MEANWELL RKP-CMU1

RKP-CMU1
1U Rack Control and Monitoring Unit
Description :
RKP-CMU1 is a fully digitalized control / monitoring unit for the
RCP-2000 power system. Equipped with USB, RS-232, and ethernet
interface, it can be connected locally to PC to execute the control
and monitoring tasks. With built-in 4 configurable relay contacts,
users can flexibility monitor specific events or alarms and react
suitable action accordingly.
Features :
1U low profile/19-inch rack mounting
Control and monitor up to 32 RCP-2000 units
Front panel LCD and buttons for on-site service without PC
USB-, RS-232 or Ethernet interface for PC connection locally or remote
monitoring and control via GSM modem
Alarm/event log with time and date
Windows-based PC communication software
Easy wire connections on rear side
4 user programmable relay outputs for traditional remote monitoring or
warning
3 years warranty
SELECTION GUIDE
Single unit: RKP-CMU1
Rack: RKP-1U I -CMU1
I: AC Inlet (IEC320-C20)
T: Terminal block
SPECIFICATION
MODEL
OUTPUT
RKP-1U
DIGITAL METER
Display the DC output voltage, current, and internal temperature of each RCP-2000 unit
CONTROL OUTPUT
PM Bus signal for each RCP-2000 unit
LED INDICATOR
Green: Power on
RELAY CONTACT
4 user programmable relay, relay contact rating(max.): 30V/1A resistive
VOLTAGE RANGE
INPUT
FUNCTION
Red:Alarm
Note.3 12 ~ 15VDC
CURRENT
1A/12VDC
MONITORING INPUTS
PM Bus signal for each RCP-2000 unit
DISPLAY
MONITOR
LCD 16x2 Alphanumeric Matrix Display / PC Web Page Display
CONTROL
Output Voltage, Current Limit, ON/OFF
WORKING TEMP.
0.8A/15VDC
Output Voltage / Load Current / Temperature / Input Voltage
USB, RS-232, Ethernet
COMM. INTERFACE
ENVIRONMENT
RKP-CMU1
-CMU1
Note.1 -25 ~ +70
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
VIBRATION
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
Design refer to TUV EN60950-1
UL60950-1, TUV EN60950-1 approved
O/P-FG:0.7KVDC
WITHSTAND VOLTAGE Note.2 I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.7KVDC
SAFETY &
ISOLATION RESISTANCE Note.2 I/P-O/P, I/P-FG,O/P-FG:100M Ohms / 500VDC / 25 / 70% RH O/P-FG:100M Ohms / 500VDC / 25
EMC
EMC EMISSION
Compliance to EN55022 (CISPR22) Conduction Class B, Radiation Class A ; EN61000-3-2,-3
SAFETY STANDARDS
OTHERS
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-1(EN50082-2), light industry level, criteria A
MTBF
110.5K hrs min.
DIMENSION
486.6*350.8*44mm (L*W*H)
4.4Kg; 3pcs/14.2Kg/2.67CUFT
PACKING
NOTE
MIL-HDBK-217F (25
/ 70% RH
)
147.5*127*41mm (L*W*H)
0.8Kg; 16pcs/13.8Kg/0.79CUFT
1. LCD may freeze under -10 .
2. SK100 and all of signal connectors (except CN502, CN503, and USB port) are considered as O/P.
3. Recommanded use MEAN WELL power adaptor series: GS12, GS15, GS18, GE12, GE18.
File Name:RKP-CMU1-SPEC 2012-03-20
RKP-CMU1
1U Rack Control and Monitoring Unit
Mechanical Specification (Single Unit)
Case No. 959A
Unit:mm
40.9
18
78
2-M3 L=6mm
147.5
41
1
DC IN
SK100
1
8
8
1
1
RS-232
JK1
TB4
12
6
9
5
1
CN502
2
RY1 RY2 RY3 RY4
8
1
1 3 5 7
2 4 6 8
127
CN503
JK500
M E A N WELL
40.9
78
40.9
23
78
2-M3 L=6mm
71
USB
Ethernet
Fig1
2-M3 L=6mm
BOTTOM VIEW
File Name:RKP-CMU1-SPEC 2012-03-20
RKP-CMU1
1U Rack Control and Monitoring Unit
Mechanical Specification (Rack System)
Case No. 959D
Unit:mm
Fig1
14
25
1
13
Fig2
USB
1
CN500
SK100
DC IN
Fig3
14
25
+
_
A
B
1
13
RKP-1UT-CMU1
2
TB4
RY1 RY2 RY3 RY4
ADDRESS
SWITCH
ADDRESS
SWITCH
Ethernet
1 3 5 7
2 4 6 8
1
RS-232
JK500 CN503 CN502
CN500
SK100
14
25
+
_
FG
A
B
1
JK1
RS-232
1 3 5 7
2 4 6 8
IEC320-C20
1
8
Mounting Bracket
Ethernet
8
1
1
TB4
13
RKP-1UI-CMU1
DC IN
N
L
FG
ADDRESS
SWITCH
8
RY1 RY2 RY3 RY4
N
L
ADDRESS
SWITCH
8
8.2
10
JK1
8.2
10
JK500 CN503 CN502
IEC320-C20
440
125
SVR1
24
50
50
125
125
3-M5 L=6mm
3-M5 L=6mm
350.8
125
SVR1
22
22
Module A
M E A N WELL
10.2
USB
DC OK
DC OK
466.1
7.42
44
7.1 7
Module B
Air flow
direction
29.48
46
483.6
File Name:RKP-CMU1-SPEC 2012-03-20
RKP-CMU1
1U Rack Control and Monitoring Unit
CN500 Pin No. Assignment
Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions
Pin No.
1
2
3
4
5
Assignment
ON/OFF-A
AC-OK-A
DC-OK-A
PV-A
T-ALARM-A
Pin No.
Pin No.
Assignment
FAN FAIL-A
ON/OFF-B
AC-OK-B
DC-OK-B
PV-B
6
7
8
9
10
Assignment
T-ALARM-B
FAN FAIL-B
+5V-AUX
+12V-AUX
GND-AUX
11
12
13
14
15
Pin No.
16~21
22
23
24
25
Assignment
N.C.
+S
-S
+V
-V
JK1 Pin No. Assignment
Connector Pin No. Assignment(JK1) : RJ45 8 positions
Pin No.
1
2
3
Assignment
DA
DB
-V
Pin No.
4
5
6
Assignment
CONTROL
NC
SDA
Pin No.
7
8
Assignment
SCL
GND-AUX
CN502 Pin No. Assignment
Connector Pin No. Assignment(CN502) : D-type Male 9 positions
Pin No.
1,4,6,7,8,9
2
Assignment
NC
RXD
Pin No.
3
5
Assignment
TXD
GND-FG
CN503 Pin No. Assignment
Connector Pin No. Assignment(CN503) : HRS DF11-8DP-2DS or equivalent
Pin No.
1
2,4,6,8
3
Assignment
D-IN1
GND-FG
D-IN2
Pin No.
5
7
Assignment
D-IN3
D-IN4
JK500 Pin No. Assignment
Connector Pin No. Assignment(JK500) : RJ45 8 position
Pin No.
1
2
3
Assignment
TX+
TXRX+
Pin No.
4,5,7,8
6
Assignment
NC
RX-
TB4 Pin No. Assignment
Connector Pin No. Assignment(TB4) : DECA MX422-25412 or equivalent
Pin No. Assignment
1
Relay1-NO
2
Relay1-NC
3
Relay1-COM
Pin No.
4
5
6
Assignment
Relay2-NO
Relay2-NC
Relay2-COM
Pin No.
7
8
9
Assignment
Relay3-NO
Relay3-NC
Relay3-COM
Pin No.
10
11
12
Assignment
Relay4-NO
Relay4-NC
Relay4-COM
SK100 Pin No. Assignment
Connector Pin No. Assignment(SK100): Schurter 4840.2201 or equivalent
Pin No.
1
Assignment
+VIN
Pin No.
2
Assignment
-VIN
File Name:RKP-CMU1-SPEC 2012-03-20
1U Rack Control and Monitoring Unit
RKP-CMU1
CN500 IN/OUT Connector pins function description
Pin No.
Function
1,7
ON/OFF
2,8
3,9
4,10
AC-OK
DC-OK
PV
5,11
T-ALARM
6,12
FAN FAIL
13
+5V-AUX
14
+12V-AUX Auxiliary voltage output, 10.8 ~ 13.2V, referenced to GND- AUX (pin 15). The maximum load current is 0.8A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
GND-AUX Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Not used.
N.C.
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted
+S
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
15
16~21
22
23
-S
24
25
+V
-V
Description
Each unit can separately turn the output on and off by electrical signal or dry contact between ON/OFF A,B(pin 1,7) and +5V-AUX(pin 13).
Short: ON, Open:OFF. (Note.2)
Low : When the input voltage is 87Vrms. High : when the input voltage in 75Vrms. (Note.2)
High : When the Vout 80 5%. Low : When Vout 80 5%. (Note.2)
Connection for output voltage trimming. The voltage can be trimmed within its defined range. (Note.1)
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. (Note.2)
High : When the internal fan fail. Low : When the internal fan is normal. (Note.2)
Auxiliary voltage output, 4.5 ~ 5.5V, referenced to GND- AUX (pin 15). The maximum load current is 0.3A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Positive output voltage. For local sense use only, can't be connected directly to the load.
Negative output voltage. For local sense use only, can't be connected directly to the load.
JK1 IN/OUT Connector pins function description
Pin No.
Function
1,2
DA,DB
3
-V
4
CONTROL
Description
Differential digital signal for parallel control. (Note.1)
Negative output voltage. For parallel control, can't be connected directly to the load.
Remote ON/OFF control pin used in the PMBus interface. (Note.2)
5
NC
Not use.
6
SDA
Serial Data used in the PMBus interface. (Note.2)
7
SCL
8
GND-AUX
Serial Clock used in the PMBus interface. (Note.2)
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Note.1: Non-isolated signal, referenced to the output terminals (-V).
Note.2: Isolated signal, referenced to GND-AUX.
CN502 IN/OUT Connector pins function description
Pin No.
Function
1,4,6,7,8,9
NC
2
RXD
Receive data used in the RS-232 interface.
3
TXD
Transmit data used in the RS-232 interface.
4
GND-FG
Description
Not used.
RS-232 common GND. This signal connects to FG and isolated from -V and GND-AUX.
CN503 IN/OUT Connector pins function description
Pin No.
1,3,5,7
2,4,6,8
Function
Description
D-IN1
D-IN2
D-IN3
D-IN4
GND-FG
The isolated digital input signal and referenced to GND-FG.
Open form GND-FG or +5V : Logic "1" input to RKP-CMU1
short to GND-FG or 0V : Logic "0" input to RKP-CMU1
Common GND for D-IN. This signal connects to FG and isolated from -V and GND-AUX.
JK500 IN/OUT Connector pins function description
Pin No.
Function
1,2
TX+/TX-
3,6
RX+/RX-
4,5,7,8
NC
Description
Transmit data used in the Ethernet interface.
Receive data used in the Ethernet interface.
Not used.
File Name:RKP-CMU1-SPEC 2012-03-20
RKP-CMU1
1U Rack Control and Monitoring Unit
TB4 IN/OUT Connector pins function description
Pin No.
Function
1,4,7,10
Relay-NO
Description
Normal-open contact of programmable relay.
Relay-NC
Normal-close contact of programmable relay.
2,5,8,11
3,6,9,12
Relay-COM Common for NO/NC contact.
Note: Relay contact rating (max.) : 30V/1A resistive.
SK100 IN/OUT Connector pins function description
Pin No.
Function
1
+VIN
Description
Positive input voltage for RKP-CMU1.
2
-VIN
Negative input voltage for RKP-CMU1.
Function Manual
1.Communication interface
RKP-CMU1 can control and monitor RCP-2000 parameter via PMBus communication, and PC can manage the whole system by using USB, RS232, or
Ethernet to connect to RKP-CMU1.
USB
PMBus
RS-232
Ethernet
2.RCP-2000 Monitoring and control
RKP-CMU1 can monitor parameter of RCP-2000 such as output voltage, output current, internal temperature, status, serial number, and firmware
version. It also can turn RCP-2000 on/off together or separately by using "ON/OFF" pin in CN500 or PMBus "CONTROL" pin in JK1 or PMBus
"OPERATION" command, shows below. By using PMBus, output voltage and over load protection of RCP-2000 are adjustable.
RKP-1U
ON/OFF pin
PMBus
CONTROL pin
PMBus
OPERATION command
RCP-2000
Output status
Connect to +5V-AUX
Open
80h (ON)
ON
Connect to +5V-AUX
Connect to +5V-AUX
80h (ON)
ON
Open
Open
80h (ON)
OFF
Open
Connect to +5V-AUX
80h (ON)
ON
Don't care
Don't care
00h (OFF)
OFF
3.Real time clock, Data Log and Event Log
RKP-CMU1 has a build-in real time clock data to display actual date/time and for log time stamp. The data logger is designed to store operating data
when the systems works. It has 1000 recodes and the interval of log is programmable from 1 to 60 minutes. The event log store system condition
when alarm occur and remove. There are 600 records in event log.
4.Programmable relay
There are 4 relays and each relay has normal open, normal close and common contact in terminal block. Their active conditions are programmable for
flexible application, like charger and generator control, shows below.
Function
Alarm
Sub-function
1.Any alarm
2.OVP
3.OLP
4.Short circuit
5.OTP
6.High Temperature
7.AC fail
8.Fan lock
9.PMBus error
PSU
Parameter
N/A
N/A
File Name:RKP-CMU1-SPEC 2012-03-20
RKP-CMU1
1U Rack Control and Monitoring Unit
Function
Sub-function
1.Immediately
2.Delay
1.Immediately
2.Delay
D-IN1 ~ D-IN4
PSU ON
PSU OFF
Digital input
PSU
Parameter
0 sec.
1 ~ 600 sec.
0 sec.
1 ~ 600 sec.
N/A
PSU0~ 31
PSU0~ 31
N/A
5.PMBus communication interface
RKP-CMU1 integrates PMBus into RCP-2000 control. The supported PMBus commands are shown below.
Command
Name
Command
Code
Transaction
Type
# of data
Bytes
Description
01h
OPERATION
R/W Byte
1
Remote ON/OFF control
02h
ON_OFF_CONFIG
Read Byte
1
ON/OFF function configuration
19h
CAPABILITY
Read Byte
1
Capabilities of a PMBus device
20h
VOUT_MODE
R Byte
1
Define data format for output voltage
(format: Linear, N= -9)
21h
VOUT_COMMAND
R Word
2
Output voltage setting value
(format: Linear, N= -9)
22h
VOUT_TRIM
R/W Word
2
Output voltage trimming value
(format: Linear, N= -9)
46h
IOUT_OC_FAULT_LIMIT
R/W Word
2
Output overcurrent setting value
47h
IOUT_OC_FAULT_RESPONSE
R Byte
1
Define protection and response when an
output overcurrent fault occurred
79h
STATUS_WORD
R Word
2
Summary status reporting
7Ah
STATUS_VOUT
R Byte
1
Output voltage status reporting
7Bh
STATUS_IOUT
R Byte
1
Output current status reporting
7Ch
STATUS_INPUT
R Byte
1
AC inpit voltage status reporting
7Dh
STATUS_TEMPERATURE
R Byte
1
Temperature status reporting
80h
STATUS_MFR_SPECIFIC
R Byte
1
Manufacture specific status reporting
81h
STATUS_FANS_1_2
R Byte
1
Fan1 and 2 status reporting
88h
READ_VIN
R Word
2
AC input voltage reading value
(format: Linear, N=-1)
8Bh
READ_VOUT
R Word
2
Output voltage reading value
(format: Linear, N= -9)
8Ch
READ_IOUT
R Word
2
Output current reading value
(format: Linear, N= -3)
8Dh
READ_TEMPERATURE_1
R Word
2
Temperature 1 reading value
(format: Linear, N= -3)
90h
READ_FAN_SPEED_1
R Word
2
Fan speed 1 reading value
(format: Linear, N= 4)
91h
READ_FAN_SPEED_2
R Word
2
Fan speed 2 reading value
(format: Linear, N= 4)
98h
PMBUS_REVISION
R Byte
1
The compliant revision of the PMBus
(default: 11h for Rev. 1.1)
99h
MFR_ID
Block Read
12
Manufacturer's name
9Ah
MFR_MODEL
Block Read
12
Manufacturer's model name
9Bh
MFR_REVISION
Block Read
6
Firmware revision
9Ch
MFR_LOCATION
Block R/W
3
Manufacturer's factory location
9Dh
MFR_DATE
Block R/W
6
Manufacture date. (format: YYMMDD)
9Eh
MFR_SERIAL
Block R/W
12
Product serial number
File Name:RKP-CMU1-SPEC 2012-03-20