FUJI EDSX5-97H

ABSOLUTE PRESSURE TRANSMITTER (DIRECT MOUNT TYPE)
FKH...5
DATA SHEET
The FCX–AIII absolute pressure transmitter (Direct mount
type) accurately measures absolute pressure and transmits
proportional 4 to 20mA signal.
The transmitter utilizes the unique micromachined capacitive silicon sensor with state-of-the-art microprocessor
technology to provide exceptional performance and
functionality.
FEATURES
1. High accuracy
0.2% accuracy for all calibrated spans is the standard
feature for all AP models covering 8.125 to 3000kPa {0.13
to 30bar} high pressure range. Fuji's micro-capacitance
silicon sensor assures this feature for all suppressed
calibration ranges without additional adjustment.
2. Minimum inventory
Electronics unit, communication module, local indicators
and electronics housing are interchangeable among all
FCX– AIII models.
3. Fuji/HART bilingual communication module
The communication module is "bilingual" to speak both
Fuji proprietary protocol and HART. Any HART compatible
devices can communicate with FCX– AIII series transmitters.
4. Application flexibility
Example features that render the FCX– AIII suitable for
almost any process applications includes:
— Full range of hazardous location approvals
— Built-in RFI filter and lightning arrester
— 5-digits LCD meter
— The maximum span of each sensor can be converted
to in different units using below factors.
5. Burnout current flexibility (Under Scale: 3.2 to 4.0mA,
Over Scale: 20.0 to 22.5mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator (HHC) to comply with NAMUR
NE43.
SPECIFICATIONS
Functional specifications
Type:
4 to 20mA with digital signal
Service:
Liquid, gas, or vapour
Span, range, and overrange limit:
Type
Span limit [kPa abs] {bar abs}
Min.
FKH 02
FKH 03
FKH 04
Max.
8.125
{0.08125}
31.25
{0.3125}
187.5
{1.875}
Output signal:
Power supply:
130
{1.3}
500
{5}
3000
{30}
Range limit
[kPa abs]
{bar abs}
Overrange
limit
[MPa] {bar}
0.5
{5}
1.5
{15}
9
{90}
0 to 130
{0 to 1.3}
0 to 500
{0 to 5}
0 to 3000
{0 to 30}
4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal.
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester
EDSX5-97h
Date
Aug. 10, 2011
FKH...5
Load limitations: see figure below
[Ω]
Load resistance
2000
1500
1474Ω
R=
E-10.5
(Imax+0.9)x10-3
1000
577Ω
Operating
area
500
24V
250
0
10
16.35
10.5V
Power voltage (DC)
45V
50
E[ V ]
Note: For communication with FXW, min. of 250  required.
Hazardous locations: SEE TABLE 3
Zero/span adjustment:
Zero and span are adjustable either from
the HHC(1). Zero is also adjustable externally from the adjustable screw.
Damping:
Adjustable electrical damping
The time constant is adjustable between
0.06 to 32.0 seconds.
Zero elevation/suppression:
Zero may be elevated within the specified
range limit of each sensor model.
Normal/reverse action:
Configurable from HHC(1).
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure,
the analog signal will be driven to either
“Output Hold”, “Output Overscale” or
“Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just
before failure happens.
“Output Overscale”:
Adjustable within the range 20.0mA to
22.5mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2mA to
4.0mA from HHC(1)
3.2
4
20
22.5 [mA]
Over scale
Burnout
Normal operating range
Under scale
Probable under range
Burnout
Temperature limit: Ambient: −40 to +85°C
(−20 to +80°C for LCD indicator)
(−40 to +60°C for arrester option)
For explosionproof units (flameproof or
intrinsic safety), ambient temperature
must be within the limits specified by
each standard.
Process: −40 to +85°C for silicone fill
sensor
Storage: −40 to +90°C
Humidity limit: 0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following items can
be remotely displayed or configured.
Note: HHC’s version must be higher than
7.0 (or FXW
1– 4), for FCX AIII.
Local configurator with LCD display (option):
Local confi gurator with 3 push button
and LCD display can support following
items.
Items
By communication By local configurator
with FXW
(with 3 push button)
Display
Set
Display
Set
Tag No.
v
v
v
v
Model No.
v
v
v
v
Serial No. & Software Version
v
—
v
—
Engineering unit
v
v
v
v
Range limit
v
—
v
—
Measuring range
v
v
v
v
Damping
v
v
v
v
Output mode
v
—
v
—
Burnout direction
v
v
v
v
Calibration
v
v
v
v
Output adjust
—
v
—
v
Data
v
—
v
—
Self diagnoses
v
—
v
—
Printer (In case of FXW with
printer option)
v
—
—
—
External switch lock
v
v
v
v
Transmitter display
v
v
v
v
Linearize
v
v
—
—
Rerange
v
v
v
v
Saturate current
v
v
v
v
Write protect
v
v
v
v
History
– Calibration history
– Ambient temperature history
v
v
v
—
v
v
v
—
Probable over range
EMC Conformity: EN61326-1: 2006
Output Limits comforming the NAMUR NE43 by order.
(Note)
2
(1) HHC: Hand Held Communicator
Performance specifications
Accuracy rating: (including linearity, hysteresis, and repeatability).
For spans greater than 1/10 of URL: ±0.2% of span
For spans below 1/10 of URL:
0.1 x URL
± (0.1 + 0.1 span
) % of span
Stability:
±0.2% of upper range limit (URL) for 10
years
(In case of 6th digit code "3", "4")
Temperature effect:
Effect per 28°C change between the
limits of −40°C and +85°C
URL
Zero shift: ± (0.4 + 0.2 span )%/28°C
URL
Total effect: ± (0.475 + 0.2 span )%/28°C
Overrange effect: Zero shift, 0.3% of URL for any overrange
to maximum limit
Update rate:
60 msec
Step response: Time constant. 0.08 s (at 23°C)
Dead time: about 0.12 s
(without electrical damping)
Mounting position effect:
Zero shift, less than 0.1kPa for a 10° tilt
in any plane.
No effect on span. This error can be
corrected by adjusting zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100M at 500V DC.
Internal resistance for external field indicator:
12 or less
Physical specifications
Electrical connections:
G1/2, 1/2-14NPT, Pg13.5, or M20 x 1.5
conduit, as specified.
Process connections:
1/2-14 NPT, 1/4-18NPT, Rc1/2 or Rc1/4
as specified.
Process-wetted parts material:
Material
code
(7th digit Process cover
in "Code
symbols")
V
316 stainless
steel
Diaphragm
Wetted
sensor body
316L stainless 316 stainless
steel
steel
Vent/drain
316 stainless
steel
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy (standard), fi nished
with polyester coating, as specified.
Fill fluid: Silicone oil
Mounting bracket: 304 stainless steel
Environmental protection:
IEC IP67 and NEMA 4X
Mounting:
On 60.5mm (JIS 50A or 2B) pipe using
mounting bracket, direct wall mounting,
or direct process mounting.
Mass{weight}:
Transmitter approximately 2.2kg without
options.
Add; 0.5kg for mounting bracket
3
FKH...5
Optional features
Indicator:
A plug-in turnable analog indicator (2.5%
accuracy)
An optional 5 digits LCD meter is also
available.
Local configurator with LCD display:
An optional 5 digits LCD meter with 3
push buttons can support items as using
communication with FXW.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity: 4KV (1.250µs)
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
for oxygen or chlorine measurement.
NACE specification:
Metallic materials for all pressure boundary parts comply with NACE MR-01-75.
Customer tag:
A stainless steel tag for customer tag
data is wired to the transmitter.
4
ACCESSORIES
Hand held communicator:
(Model FXW, refer to Data Sheet No.EDS
8-47)
CODE SYMBOLS
1 2 3 4 5 6 7 8
F KH
0
9 10 11 12 13
5
14 15
21
Description
0
Connections
5
6
7
8
Conduit connection
Case type
Process connection
G1/2
1/2-14NPT
Pg 13.5
M20 x 1.5
T type
T type
T type
T type
1/2-14NPT
1/2-14NPT
1/2-14NPT
1/2-14NPT
Span limit
[kPa abs] {bar abs}
8.125…130 {0.08125…1.3}
31.25…500 {0.3125…5}
187.5…3000 {1.875…30}
2
3
4
Material
Process cover
316 stainless steel
V
Diaphragm
316L stainless steel
Wetted cell body
316 stainless steel
Indicator and arrester
Indicator
None
Analog, 0 to 100% linear scale
Analog, custom scale
None
Analog, 0 to 100% linear scale
Analog, custom scale
Digital, 0 to 100% linear scale
Digital, custom scale
Digital, 0 to 100% linear scale
Digital, custom scale
Digital, 0 to 100% linear scale
(Local configurator unit with LCD displey)
Digital, Custom scale
(Local configurator unit with LCD displey)
Digital, 0 to 100% linear scale
(Local configurator unit with LCD displey)
Digital, Custom scale
(Local configurator unit with LCD displey)
A
B
D
E
F
H
L
P
Q
S
1
2
4
5
Arrester
None
None
None
Yes
Yes
Yes
None
None
Yes
Yes
None
None
Yes
Yes
Approvals for hazardous locations
None (for ordinary locations)
TIIS, Flameproof (Cable gland seal) (*1)
TIIS, Intrinsic safety
FM, Flameproof (or explosionproof) (*4)
FM, Intrinsic safety and nonincentive
FM Combined of flameproof and intrinsic safety (*4)
ATEX Flameproof (*3)
ATEX Intrinsic safety
ATEX Type n
ATEX Combined of flameproof and intrinsic safety (*3)
IECEx Scheme, Flameproof (*3)
IECEx Scheme, Intrinsic safety
CSA, Flameproof (or explosionproof) (*4)
CSA, Intrinsic safety and nonincentive
NEPSI, Flameproof (or exprosionproof)
NEPSI, Intrinsic safety
NEPSI, Combined of flameproof and intrinsic safety
A
C
G
D
H
V
X
K
P
M
R
T
E
J
F
S
U
(Note 1)
(Note 4)
(Note 4)
(Note 3)
(Note 3)
(Note 3)
(Note 4)
Mounting bracket
None
Yes (stainless steel)
A
C
Optional specification
Stainless tag
None
(*5)
Yes
Y
B
(Note 5)
Special applications and fill fluid
Y
G
N
L
(*1)
(*3)
(*4)
(*5)
(*6)
Filled liquid
None (standard)
Degreasing
NACE specification
Silicon oil
Silicon oil
Silicon oil
Process adaptor
None (1/2 -14NPT)
Rc1/4
Rc1/2
1/4-18NPT
Y
A
B
C
Note1:
Note3:
Note4:
Note5:
Note6:
Treatment
<Other options> (*6)
Instruction manual unattached
(Note 6)
Available for 4th digit code "5".
Available for 4th digit code "6", "8".
Available for 4th digit code "6".
Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required select "Yes".
If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached.
5
FKH...5
OUTLINE DIAGRAM (Unit:mm)
IN CASE OF 4TH DIGIT CODE "5, 7, 8"
IN CASE OF 4TH DIGIT CODE "6"
2 HOLES 9 DIA.
MTG. PIPE JIS 50A (2B)
ZERO ADJ. SCREW
10
EARTH TERMINAL
8
17
100
ZERO
212
"B" CONDUIT CONN.
WITH ANALOG IND.
(21)
(11)
WITH DIGITAL IND.
127
20
DETAIL "B"
DETAIL "A"
DETAIL "D"
φ81
φ18
F
φ15
K
E
16
φ6
70
D
"A" PRESS. CONN.
MTG. BLACKET
SEE TABLE2
85
4th digit of the
code symbols
"D" ADAPTER (OPTION)
SEE TABLE2
U-BOLT M8
J
SEE TABLE2
SEE TABLE1
Conduit conn.
D
E
F
5
G 1/2
18
2
6
1/2-14NPT
16
4
7
Pg13.5
10.5
4.5
8
M20×1.5
16
4
ADAPTER
CONN.(L)
Rc 1/2
NPT 1/4
Rc 1/4
G
38
H
31
J
27
K
16
18
25
22
8
TABLE 2
TABLE 1
H
108
L
G
27
1/2-14NPT
35
170
OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN)
CONNECTION DIAGRAM
<SS TAG PLATE>
10th digit code C (Cable gland type)
NOTE1)
G1/2
φ13
φ33.5
−/CK− CK+
75
+
DETAIL C
106
17
19
20
"C" CONDUIT CONN.
G1/2
CABLE GLAND
NOTE1) IN CASE OF 10TH CODE“C”
, φ11 CABLE IS SUITBLE.
6
TABLE 3
Authorities
ATEX
Authorities
Intrinsic safety
Ex II 1 G
Ex ia IIC T5 Tamb = –40°C to +50°C
Ex ia IIC T4 Tamb = –40°C to +70°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
Factory
Mutual
Tamb
A,B,D
Y,G,N
−40°C to +85°C
L,P,1,2
Y,G,N
−20°C to +80°C
Q,S,4,5
Y,G,N
−20°C to +60°C
E,F,H
Y,G,N
−40°C to +60°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Pi=0.66W,
Ci=35.98nF, Li=0.694mH
CSA
Ex II 2 GD
Ex d IIC T6 IP66/67 T85°C
Tamb = −40°C to +65°C
Ex d IIC T5 IP66/67 T100°C
Tamb = −40°C to +85°C
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Note) “Seal Not Required” enclosure is allowed.
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester),
Ci=36nF (With Arrester),Li=0.6mH (Without analog meter),
Li=0.7mH (With analog meter)
Ex ia IIC T4
Tamb max = +60°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=38.4nF, Li=0.694mH
IECEx
Scheme
Ex ia IIC T4
Tamb = –40°C to +70°C
Ex ia IIC T5
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
Ex ia IIC T4
Ex d IIB+H2 T6 / Ex ia IIC T4
Model code
9th digit
13th digit
IECEx
Scheme
Ex d IIC T5 IP66/67
Tamb = −40°C to +85°C
Ex d IIC T6 IP66/67
Tamb = −40°C to +65°C
TIIS
Ex do IIB+H2 T4
Tamb max = +60°C
Maximum process temp. = +120°C
NEPSI
Ex d IIB+H2 T6
Tamb = −40°C to +60°C
Y,G,N
−40°C to +85°C
L,P,1,2
Y,G,N
−20°C to +80°C
Q,S,4,5
Y,G,N
−20°C to +60°C
E,F,H
Y,G,N
−40°C to +60°C
Ex II 3 GD
EEx nL IIC T5 Tamb = −40°C to +50°C
EEx nL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=25.18nF, Li=0.694mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
EEx nAL IIC T5 Tamb = −40°C to +50°C
EEx nAL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W,
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Tamb
A,B,D
Type n
Nonincendive
Authorities
ATEX
TIIS
NEPSI
ATEX
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
Model code
9th digit
13th digit
Flameproof
Factory
Mutual
(pending)
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
9th digit
13th digit
Entity Parameters:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
CSA
Tamb
A,B,D
Y,G,N
−40°C to +85°C
L,P,1,2
Y,G,N
−20°C to +80°C
Q,S,4,5
Y,G,N
−20°C to +60°C
E,F,H
Y,G,N
−40°C to +60°C
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Ci=25.18nF (Without Arrester),
Ci=35.98nF (With Arrester), Li=0.694mH
7
FKH...5
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan