) SiC, SUS316, SUS304 Calibration gas inlet: SUS316 Reference air inlet (option): Rc1/8 or NPT1/8 Detector mounting: Horizontal plane ± 45°, ambient surrounding air should be clean. Outer dimensions: (L x max. dia.) 210mm x 100mm (detector) Mass (approx.) {weight}: Detector; 1.6kg Ejector; 15kg (insertion length 1m) Flow guide tube (general-use, 1m); 5kg Finish color: Silver and SUS metallic color Ejector air inlet flow rate: 5 to 10r/min Blowdown air inlet pressure: 200 to 300kPa {2 to 3 kgf/cm2} Ejector exhaust gas processing: Within furnace, returned to flue Heater temperature drop alarm output (ejector): Alarm output when below 100 °C Mechanical thermostat N.O. (1a) contact, 200V AC, 2A Oxygen converter (ZRM) Measuring range: 0 to 2 ……50 vol% O2 freely settable (in 0.5% O2 steps) 2 ± 0.5% of full scale ± 1.0% of full scale Oxygen concentration; 3-digit LED Operation/setting display: 16-digit, 2-line LCD Mode display: 3pcs LED Oxygen concentration output signal: 4 to 20mA DC (allowable load resistance: 500 Ω or less) or 0 to 1V (output resistance: 100 Ω or less) Isolated output, linear Contact output signal: (1) Contact specification; 4 points, N.O. (1a), 250V AC, 2A (2) Contact function; • Under maintenance • Under blowdown • Span calibrating gas • Zero calibration gas Following functions freely selected • High limit alarm • Low limit alarm • High/low limit alarm • Fault (abnormal) Contact input signal: Auto. calibration start (auto. calibration starts when contact closes) Calibration disable (calibration disabled when contact closes) Contact specification; isolated, ON at 1kΩ or less Calibration method: (a) Manual calibration with key operation (b) Auto. calibration (standard function) Calibration cycle; 00 day 00 hour to 90 days 60 hours Calibration gas: • Range settings Zero gas; 0.010 to 50.000% O2 Span gas: 8.000 to 23.000% O2 • Recommended calibration gas concentration Zero gas; 0.25 to 2.0% O2 Span gas; 20.6 to 21.0% O2 (oxygen concentration in the air) Blowdown: A function for blowing out with compressed air dust that has deposited in the flow guide tube. Blowdown can be performed for a predetermined time and at predetermined intervals. Blowdown cycle; 00 hour 00 minute to 99 hours 60 minutes Blowdown time; 0 minute 00 second to 9 minutes 60 seconds Output signal hold: Output signal is held during calibration and blowdown. The hold function can also be released. Transmission function (option): RS-485 Transmission distance; Max. 500m total Number of units connected; Max. 8 units Half-duplex bit serial transmission, startstop synchronization. Repeatability: Linearity: Indication: Remark: When connecting via an RS232C interface, a RS232 ↔ RS 485 converter should be used. Combustion efficiency display (option): This function calculates and displays combustion efficiency from oxygen concentration and measured gas temperature. Thermocouple (K or R) is required for temperature measurement. Rich mode display: When the detector output voltage exceeds 200mV (0.0023%O 2 ), the rich mode (fuel rich) is indicated in LCD where the LED showing the detector output voltage flickers. Self-diagnosis function: Provided for detector temperature fault, zero calibration fault, span calibration fault, calibration disable, and detector output fault. Ambient temperature: –10 to +50°C Ambient humidity: 90% RH or less Power supply: 90 to 220 or 230 V AC, 50/60Hz Construction: Dust-proof, rainproof construction (corresponding to IP53 of IEC) Material: Steel Outer dimensions (H x W x D): 220 X 193 X 89mm Mass {weight}: Approx. 3.5kg (excluding cable and detector) Finish color: Munsell 2.5Y8.4/1.2 Mounting method: Mounted flush on panel or on pipe Electrical Safety: Overvoltage category ; II power supply input ; I relay interfaces (IEC1010-1) External overcurrent protective device ; 10A Equipment interfaces are safety separated (SELV) The product conforms to the requirements of the Electromagnetic compatibility Directive 89/336/EEC as detailed within the technical construction file number TZ734575. The applicable standards used to demonstrate compliance are : EN 55011 : 1992 CLASSA Conducted and Radiated emissions EN 50082-1 : 1992 Radiated immunity, ESD and FBT ZFK, ZRM 3 ZFK, ZRM CODE SYMBOLS (Detector) 4 5 6 7 8 ZFK (Ejector) 9 10 11 12 13 1 2 3 4 5 6 7 8 14 Z T A Description 4 Application General use For corrosive gas (refuse incinerator) 2 5 1 2 Power supply 100/115VAC 50/60Hz 200/220VAC 50/60Hz 230VAC 50/60Hz (CE-marking approved) 1 3 5 Flow guide tube flange application None SUS304 general use SUS304 general use SUS304 general use SUS304 general use SUS316 for corrosive gas SUS316 for corrosive gas SUS316 for corrosive gas SUS316 for corrosive gas SUS316 with blow-down nozzle SUS316 with blow-down nozzle SUS316 with blow-down nozzle SUS316 with blow-down nozzle SUS316 for high particulate SUS316 for high particulate SUS316 for high particulate SUS316 for high particulate SUS316 for high particulate with cover SUS316 for high particulate with cover SUS316 for high particulate with cover SUS316 for high particulate with cover Others 0Y0 5A3 5A5 5A7 5A1 5B3 5B5 5B7 5B1 5C3 5C5 5C7 5C1 6D3 6D5 6D7 6D1 6E3 6E5 6E7 6E1 ZZZ length 300mm 500mm 750mm 1000mm 300mm 500mm 750mm 1000mm 300mm 500mm 750mm 1000mm 300mm 500mm 750mm 1000mm 300mm Z 1000mm Non-standard spec. Other non-standard items ( Replacement Detector element) 4 5 6 7 8 9 10 11 12 13 4 0 Y 0 Y Y ZFK Description Application General use (TC516041) For corrosive gas (refer to incinerator) (TC516042) 2 5 Kinds Standard R Cal. gas inlet Polypropylene joint for φ6 tube Brass joint for φ1/4 inch tube 6 7 1 3 5 Power supply 100/115VAC 50/60Hz 200/220VAC 50/60Hz 230VAC 50/60Hz (Converter) 1 2 3 4 5 6 7 8 Z RM1 9 Description 1 1 Output signal 4 to 20mA DC 0 to 1V DC B E Optional functions None Serial communication (RS-485) Combustion efficiency display Transmission function + Combustion efficiency display Y A B C Power supply 90 to 220V AC 50/60Hz 230VAC 50/60Hz (CE marking approved) 1 5 1 2 Mounting method Panel mounting Pipe mounting Note: Specify the detector type. (ZFK 2 or 5, R-type or K-type thermocouple) 750mm Reference air inlet Non Rc1/8 NPT1/8 Y A B Power supply 100V/115V AC 50/60Hz 200V/220V AC 50/60Hz 230VAC 50/60Hz 1 3 5 500mm Protection cover Without With Y A Insertion length [mm] 500 750 1000 1500 B C D E Cal. gas inlet For φ6mm tube For φ1/4 inch tube 1 2 Description 1 Measured gas temperature For high temperatures (+1590°C max.) General-use (+800°C max.) Kinds Standard R 4 1 (Exclusive-special cable) 1 2 3 4 5 6 7 8 Z R ZM 9 Description 1 - Connectable devices For ZRM M Types For R thermocouple R Conduit length None None None None None None None None None None None None 6m 10m 15m 20m YA YB YC YD YE YF YG YH YJ YK YL YM AA BB CC DD 0 1 2 Cable length 6m 10m 15m 20m 30m 40m 50m 60m 70m 80m 90m 100m 6m 10m 15m 20m Cable end treatment None One side (detector side) Both sides Note: For connection between detector and converter, the conduit to be used should be rainproof flexible type. CONFIGURATION Flow guide tube system Rc1/4 (upper side blow port should be selected) Reduction valve (unnecessary when supply air pressure is 200 to 300kPa {2 to 3kgf/cm2} Solenoid valve (not supplied) Blow-down, 200 to 300kPa {2 to 3kgf/cm2} Supply air Rainproof cover 15ASGP tube equivalent (not supplied) or 10/ 8 PTFE pipe or copper pipe Flow guide tube 15ASGP tube equivalent (not supplied) Detector ZFK2 ZFK5 Gas temperature. 600°C max. 1 2 3 4 5 6 Bule Red Yellow Black White White Sample gas outlet Rainproof flexible conduit. 20m max. AC power supply 4-core cable Converter (ZRM) 2-core cable Analog output Gas temperature. 600°C max. 1 2 Auxiliary input Zirconia Thermocouple Maintenance Blow-down signal signal contact contact Heater 3 5 4 6 7 8 9 10 11 12 13 14 Flow guide tube for high particulate Blue Yellow Red White 4 to 20mA DC (0 to 1V) 6mm or 4 inch tube for calibration gas (not supplied) Black White Cell/thermocouple output Heater power supply Sample gas outlet Serial communication Contact input NC 15 16 17 18 19 20 AC power supply Calibrating gas contact 21 22 23 Gas temperature. 600°C max. 24 SG FG N L 25 26 27 28 PE AC power supply Flow guide for high particulate with cover AC power supply RS-485 Joint Solenoid valve (not supplied) Reduction valve (ZBD6) Standrad gas for zero point (ZBM) *2 Ref. air Flowmeter (ZBD4) (1 to 1.5R/min) Reduction valve (unnecessary when supply air pressure is 50 to 100kPa {0.5 to 1kgf/cm2} *1 Air supply to Detector (0.2 to 0.5R/min) Solenoid valve (not supplied) Reduction vale (ZBD6) *1 Standard gas for span point (ZBM) Note *1 Sandard gas or instrumentation air can be used in plase of span gas. *2 Instrument quality air or bottled air is available as reference air instead of ambient air. 5 ZFK, ZRM Ejector system Flowmeter (ZBD) Ejector (ZTA) Reduction valve (unnecessary when supply air pressure is 200 to 300kPa {2 to 3kgf/cm2} ) Ejector (5 to 10R/min) Joint Supply air 1 2 4 5 Gas temperature. 1590°C max. Power supply Copper pipe 6/ 4mm Heater temperature drop Alarm Solenoid valve (not supplied) Copper pipe 10/ 8mm Copper pipe 10/ 6mm Detector (ZFK2) 1 2 3 4 5 6 Bule Rainproof flexible conduit. Red Yellow Black White White 4-core cable AC power supply 2-core cable Converter (ZRM) Analog output 1 2 Auxiliary input Zirconia Thermocouple Maintenance Blow-down signal signal contact contact 3 5 4 6 7 8 9 10 11 12 Blue Yellow Red White 4 to 20mA DC (0 to 1V) Heater 13 14 Black White Cell / thermocouple output Heater power supply Serial communication Contact input 15 18 NC 6mm or 4 inch tube for calibration gas (not supplied) 16 17 19 20 AC power supply Calibrating gas contact 21 22 23 24 SG FG N L 25 26 27 28 PE AC power supply AC power supply RS-485 (1 to 1.5R/min) joint Solenoid valve (not supplied) Reduction vale (ZBD6) Standrad gas for zero point (ZBM) Flowmeter (ZBD4) *2 Reduction valve (unnecessary when supply air pressure is 50 to 100kPa {0.5 to 1kgf/cm2} Ref. air *1 Air supply to Detector (0.2 to 0.5R/min) Solenoid valve (not supplied) Reduction vale (ZBD6) *1 Standard gas for span point (ZBM) Note: 6 *1 Standard gas or instrumentation air can be used in place of span gas. *2 Instrument quality air or bottled air is available as reference air instead of ambient air. SCOPE OF DELIVERY Detector: Detector main unit x 1, Viton O ring x 2, mounting screw (M5mm x 16) x 6, thermal sticker x 1, flow guide tube (as specified) x 1, ceramic filter x 1, rainproof cover (as specified) x 1 Converter: Converter main unit x 1, mounting bracket set, (according to specification) x 1 Accessories (AC250V 500mA T fuse x 2, AC250V 3.15A T fuse x 2) Ejector: Ejector main unit x 1, insertion tube x 1, M16mm nut, and washer x 4, packing x 1 Items to be prepared separately: (1) Standard gas for calibration Type ZBM NSH4-01 (up to 5% O2 range) Type ZBM NSJ4-01 (over 5% O2 range) (2) Reduction valve for standard gas (type ZBD61003) (3) Flowmeter Type; ZBD42203, 0.2 to 2r/min (for calibrating gas) Type; ZBD42403, 1 to 10r/min (for ejector) CAUTIONS • If combustible gas (CO, H2 etc.) exists in the measured gas, error will occur due to burning at the sensor section. The inclusion of corrosive gas (Si vapor, alkaline metal, P, Pb etc.) will shorten the life of the sensor. • When the measured gas temperature is high (+300°C or higher), the flange should be separated from the furnace wall in order to bring the detector flange surface temperature below the specified value +125°C). The flow guide should be attached in the direction in which the gas flow to the detector decreases. • When much dust is included in the gas, the flow guide tube should be attached at an inclination so that the flow goes from below to above. And the flow guide should be attached in the direction in which the gas flow to the detector decreases. • In the case of a refuse incinerator, automatic blow down of the flow guide should not be performed (to prevent corrosion of the flow guide tube due to drainage). Blowdown should be performed manually when change in the indication has become very little with the furnace stopped. DEVICE CONFIGURATION The device to be combined differ according to the conditions of the gas to be measured. Select the devices to be combined with reference to the following table. Measured gas Application Temperature Gas Flow General-use 600°C or (boiler) less DUST Device configuration Protection Note cover 5 to 20m/s Less than 0.2g/mm3 — Less than 10g/Nm3 Detector type Converter Ejector type type Fuel; gas, oil ZFK2R 4- 5 A ZRM — Fuel: coal ZFK2R 4- 5 C ZRM — — Included low moisture ZFK5R 4- 5 B ZRM — — Included low moisture ZFK5R 4- 5 C ZRM — 4- 6 D ZRM — 4- 6 E ZRM — ZFK2R 4-OYO ZRM ZTA2 ZFK2R 4-OYO ZRM ZTA1 — with blow down For corrosive 600°C or gas (refuse less 5 to 20m/s Less than 1g/Nm3 Less than 10g/Nm3 with blow down incinerator) Less than 25g/Nm3 no Included low moisture ZFK5R with blow down Less than 25g/Nm3 yes Included high moisture ZFK5R with blow down General-use 800°C or Less than (boiler) less 1m/s 1590°C or Less than less 1m/s Less than 1g/Nm3 — SUS316 tube with blow down Less than 1g/Nm3 — SIC tube with blow down Note (1) Dust volume is approximate value. (2) Instrument quality air or bottled air is available as reference air by selecting detector with reference air inlet. 7 ZFK, ZRM OUTLINE DIAGRAM (Unit:mm) Detector (ZFK2) 80 Proof cover (to order) Approx. 130 67 Approx. 65 45.4 Approx. 118 36 5 26 Filter EXTERNAL CONNECTION DIAGRAM 85 Heater Thermocouple Element output 60 ° A Approx. 25 1 3 2 4 Black / White/ red / White/ 2-core wire 6- 6 5 6 yellow / blue 4-core wire Exclusive-special cable Ref. air inlet (to order) NPT1/8 or Rc1/8 Calibration gas inlet (to order) SUS316 for 6/ 4 PTEF tube or 1/4 inch tube. Exclusive cable gland Flow guide tube 155 Approx. L 12 Approx. 20 130 67 20 34 Gas inlet Cord 11th 3 5 L (m) 0.3 0.5 MASS 2.7 Approx.(kg) 1 7 ZFK2R 4-5C3 5 7 1 Z 8–15 MTG. holes 0.75 1.0 4.1 3.3 4-5A3 5 7 1 6-M5 detector side Gas outlet Oxygen detector ZFK2R 4.8 L= (to order) Flow guide tube (with blow-down nozzle) 155 Approx. L 18 Approx. 20 130 67 60.5 67 3 Gas inlet 6-M5 detector side Gas outlet Oxygen detector Blow down air inlet Cord 11th 3 L (m) 0.3 Mass 3.0 Approx.(kg) 8 5 7 1 Z 0.5 0.75 1.0 3.8 4.8 5.7 L= (to order) Select an upper port to avoid the condensation in the piping 8–15 MTG. holes 4-Rc1/4 with plug int.thd. Flow guide tube (for high particulate) 14 5 180 4 - Rc 1/4 with plug int thd. Blow down air inlet Select an upper port to avoid the condensation in the piping 8 - 19 MTG. hole 67 29. 5 Flange: JIS 5K80A FF ZFK MTG. position 185 Packing 4-6D3 5 7 1 800 50 ZFK2R Gas outlet 30 Cord 11th 3 L (m) 0.3 Mass 4.5 Approx.(kg) 5 7 1 Z 0.5 0.75 1.0 5.6 7.0 8.3 L= (to order) 1 Z Gas flow Tube (50A SCH40) 5 14 4 - Rc 1/4 with plug int thd. 180 Flow guide tube (for high particulate with cover) Blow down air inlet 8 - 19 MTG. holes Select an upper port to avoid the condensation in the piping 67 29 .5 Flange: JIS 5K80A FF (175) ZFK MTG. position 50 Packing ZFK2R 4-6E3 5 7 1 800 (790) Gas outlet Cord 11th 3 L (m) 0.3 Mass 7.1 Approx.(kg) Gas flow Protection tube (65A SCH40) 30 (38) 5 7 0.5 0.75 1.0 L= 9.0 11.4 13.6 (to order) Tube (50A SCH40) 9 ZFK, ZRM Detector (ZFK5) 80 67 Proof cover (to order) Approx. 130 Approx. 65 45.4 Approx. 118 36 5 26 Filter EXTERNAL CONNECTION DIAGRAM Thermocouple Element output 60 ° Heater Approx. 35 1 3 2 4 Black / White/ red / White/ 2-core wire 5 6 yellow / blue 4-core wire Exclusive-special cable Ref. air inlet (to order) NPT1/8 or Rc1/8 6- 6 Calibration gas inlet (to order) SUS316 for 6/ 4 PTEF tube or 1/4 inch tube. Exclusive cable gland Flow guide tube 155 12 Approx. 40 Approx. L 130 3 67 67 60.5 Gas inlet 4-5B3 5 7 1 ZFK5R 4-5C3 5 7 1 6-M5 detector side Gas outlet Cord 11th 3 L (m) 0.3 Oxygen detector ZFK5R MASS 3.3 Approx.(kg) 5 7 0.5 0.75 4.5 6.1 1 Z 8- 15 MTG. holes 1.0 7.6 L= (to order) Flow guide tube (with blow - down nozzle) 155 18 Approx. 20 Approx. L 130 3 67 60.5 67 Gas inlet 6-M5 detector side Gas outlet Blow down air inlet 8- 15 MTG. holes Oxygen detector Cord 11th 3 L (m) 0.3 MASS 3.3 Approx.(kg) 10 5 7 0.5 0.75 4.2 5.7 1 Z 1.0 7.4 L= (to order) Select an upper port to avoid the condensation 4- Rc 1/4 in the piping with plug int. thd. 14 180 5 Flow guide tube (for high particulate) 4 - Rc 1/4 with plug int thd. Blow down air inlet 8 - 19 MTG. hole Select an upper port to avoid the condensation in the piping 67 29. 5 Flange: JIS 5K80A FF ZFK MTG. position 185 Packing 4-6D3 5 7 1 Gas outlet 800 50 ZFK5R 30 Cord 11th 3 L (m) 0.3 MASS 4.5 Approx.(kg) 5 7 1 0.5 0.75 1.0 5.6 7.0 Z 8.3 L= (to order) 1 Z Gas flow Tube (50A SCH40) 5 14 4 - Rc 1/4 with plug int thd. 180 Flow guide tube (for high particulate with cover) Blow down air inlet 8 - 19 MTG. holes Select an upper port to avoid the condensation in the piping 67 29 .5 Flange: JIS 5K80A FF (175) ZFK MTG. position 50 Packing 4-6E3 5 7 1 ZFK5R (800) 790 Gas outlet 30 Cord 11th 3 L (m) 0.3 MASS 7.1 Approx.(kg) 5 7 0.5 0.75 1.0 L= 9.0 11.4 13.6 (to order) Gas flow Protection tube (65A SCH40) (38) Tube (50A SCH40) 11 ZFK, ZRM Converter (ZRM) Panel flush mounting Pipe mounting 88.6 204 193 50 220 200 6 18 2B pipe for mounting ( 60.5 0.5mm) Cable gland 194 35 9 EXTERNAL CONNECTION DIAGRAM 4-core Cable 1 55 2 3 4 2-core Cable 6 5 3 4 5 6 7 8 9 10 11 12 1 2 13 14 37 28 176 Wiring port, 3- 23. with rubber bushing A.OUT AUX.IN Zr.SIG Output signal Auxiliary input Element input Thermo- Maintenance Blow contact couple contact Heater power supply 17 19 21 27 28 N L 15 16 18 20 MENT T.C 22 23 24 BLOW 25 26 HEAT PE DXA DXB G D11 D12 DI ZV COM SV SG FG COM Serial Contact input POWER Calibrating gas communication contact Power supply Note (1) : The numbers 1 through 6 denote detector terminal No. for exclusive - special cables. (2) : M3 terminal screws are used for the terminal block. Ejector (ZTA) 4-M16 bolt 190 30 42.7 Approx. L 170 P 217 Gas inlet L [mm] 500 750 1000 1500 40 Detector (ZFK2) Viewed from P direction 35 Blow -down air inlet (Rc1/4) Ejector air inlet (Rc1/4) 8 25 105 140 (JIS 10K65ARF) Caution on Safety 50 45 Cable gland (A15C) EXTERNAL CONNECTION DAIAGRAM 1 Ejector air outlet (Rc1/4) 40 2 AC power supply 3 4 5 Heater temp.drop alam *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan